cvxopf

CI codecov

Optimal power flow via CVXPY, supporting AC-OPF (nonconvex, DNLP), lossy DC OPF (convex QP), and single-node DC dispatch (convex QP).

Motivation

Grid resiliency events rarely happen in an instant. The most dangerous scenarios unfold over days: solar suppressed by sustained weather systems, load elevated beyond seasonal norms, and battery storage depleted by controllers that optimize for the current hour. Studying the behavior of the modern grid under these conditions and developing optimal control policies requires an optimization framework that is simultaneously time-aware and physically grounded, that is able to plan dispatch strategy across a full multi-day horizon and able to enforce the AC network constraints that determine whether a plan is actually executable.

cvxopf is designed with this application in mind. It formulates optimal power flow problems using CVXPY, supports nonlinear AC-OPF, a convex lossy DC relaxation, and single-node economic dispatch from a single entry point (with more to come), and handles multi-step optimization with time-varying load, battery storage, and nondispatchable generation (wind, solar, hydro) natively. The intended use case is resiliency research: studying how battery controllers should behave under adverse multi-day conditions, how much temporal foresight matters, and how well convex approximations track AC feasibility across extended horizons.

Storage is treated as an intertemporal network device, not as a sequence of independent power injections. A multi-step solve co-optimizes the complete dispatch and state-of-charge trajectories, including power and energy limits and configurable terminal constraints or costs. This temporal coupling changes both the feasible set and the economics of the OPF: stored energy acquires an opportunity value, strongly convex generation costs induce levelization, and the controller can preserve energy for future scarcity.

High-stress intertemporal and greedy battery-control comparison

High-stress 96-hour comparison with a 500 MWh terminal target. The experiment augments the 9-bus test case with nondispatchable generation and a single storage device, driven by time-series load and renewable-availability inputs supplied through the native df_P, df_Q, and df_nd pandas interfaces. The top panel shows the active load together with the utility solar, distributed solar, and wind availability supplied to the model. The network-constrained optimum anticipates future scarcity and enforces the terminal state; the causal greedy controllers are terminal-blind. Their lower dispatchable-energy totals are not improvements where they accompany unserved load.

Because it is built on CVXPY, the problem structure is transparent and composable. Researchers can modify objectives, add contingency constraints, or experiment with formulations — including multi-forecast Model Predictive Control — without rewriting solver interfaces.

Overview

cvxopf formulates optimal power flow problems using CVXPY and solves them with appropriate solvers. It is designed to:

  • Run MATPOWER/Pypower test cases out of the box
  • Support multiple OPF formulations from a single entry point
  • Support single-shot optimization over multiple time steps
  • Accept time-varying nodal load as pandas DataFrames
  • Model storage as a first-class intertemporal device with state-of-charge coupling and configurable terminal policies
  • Model nondispatchable generators (wind, solar, run-of-river hydro) with curtailable output and reactive power support

Methodology

Many individual capabilities exposed by cvxopf, including multi-period OPF and intertemporal storage, also appear in other power-system optimization packages. The central contribution here is their organization within a disciplined convex programming (DCP) and disciplined nonlinear programming (DNLP) methodology: device dynamics, costs, and operating sets remain convex wherever the model permits, while the nonconvexity of the full AC formulation is confined to the network-flow physics.

This separation supports an explicit hierarchical solve structure. A globally solvable, long-horizon convex layer determines intertemporal energy decisions and passes device states, especially battery state of charge, to a short-horizon AC layer. The AC layer verifies and corrects for full network physics without needing to reproduce the approximate dispatch trajectory.

Nondispatchable resources are likewise first-class devices rather than generic generator boxes: time-varying real-power availability is coupled to a convex inverter apparent-power region in AC and to separate availability and rating bounds in DC. This preserves the converter-capacity limit without adding nonconvexity.

The implementation follows the same separation of responsibilities. Public build APIs select formulation-owned network physics, while a shared typed assembly layer obtains variables, injections, feasible sets, costs, and intertemporal contributions from component-owned models. The resulting OPFBuild provides one boundary for solving and stable result extraction across all formulations.

flowchart LR
    user["User inputs<br/>case · time series · devices"] --> api["Public build API<br/>validation and formulation selection"]

    api --> physics["Formulation-owned network physics<br/>AC · lossy DC · single-node DC"]
    api --> assembly["Shared typed component assembly"]
    devices["Component-owned models<br/>generation · storage<br/>nondispatchable · HVDC"] --> assembly
    assembly --> physics

    physics --> build["OPFBuild<br/>problem · variables · data · expressions"]
    build --> solve["Formulation-appropriate solve<br/>and stable results"]

    classDef public fill:#e8f1ff,stroke:#2563a6,color:#102a43
    classDef formulation fill:#fff4dd,stroke:#b7791f,color:#4a2c0a
    classDef assembly fill:#e8f8ef,stroke:#27864b,color:#123d24
    classDef component fill:#f2eafe,stroke:#7650a8,color:#321c52
    classDef output fill:#fdecec,stroke:#b74b4b,color:#551d1d

    class user,api public
    class physics formulation
    class assembly assembly
    class devices component
    class build,solve output
Loading

See the full software architecture and component lifecycle for the as-built assembly sequence, architectural invariants, and the boundary reserved for the Milestone 17 hierarchical controller.

Formulations

Key Description Convex Solver
"ac" Nonlinear AC-OPF with two-terminal apparent-power branch limits via CVXPY DNLP (requires cvxpy>=1.9) No IPOPT
"lossy_dc" Lossy DC OPF (Boyd et al.) Yes CLARABEL
"singlenode_dc" Single-node "copper-plate" DC dispatch Yes CLARABEL

AC branch-limit enforcement is enabled by default. rateA == 0 means no thermal limit; every positive finite value is enforced at both terminals, including large values that MATPOWER may treat as unconstrained sentinels. Set OPFOptions(enforce_branch_limits=False) for reporting-only terminal flows under the former compatibility behavior. Because terminal flows retain exact branch coefficients, any positive sparsity_tol also requires this explicit opt-out.

AC network operating-set scope:

  • Implemented: MATPOWER branch status; fixed tap ratios and phase shifts; line charging and bus shunts; voltage-magnitude bounds; nonlinear nodal real/reactive balance; generator real/reactive bounds; and two-terminal apparent-power limits using rateA.
  • Not yet implemented: branch angle-difference bounds (ANGMIN/ANGMAX); selection or contingency use of alternate rateB/rateC ratings; soft thermal limits; current-magnitude or active-power-only branch limits; time-varying or contingency-dependent ratings; topology switching; and controllable transformer tap or phase-shift decisions.

The fixed electrical data in the branch table still enters the AC equations even when its associated operating control is not implemented. See the M4 plan for the detailed boundary and future extension notes.

The "singlenode_dc" formulation collapses the whole network to a single bus: no branch flows, no transmission limits, no losses, no reactive power — just total generation equals total load. It is the classic economic dispatch problem, useful as a fast baseline and for large-horizon energy planning.

The intended workflow for large-scale resiliency studies is hierarchical: solve the convex lossy_dc formulation over the full planning horizon to obtain a globally optimal battery SoC trajectory and dispatch plan, then use the AC formulation over a short receding horizon to verify and correct for true network physics, with SoC targets inherited from the convex layer as boundary constraints.

References:

Prerequisites

cvxopf requires the IPOPT nonlinear solver system library. This must be installed before running pip install cvxopf.

Ubuntu / Debian

sudo apt-get update
sudo apt-get install -y coinor-libipopt-dev liblapack-dev libblas-dev gfortran

Note: On Linux, coinor-libipopt-dev alone is not sufficient. liblapack-dev, libblas-dev, and gfortran are also required because IPOPT's internal linear solver (MUMPS) links against them at build time. Without these, pip install cvxopf will fail when building cyipopt with a linker error (cannot find -llapack, cannot find -lblas).

macOS

brew install ipopt

Windows (conda recommended)

conda install -c conda-forge ipopt

Full IPOPT installation documentation: https://coin-or.github.io/Ipopt/INSTALL.html

Installation

Once the IPOPT system library is installed:

pip install git+https://github.com/cvxgrp/cvxopf.git

This will automatically install all Python dependencies including cyipopt (the Python interface to IPOPT), cvxpy, numpy, and pandas.

When the package is published to PyPI, installation will simplify to:

pip install cvxopf  # coming soon

Quick start

AC-OPF:

from cvxopf.testcases import case9
from cvxopf.problem import build_opf
from cvxopf.results import extract_results

build = build_opf(case9(), formulation="ac")
build.solve()
results = extract_results(build)
print(f"Status: {results['status']}")
if results["Pg"] is not None:
    print(f"Objective: {results['objective']:.2f}")
    print(f"Pg (MW):   {results['Pg']}")

Result keys are determined by the built model and remain stable when a solve does not return primal values. Check status first: unavailable array-valued and derived quantities are None, while scalar objective and cost quantities are NaN.

AC results include signed terminal powers branch_p_from, branch_q_from, branch_p_to, and branch_q_to, plus apparent magnitudes branch_s_from and branch_s_to, all in original MATPOWER branch-table row order. The branch_p_* fields are MW, branch_q_* fields are MVAr, and branch_s_* fields are MVA. Each is shaped (nl,) for a single-step result and (T, nl) for a multistep result. Real and reactive powers are positive when entering a branch from the named terminal; apparent powers are nonnegative.

Lossy DC OPF:

from cvxopf.testcases import case14
from cvxopf.problem import build_opf
from cvxopf.results import extract_results

build = build_opf(case14(), formulation="lossy_dc")
build.solve()
results = extract_results(build)
print(f"Objective:  {results['objective']:.2f}")
print(f"Pg (MW):    {results['Pg']}")
print(f"Flows (MW): {results['p_flows']}")

Single-node DC dispatch:

Any MATPOWER case works (the branch table is ignored), or use the make_singlenode_case convenience constructor to build a minimal economic-dispatch problem without a full network:

from cvxopf.testcases import make_singlenode_case
from cvxopf.problem import build_opf
from cvxopf.generator import DispatchableGenerator
from cvxopf.results import extract_results

case = make_singlenode_case(
    P_load_MW=250.0,
    generators=[
        DispatchableGenerator(
            bus=1, p_max_mw=200.0, cost_coeffs=(0.0, 10.0, 0.05)
        ),
        DispatchableGenerator(
            bus=1, p_max_mw=150.0, cost_coeffs=(0.0, 15.0, 0.08)
        ),
    ],
)

build = build_opf(case, formulation="singlenode_dc")
build.solve()
results = extract_results(build)
print(f"Objective: {results['objective']:.2f}")
print(f"Pg (MW):   {results['Pg']}")

The examples/case14_formulation_comparison.py script solves the IEEE 14-bus case with all three formulations side by side and contrasts their dispatch and implied losses.

First-class dispatchable generators

Pass DispatchableGenerator objects to define generator locations, operating bounds, and costs directly. Polynomial costs use lowest-power-first coefficients and are limited to degree two; piecewise-linear costs use explicit (power_MW, cost) breakpoints. All cost expressions are evaluated by the shared implementation in cost.py.

from cvxopf import DispatchableGenerator, build_opf

generators = [
    DispatchableGenerator(
        bus=1,
        p_min_mw=10.0,
        p_max_mw=250.0,
        q_min_mvar=-300.0,
        q_max_mvar=300.0,
        cost_type="piecewise_linear",
        cost_points=((0.0, 0.0), (100.0, 2500.0), (250.0, 7250.0)),
    ),
]

# network_case needs bus, branch, and baseMVA, but may omit gen/gencost.
build = build_opf(network_case, formulation="ac", generators=generators)

For backward compatibility, omitting generators= converts the case's MATPOWER gen and gencost tables to the same component representation at build time. Supplying generators= overrides those tables; they may be absent, and the input case dict is not mutated.

Interactive notebooks

We recommend using uv (https://docs.astral.sh/uv/) to run the notebooks. From the project root:

uv run --extra notebook marimo run notebooks/cvxopf_demo.py

Select a test case (case9 through case118), choose AC-OPF or lossy DC OPF, and adjust generator limits, branch limits, and load scale interactively. The AC formulation interprets each positive finite rateA as an MVA limit and enforces it independently at both branch terminals; lossy DC interprets the selected value as an MW flow limit. Results update automatically after each solve.

uv run --extra notebook marimo run notebooks/benchmark_opf.py

Select number of repetitions and run a timing study across all test cases and OPF configurations. The results should look something like this:

OPF benchmark: AC sparse vs AC dense vs lossy DC

Multi-step example

Time-varying load is passed as a DataFrame — one row per timestep, one column per bus. This is the foundation for resiliency studies: feed in a multi-day solar and load profile and the optimizer plans dispatch across the full horizon in a single solve.

import numpy as np
import pandas as pd
from cvxopf.testcases import case9
from cvxopf.problem import build_opf_multistep
from cvxopf.results import extract_results

ppc     = case9()
T       = 3
Pd_base = ppc["bus"][:, 2]
Qd_base = ppc["bus"][:, 3]

# Three time steps at 80%, 100%, 120% of base load
scales  = [0.8, 1.0, 1.2]
df_P    = pd.DataFrame(np.outer(scales, Pd_base))
df_Q    = pd.DataFrame(np.outer(scales, Qd_base))

build   = build_opf_multistep(ppc, df_P, df_Q, T=T, formulation="ac")
build.solve()
results = extract_results(build)
print(f"Integrated horizon objective: {results['objective']:.2f}")
print(f"Pg per step (MW):\n{results['Pg']}")

Objective units and time discretization

delta is the interval duration in hours. cvxopf treats generator, storage cycling, HVDC, and lossy-DC regularization terms as stage-cost rates and forms

objective = delta * sum(stage-cost rates) + horizon-boundary costs.

Thus the reported objective is a total over the modeled interval or horizon, normally in currency when the coefficients use currency-based units. Terminal storage penalties occur once and are not multiplied by delta. build.expressions retains integrated generator_cost, conditional storage_cost and hvdc_cost, and dc_loss_cost for lossy DC so the objective composition can be audited. This corrects the former unscaled per-step sum for delta != 1; delta=1 results are unchanged.

Battery storage example

Battery state-of-charge evolves across timesteps, coupling decisions made at hour 1 to feasibility at hour 72. This intertemporal coupling is why multi-step optimization matters for resiliency: the optimizer can see that conditions worsen on day 3 and hold reserves accordingly rather than depleting storage on day 1.

import numpy as np
import pandas as pd
from cvxopf.testcases import case9
from cvxopf.problem import build_opf_multistep, StorageUnitIdeal
from cvxopf.results import extract_results

ppc     = case9()
T       = 3
Pd_base = ppc["bus"][:, 2]
Qd_base = ppc["bus"][:, 3]

scales = [0.8, 1.0, 1.2]
df_P   = pd.DataFrame(np.outer(scales, Pd_base))
df_Q   = pd.DataFrame(np.outer(scales, Qd_base))

unit = StorageUnitIdeal(
    bus=5,
    apparent_power_rating=50.0,  # MVA
    capacity=100.0,              # MWh
    initial_soc=50.0,            # MWh
    aging_weight=1e-2,           # objective units/MWh
)

build = build_opf_multistep(
    ppc, df_P, df_Q, T=T, formulation="ac",
    storage=[unit], delta=1.0,
)
build.solve()
results = extract_results(build)
print(f"Integrated horizon objective: {results['objective']:.2f}")
print(f"Storage real power (MW): {results['b']}")
print(f"State of charge (MWh):   {results['soc']}")

Each storage unit may optionally configure one terminal policy. Hard policies use terminal_constraint="equality" to fix the final post-step SoC or terminal_constraint="shortfall" to enforce soc[-1] >= terminal_soc. Soft alternatives use terminal_cost="linear" or "quadratic" for two-sided deviation, and "shortfall_linear" or "shortfall_quadratic" to penalize only energy below the target. A hard constraint and terminal cost are alternatives for a given unit. A hard terminal policy makes the problem infeasible when the target cannot be reached within the horizon; use a soft terminal cost when a controlled violation is preferable.

Linear terminal weights have units of objective units/MWh, and quadratic weights have units of objective units/MWh². The terminal term is applied once at the horizon boundary and is not scaled by delta. Stage-cost rates are integrated over time, so a fixed terminal weight retains its meaning when the same physical signals are represented at a finer resolution. See examples/case9_storage_terminal.py for a side-by-side comparison.

Nondispatchable generator example

Nondispatchable generators (wind turbines, PV arrays, run-of-river hydro) produce up to a time-varying available power R_t determined by ambient conditions. The OPF can curtail freely; there is no cost for generation or curtailment. In AC, the inverter also provides reactive power support within its apparent power rating. In DC, reactive power is absent, but the availability and apparent-power rating remain as separate real-power upper bounds. Passing a multi-day solar availability profile via df_nd lets the optimizer account for sustained generation shortfalls across the full planning horizon.

import numpy as np
import pandas as pd
from cvxopf.testcases import case9
from cvxopf.problem import build_opf_multistep, NondispatchableUnit
from cvxopf.results import extract_results

ppc     = case9()
T       = 3
Pd_base = ppc["bus"][:, 2]
Qd_base = ppc["bus"][:, 3]

scales = [0.8, 1.0, 1.2]
df_P   = pd.DataFrame(np.outer(scales, Pd_base))
df_Q   = pd.DataFrame(np.outer(scales, Qd_base))

# Solar unit on bus 5: available output ramps down over three steps,
# simulating a multi-day irradiance suppression event
unit  = NondispatchableUnit(
    bus=5,
    p_available=100.0,            # MW — fallback for single-step
    apparent_power_rating=120.0,  # MVA — inverter nameplate
    device_id="solar_5",          # stable key for external time series
)
df_nd = pd.DataFrame({"solar_5": [100.0, 75.0, 50.0]})

build = build_opf_multistep(
    ppc, df_P, df_Q, T=T, formulation="ac",
    nondispatchable=[unit], df_nd=df_nd,
)
build.solve()
results = extract_results(build)
print(f"Integrated horizon objective: {results['objective']:.2f}")
print(f"ND real power (MW):   {results['p_nd']}")
print(f"ND reactive (MVAr):   {results['q_nd']}")
print(f"Curtailment (MW):     {results['curtailment']}")

HVDC transmission link example

HVDC links are controllable point-to-point power transfers between two buses, modelled as signed nodal injections (Convention B: positive = injection into the grid) subject to capacity limits. On fixed-direction links the converter loss is proportional. With signed grid injections, negative p_in sends power from the from-bus and gives p_out = -(1 - loss_frac) * p_in; positive p_in receives power at the from-bus and gives p_out = -p_in / (1 - loss_frac). Links can be built directly as HVDCLink objects or imported from a MATPOWER dcline table via hvdc_from_dcline. The MVP is unity power factor and drops fixed converter loss (loss0, emitting a UserWarning); it applies to both the AC and lossy DC formulations.

from cvxopf.testcases.case9_dcline import case9_dcline
from cvxopf.problem import build_opf
from cvxopf.hvdc import hvdc_from_dcline
from cvxopf.results import extract_results

ppc   = case9_dcline()
links = hvdc_from_dcline(ppc["dcline"])  # three in-service DC links

build = build_opf(ppc, formulation="ac", hvdc=links)
build.solve()
results = extract_results(build)
print(f"Objective:          {results['objective']:.2f}")
print(f"HVDC in  (MW):      {results['p_hvdc_in']}")
print(f"HVDC out (MW):      {results['p_hvdc_out']}")
print(f"HVDC loss (MW):     {results['hvdc_loss']}")

Project structure

src/cvxopf/           Core package
  problem.py          Public API: build_opf, build_opf_multistep
  ac_problem.py       AC-OPF helpers (DNLP formulation)
  dc_problem.py       Lossy DC OPF helpers (convex QP)
  singlenode_dc_problem.py  Single-node DC dispatch helpers (convex QP)
  network.py          Ybus, incidence matrices, reindexing
  cost.py             Generator cost expression builders
  generator.py        DispatchableGenerator component and MATPOWER conversion
  data.py             Input validation and time-series handling
  results.py          Result extraction and comparison utilities
  storage.py          Storage component: data, injections, constraints, cost
  nondispatchable.py  ND component: data, injections, and constraints
  hvdc.py             HVDC component and MATPOWER dcline conversion
  testcases/          Built-in MATPOWER test cases (case9 — case118)
tests/                Pytest test suite
tests/fixtures/       Committed Pypower reference outputs (static)
scripts/              Fixture and test case generation scripts
notebooks/            Interactive marimo notebooks
examples/             Runnable example scripts

Development

Clone the repository and install in editable mode with development dependencies:

git clone https://github.com/cvxgrp/cvxopf.git
cd cvxopf

If you have uv installed, that's it. Just run things with uv from the project root.

If you are managing your own virtual environment, install the development dependencies with pip:

pip install -e ".[dev]"

If you want to run the Marimo notebooks, you'll want the notebook dependencies as well:

pip install -e ".[dev,notebook]"

To run the test suite:

# If using uv (recommended)
uv run --extra dev pytest tests/ -v

# If installed directly with pip
pytest tests/ -v

Run the project lint policy with:

uv run --extra dev ruff check .

The routine lint gate covers the package, tests, examples, and maintenance scripts. Exploratory experiments/ code and interactive notebooks/ are excluded; they are reviewed in the context of the study or notebook rather than held to the library policy.

To regenerate the Pypower reference fixtures (requires uv):

uv run scripts/generate_pypower_fixtures.py

Note: the fixture script runs in an isolated environment with pinned pypower==5.1.19 and numpy==2.2.6. It does not affect the main package environment.

Roadmap

  • Repository skeleton
  • Port and modularize working code
  • Pypower fixture generation and validation tests
  • Multi-step problem builder
  • AC branch-terminal flows and two-terminal apparent-power limits
  • Battery/storage model
  • Lossy DC OPF and multi-formulation architecture
  • HVDC transmission links (lossless + fixed-direction proportional loss, unity power factor)
  • Nondispatchable generators
  • Sparse P/Q variables for AC-OPF
  • Single-node equivalent "copper plate" model
  • SOCP network model
  • Extend battery parameters: terminal equality/shortfall constraints and linear/quadratic terminal costs
  • Implement cvxpy parameters for problem data
  • Vectorize time constraints (currently built with iterative loop)
  • Full lossy HVDC (sign-switching converter losses via charge/discharge split) and reactive power support
  • Unify grid component model patterns (dispatchable generators, storage, nondispatchable → first-class composable components)
  • M16+ typed component adapters and shared formulation assembly (see plans/milestone-16-plus-component-adapters.md)
  • Post-M12/M16 correctness and API hardening: finite temporal inputs, stable unsuccessful-result schemas, and objective time units (see plans/correctness-api-hardening.md)
  • Hierarchical DC→AC receding-horizon dispatch (long-horizon convex plan passes SoC signposts into a short AC window; the implementation of the core vision)
  • Convex lossy storage with asymmetric efficiency, explicit storage loss, and a relax-round-polish fallback (see plans/milestone-18-lossy-storage.md)
  • Explicit nodal load shedding with value-of-lost-load costs and energy-not-served reporting (see plans/milestone-19-load-shedding.md)