iDRAC Fan Speed Control

English | 繁體中文

Tests Container License

A fan controller for Dell PowerEdge servers. It sets the fan duty cycle through iDRAC IPMI OEM raw commands, then selects a fan-curve level using one or more temperature sources: ESXi NVMe SMART, iDRAC temperature sensors, or NVIDIA GPUs.

Caution

This program temporarily overrides Dell's automatic fan control. During initial setup, keep the iDRAC Web UI or a physical console available. Verify manual, restore, and diagnose before running auto for an extended period. If the server overheats, readings become unreliable, or behavior is abnormal, run restore immediately and stop the container.

How it works

flowchart LR
    TUI[make tui\nInteractive setup] --> ENV[.env\n600 permissions]
    ENV --> COMPOSE[Docker Compose]
    COMPOSE --> CTRL[fan-control.sh]
    CTRL --> IPMI[iDRAC / IPMI\nfan raw command]
    CTRL --> ESXI[ESXi\nesxcli SMART]
    CTRL --> SDR[iDRAC\nTemperature SDR]
    CTRL --> GPU[NVIDIA\nnvidia-smi]
    CTRL --> LOG[logs/fan_control.log\nhealthcheck]
Loading

The controller sends fan commands only to iDRAC; all temperature sources are read-only. When multiple sources are enabled, it uses the highest valid decision temperature. The GPU reading is adjusted by GPU_TEMP_OFFSET first, preventing the GPU package temperature from driving chassis fans unnecessarily fast.

iDRAC IPMI over LAN settings

Figure 1: Enabling IPMI over LAN in the iDRAC Web UI. The exact option name may vary by iDRAC firmware version.

Quick start: safe first-time setup with the TUI

Run the setup on the Docker host. The TUI requires no dialog, Python, or other additional packages. It is written in pure Bash, preserves comments from .env.example, updates files atomically, and sets file permissions to 600.

git clone https://github.com/DF-wu/iDRACFanSpeedControl.git
cd iDRACFanSpeedControl
make tui

The main menu looks like this. Each submenu writes changes back to .env, and the file location is shown again when you exit.

╭────────────────────────────────────────────────────────────╮
│              iDRAC Fan Control · Setup TUI                │
╰────────────────────────────────────────────────────────────╯

  1) Quick setup wizard       6) Safety, timing, and logging
  2) iDRAC / IPMI settings    7) Review redacted configuration
  3) Temperature source       8) Validate configuration
  4) ESXi NVMe source         9) Run read-only diagnostics
  5) Fan curve                0) Save and exit

For your first setup, select iDRAC sensors only and leave ESXi and GPU sources disabled. After completing the TUI, run:

make validate
docker compose run --rm idrac-fan-control diagnose
docker compose up -d
docker logs -f idrac-fan-control

diagnose is read-only and never sends fan raw commands. It checks iDRAC, every temperature source, the writable log path, and previews the fan level that would be selected. If you do not need a source, remove it from the TUI source preset instead of ignoring its errors.

To edit a different configuration file:

src/fan-control-tui.sh --config /path/to/staging.env

Create .env manually

cp .env.example .env
chmod 600 .env
$EDITOR .env

Minimal iDRAC-only example:

IDRAC_IP=192.0.2.10
IDRAC_ID=root
IDRAC_PASSWORD=change-me
OPERATION_MODE=auto
TEMPERATURE_SOURCES=idrac

Replace IDRAC_PASSWORD, the IP address, and the management network with real values. Values such as 192.0.2.*, change-me, and replace_with_* in .env.example are intentional placeholders and will be rejected by validate.

Command reference

Command Purpose Changes fan control
auto Continuously controls fans from the configured curve and restores automatic mode on exit when configured Yes
once Reads temperatures once, applies one decision, and exits Yes
manual 35 Sets a 35% duty cycle; without a number, uses MANUAL_FAN_SPEED Yes
restore Sends the Dell automatic fan-control command Yes (restore)
status Shows chassis status and raw temperature SDR data No
config Shows the effective configuration; passwords are shown only as set/length No
validate Checks values, placeholders, required commands, and source conditions No
diagnose Probes connections and temperature readings and shows a decision preview No
healthcheck Checks configuration and whether the auto-control log was updated recently enough No

With Docker Compose:

docker compose run --rm idrac-fan-control config
docker compose run --rm idrac-fan-control validate
docker compose run --rm idrac-fan-control diagnose
docker compose run --rm idrac-fan-control status
docker compose run --rm idrac-fan-control once
docker compose run --rm idrac-fan-control manual 35
docker compose run --rm idrac-fan-control restore

The local script accepts the same commands:

src/FanControlWithEsxiSmart.sh diagnose
src/FanControlWithEsxiSmart.sh config

Local execution requires bash, coreutils, ipmitool, and timeout. ESXi password authentication also requires sshpass. The Docker image includes these dependencies.

Safe startup sequence

sequenceDiagram
    participant U as Operator
    participant C as Controller
    participant D as iDRAC
    U->>C: validate
    C-->>U: Static configuration and dependency results
    U->>C: diagnose
    C->>D: mc info / SDR (read-only)
    D-->>C: Connection and temperatures
    C-->>U: Source checks + decision preview
    U->>C: manual 30
    C->>D: Set fan duty (controlled test)
    U->>C: restore
    C->>D: Dell automatic fan control
    U->>C: auto
Loading

Before unattended operation, confirm each item:

  1. IPMI over LAN is enabled in the iDRAC Web UI and the management network is reachable.
  2. The iDRAC account has the required permissions and its password is not a placeholder.
  3. manual 30 sets a low speed, manual 70 sets a conservative speed, and restore returns control to Dell automatic mode.
  4. Every enabled source reports [PASS] in diagnose; disable sources you do not use.
  5. Start with a conservative FAILSAFE_FAN_SPEED and RESTORE_AUTO_ON_EXIT=true.

Temperature sources and control decisions

TEMPERATURE_SOURCES is a comma-separated list containing esxi, idrac, and/or gpu. Sources can be combined, and the controller retains each source label for logging and diagnostics.

Source Reading Requirements Behavior on failure
idrac Readable sensors from ipmitool sdr type Temperature iDRAC IPMI Marks this source as failed
esxi esxcli storage core device smart get for the configured NVMe device SSH and DRIVE_DEVICE Marks this source as failed
gpu Temperature of each GPU reported by nvidia-smi NVIDIA Container Toolkit and driver Marks this source as failed
flowchart TD
    R[All valid readings] --> M{Select highest adjusted temperature}
    M --> L[temperature_level]
    L --> H{Lower than previous level?}
    H -- No --> S[Increase immediately or keep level]
    H -- Yes --> X{Below previous threshold - HYSTERESIS?}
    X -- No --> S2[Keep previous level]
    X -- Yes --> S3[Move to lower level]
    S --> F[Apply fan speed]
    S2 --> F
    S3 --> F
    R -. All sources fail .-> FS[FAILSAFE_FAN_SPEED]
Loading

The default curve is shown below. validate ensures that thresholds are strictly increasing, fan speeds never decrease, and the fail-safe speed is not lower than the critical speed.

Level Decision temperature Default fan speed
idle <65°C 25%
low 65–69°C 30%
medium 70–74°C 40%
high 75–79°C 50%
critical >=80°C 60%
failsafe All sources fail 70%

Moving to a lower fan level requires the temperature to fall by HYSTERESIS degrees below the relevant threshold, preventing repeated speed changes near a boundary. Moving to a higher level is immediate. The adjusted GPU value is GPU_TEMP - GPU_TEMP_OFFSET, with a minimum of 0°C.

Configuration reference

Connection and operating mode

Variable Default Description
IDRAC_IP Empty iDRAC hostname or IP; required for all fan commands
IDRAC_ID root iDRAC user
IDRAC_PASSWORD Empty Passed to ipmitool -E through the IPMI_PASSWORD environment variable; never appears in argv
IPMI_INTERFACE lanplus Usually left unchanged
IPMI_TIMEOUT / IPMI_RETRIES 5 / 2 Per-command timeout and retry count
OPERATION_MODE manual auto, once, or manual
DRY_RUN false Only for testing command construction; does not produce real readings
COMMAND_TIMEOUT 20 Maximum duration in seconds for SSH, IPMI, and GPU commands
CHECK_INTERVAL 60 Seconds between cycles in auto mode
RESTORE_AUTO_ON_EXIT true Restores automatic control when auto mode receives SIGTERM or exits

Temperature sources

Variable Default Description
TEMPERATURE_SOURCES esxi Comma-separated list of esxi,idrac,gpu
WITH_GPU_TEMP false Legacy compatibility switch; true appends gpu
GPU_TEMP_OFFSET 15 Offset subtracted from GPU temperature
ESXI_HOST / ESXI_USERNAME Empty / root ESXi SSH target
ESXI_PASSWORD Empty Used when no key is configured; never echoed by the TUI
ESXI_SSH_KEY Empty Preferred over password authentication when set
ESXI_SSH_PORT 22 SSH port (1–65535)
SSH_CONNECT_TIMEOUT 10 SSH connection timeout in seconds
SSH_STRICT_HOST_KEY_CHECKING accept-new yes, no, ask, or accept-new
DRIVE_DEVICE Empty Full ID returned by esxcli storage core device list
IDRAC_SENSOR_INCLUDE_REGEX Empty awk regex used to keep matching sensor names only
IDRAC_SENSOR_EXCLUDE_REGEX no reading|disabled|not readable Excludes invalid SDR entries

Fan curve, safety, and diagnostics

Variable Default Description
TEMP_LOW/MEDIUM/HIGH/CRITICAL 65/70/75/80 Strictly increasing thresholds in °C
FAN_SPEED_IDLE/LOW/MEDIUM/HIGH/CRITICAL 25/30/40/50/60 Values from 1–100% that must not decrease
HYSTERESIS 2 Degrees below the previous threshold required before lowering fan speed
FAILSAFE_ON_ERROR true Uses a conservative speed when all sources fail
FAILSAFE_FAN_SPEED 70 Must be greater than or equal to the critical speed
MANUAL_FAN_SPEED 35 Used by manual when no argument is provided
LOG_DIR / LOG_FILE /var/log/fan-control / fan_control.log Persistent state log
LOG_LEVEL INFO DEBUG adds command and source details but never logs passwords
HEALTHCHECK_MAX_AGE 0 0 means CHECK_INTERVAL*3 + COMMAND_TIMEOUT

Docker deployment and GPU support

The Compose configuration uses the GHCR image, host networking, and a ./logs volume by default:

docker compose pull
docker compose up -d
docker compose ps
docker inspect --format '{{.State.Health.Status}}' idrac-fan-control

The healthcheck verifies more than environment configuration. In OPERATION_MODE=auto, it also confirms that fan_control.log has been updated within HEALTHCHECK_MAX_AGE. If every data source fails while FAILSAFE_ON_ERROR=false, the control cycle does not write a success record and the container becomes unhealthy. This is an intentional safety signal.

GPU mode requires the NVIDIA Container Toolkit. Uncomment gpus: all in docker-compose.yml, then configure:

TEMPERATURE_SOURCES=idrac,gpu
GPU_TEMP_OFFSET=15

Verify the setup:

docker run --rm --gpus all nvidia/cuda:12.9.0-runtime-ubuntu24.04 nvidia-smi
docker compose run --rm idrac-fan-control diagnose

If GPU support is unnecessary, build locally without CUDA to reduce the image size:

docker build --build-arg BASE_IMAGE=ubuntu:24.04 -t idrac-fan-control:local .

Debugging, logs, and troubleshooting

Example normal log entry:

2026-07-18 03:12:10 [INFO] Control temp 68C -> low (30%). Sources: idrac:Inlet Temp=68C

For additional context, temporarily set:

LOG_LEVEL=DEBUG

Then inspect:

docker logs -f idrac-fan-control
tail -f logs/fan_control.log
docker compose run --rm idrac-fan-control diagnose

DEBUG logs targets, command types, source selection, and failure stages only. Passwords never appear in argv or the configuration summary. See docs/TROUBLESHOOTING.md for the complete symptom → check → fix table, and USAGE_GUIDE.md for routine and emergency operations.

Shortest recovery path for common problems:

# Restore Dell automatic control first whenever risk is uncertain
docker compose run --rm idrac-fan-control restore

# Inspect the effective configuration and dependency state
docker compose run --rm idrac-fan-control config
docker compose run --rm idrac-fan-control diagnose

Security and backups

  • Never commit .env, logs/, private keys, or incident dumps. The TUI sets configuration file permissions to 600.
  • Compose mounts the gitignored ./secrets directory read-only at /run/secrets. Use the in-container path for ESXi keys, such as /run/secrets/esxi_ed25519.
  • Prefer ESXI_SSH_KEY. When password authentication is required, the controller uses the SSHPASS environment variable with sshpass -e, keeping the password out of argv.
  • The iDRAC password is supplied through the IPMI_PASSWORD environment variable and ipmitool -E. The config command and TUI review show only whether it is set and its character count.
  • Keep iDRAC and ESXi on an isolated management network. Never expose IPMI over LAN to the public internet.
  • Before changing .env, keep an offline backup with 600 permissions and test restore.

Finding the ESXi drive identifier

ssh root@ESXI_HOST
esxcli storage core device list
esxcli storage core device smart get -d 't10.NVMe____full_identifier_string'

Copy the complete identifier into DRIVE_DEVICE; do not shorten it. If the SMART output does not include a numeric Drive Temperature, diagnose marks the ESXi source as failed instead of silently treating the error as 0°C.

Testing and quality gates

make test             # bash -n + 37 core assertions + 10 TUI assertions
make validate         # Check the current .env with Docker dependencies; does not change fans
make validate-example # DRY_RUN smoke test that does not require .env
make docker-build

Tests cover source normalization, SDR parsing, GPU offset, hysteresis, fail-safe behavior, curve/port/regex validation, credential redaction, health freshness, diagnostic previews, and safe round-tripping of TUI configuration files. Real hardware, ESXi SSH, and GPUs must still be verified with diagnose on your management network.

Project structure

.
├── src/
│   ├── FanControlWithEsxiSmart.sh   # Controller, validate, diagnose, and healthcheck
│   ├── fan-control-tui.sh           # Pure Bash setup TUI
│   └── setIdracFanSpeed.sh          # Compatibility wrapper for the legacy script
├── tests/
│   ├── fan-control.test.sh          # Core logic and safety tests
│   └── tui.test.sh                  # .env parser/writer tests
├── docs/
│   └── TROUBLESHOOTING.md           # Symptom-based troubleshooting guide
├── images/image.png                 # iDRAC IPMI settings screenshot
├── .env.example                     # Fully commented configuration template
├── docker-compose.yml
├── Dockerfile
├── Makefile
├── README.md                        # English documentation
├── README.zh-TW.md                  # Traditional Chinese documentation
└── USAGE_GUIDE.md

Compatibility and limitations

The project primarily targets Dell PowerEdge R730/R730xd-class systems with iDRAC 8 OEM fan raw commands. Other generations may be compatible, but identical behavior must not be assumed. Complete manual, restore, and diagnose checks before unattended operation. Actual iDRAC, ESXi, and GPU sensor names and permissions vary by firmware and driver, so rely on diagnostic output from your own environment.

License

MIT. See LICENSE.

Documentation last reviewed: July 18, 2026.