Space Input Data
TALAL VILLA 09/12/2017
555 08:44PM
FF BED 1
1. General Details:
Floor Area ............................................................... 46.5 m
Avg. Ceiling Height ................................................... 3.1 m
Building Weight .................................................... 341.8 kg/m
1.1. OA Ventilation Requirements:
Space Usage .............. HOTEL: Bedroom/living room
OA Requirement 1 .................................................... 2.5 L/s/person
OA Requirement 2 .................................................. 0.30 L/(s-m)
Space Usage Defaults ........... ASHRAE Std 62.1-2004
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type .............................. Recessed (Unvented) Occupancy ............................................................... 5.0 People
Wattage ................................................................ 40.00 W/m Activity Level ...................................... Sedentary Work
Ballast Multiplier ..................................................... 1.15 Sensible .................................................................. 82.1 W/person
Schedule ............................................................. 24 HR Latent ..................................................................... 79.1 W/person
Schedule ............................................................. 24 HR
2.2. Task Lighting: 2.5. Miscellaneous Loads:
Wattage .................................................................. 0.00 W/m Sensible ....................................................................... 0 W
Schedule .............................................................. None Schedule ............................................................. 24 HR
Latent ........................................................................... 0 W
Schedule ............................................................. 24 HR
2.3. Electrical Equipment:
Wattage ................................................................ 190.0 Watts
Schedule ............................................................. 24 HR
3. Walls, Windows, Doors:
Exp. Wall Gross Area (m) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 16.0 5 0 0
E 18.0 0 0 0
3.1. Construction Types for Exposure S
Wall Type ........................................................ SINGLE WALL
1st Window Type ..................................................... WINDOW
3.2. Construction Types for Exposure E
Wall Type ........................................................ SINGLE WALL
4. Roofs, Skylights:
Exp. Roof Gross Area (m) Roof Slope (deg.) Skylight Qty.
H 42.0 0 0
4.1. Construction Types for Exposure H
Roof Type ..................................................................... ROOF
5. Infiltration:
Design Cooling ....................................................... 0.00 ACH
Design Heating ....................................................... 0.00 L/s
Energy Analysis ...................................................... 0.00 L/s
Infiltration occurs only when the fan is off.
6. Floors:
Type ........................ Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ......................................... Wall Partition (No partition data)
Area ........................................................................ 20.0 m
U-Value ................................................................. 3.800 W/(m-K)
Uncondit. Space Max Temp ................................... 35.0 C
Ambient at Space Max Temp ................................. 46.0 C
Uncondit. Space Min Temp .................................... 24.0 C
Ambient at Space Min Temp .................................. 12.0 C
.
Hourly Analysis Program v4.50 Page 1 of 1