go-iec104 - IEC 60870-5-104 Client and Server Library for Go

Go Version Go Reference License: MIT CI Status Interop Code Coverage Latest Release

A pure Go implementation of IEC 60870-5-104, the TCP/IP telecontrol protocol between control centres and substations, RTUs and generation assets. No cgo, no dependencies outside the standard library.

The library provides:

  • A client (controlling station): STARTDT/STOPDT, general and counter interrogation, read, clock synchronization, process commands with select-before-operate, test command, automatic reconnect
  • A server (controlled station): any number of sessions, routing by type identification, standard-conformant rejection of what the application does not serve, redundancy groups with an event queue that keeps events until a control centre has acknowledged them
  • The complete APCI protocol machine on both sides: I/S/U frames, 15-bit sequence numbers, the k/w flow-control windows and the t0..t3 timers
  • An ASDU model and codec for 67 type identifications, file transfer included, independent of the transport and reusable for IEC 60870-5-101
  • File transfer in both directions and the directory: GetFile, PutFile and ListFiles on the client, server.FileServer on the station, with sections, segments, checksums and acknowledgements handled by the library
  • What production use needs: context.Context on every call, automatic reconnect, retries for the requests that are safe to repeat, redundancy groups with failover, structured logging, metrics hooks and TLS (IEC 62351-3)
  • Verified against third-party stacks: every push runs the library, as client and as server, against MZ Automation lib60870-C, OpenMUC j60870 and wendy512/iec104

Docs: API.md (public API) · ARCHITECTURE.md (packages, goroutines, protocol machine) · INTEROPERABILITY.md (what is implemented, clause by clause) · ERRORS.md (error semantics) · OBSERVABILITY.md (logging and metrics) · SECURITY.md · RELEASE.md (changelog)

Table of contents

go-iec104 vs lib60870, j60870 and wendy512/iec104

go-iec104 is tested against three other implementations (see Interop tests): MZ Automation lib60870-C, OpenMUC j60870 and wendy512/iec104 on its engine go-iecp5. All are good libraries; this table shows where the four differ so you can pick the right one for your project.

Capability otfabric/go-iec104 lib60870-C j60870 wendy512/iec104
Language Go C Java Go
License MIT GPL-3.0 or commercial GPL-3.0 Apache-2.0, on an LGPL-3.0 engine
IEC 60870-5-104 client (controlling station) ✅ ✅ ✅ ✅
IEC 60870-5-104 server (controlled station) ✅ ✅ ✅ ✅
IEC 60870-5-101 serial link layer — by design ¹ ✅ — — frame format only
Process information, commands, system types (1..40, 45..64, 70, 100..107) ✅ ✅ ✅ partly ³
Parameter types (110..113) ✅ ✅ ✅ ✅
File transfer types (120..127) ✅ ✅ ✅ — identifiers only
File transfer procedure, monitor direction (download) ✅ client and server ✅ server side — —
File transfer procedure, control direction (upload) ✅ client and server ✅ server side — —
File directory ✅ client and server — — —
Private types (128..255) raw payload raw payload custom decoder — dropped
Configurable k, w, t0..t3 ✅ ✅ ✅ ✅
TLS (IEC 62351-3) ✅ crypto/tls ✅ mbedTLS via socket factory ✅ crypto/tls
Application-layer security (IEC 62351-5) — types carried, no procedure — commercial add-on (2013 edition) — —
Blocking request methods (interrogate and collect, command and confirm) ✅ — callbacks — callbacks — callbacks
Server-side routing with standard refusals (unknown type, cause, address) ✅ Mux partly built in unknown type only partly, without the P/N bit
Redundancy group, client side (failover, switchover) ✅ Group — — —
Redundancy groups, server side ✅ ✅ — —
Server-side event queue for stopped or absent clients ✅ acknowledged delivery ✅ — —
Automatic reconnect with back-off ✅ — — fixed interval
Automatic retries (read-only requests) ✅ — — —
Cancellation and deadlines per call ✅ context.Context — — timeouts only —
Structured logging ✅ log/slog — compile-time debug output — (pluggable logger from 1.8.0) — pluggable printf-style logger
Metrics hooks ✅ — raw message callback — —
Threadless / single-loop operation — by design ² ✅ — —
Dependencies none none (mbedTLS optional) none one (spf13/cast) besides its engine
Cross-tested against other stacks in CI ✅ against all three — not documented — not documented — not documented

¹ IEC 60870-5-101 is a different companion standard with its own serial link layer (FT 1.2 framing, balanced and unbalanced procedures). It belongs in a module of its own, built on the asdu package of this one, which already takes the 101 field sizes.

² A mode for C programs without threads. In Go the protocol machine runs on goroutines, and a single-threaded variant would add nothing.

³ go-iecp5 encodes the commands with time tag (58..63) but has no length for them and drops them on reception, as it does the file segment (F_SG_NA_1) and every type it does not know.

✅ = available · — = not available or not documented. For lib60870-C v2.4.1, j60870 1.7.2 and wendy512/iec104 v1.0.4 on go-iecp5 v1.2.6, the versions go-iec104 is tested against, from their public sources and documentation as of October 2026. If you spot an inaccuracy, please open an issue and we will correct it.

Choose go-iec104 if you write Go and want client and server in one library with no cgo and a permissive license, blocking calls with context control, reconnect, retries, client-side redundancy and observability built in.

Choose lib60870-C if you need IEC 60870-5-101 over serial lines or a C library for embedded targets.

Choose j60870 if you are on the JVM and want a compact IEC 60870-5-104 library.

Install

go get github.com/otfabric/go-iec104

Requires Go 1.23 or later.

Project structure

go-iec104/
├── doc.go, errors.go, state.go     package iec104: shared errors, State,
├── logger.go, metrics.go           Logger and Metrics
├── apci/                           APDU framing, I/S/U control fields,
│                                   sequence numbers, k/w/t0..t3 parameters
├── asdu/                           ASDU model and codec (IEC 101/104)
├── client/                         controlling station
├── server/                         controlled station, sessions, Mux
├── internal/link/                  the protocol machine client and server share
├── internal/station/               a fixture-driven station for the tests below
├── e2e/                            go-iec104 client against go-iec104 server
├── interop/                        tests against lib60870, OpenMUC j60870, wendy512
│                                   (build tag "interop", needs Docker)
└── examples/                       nine programs to start from

APCI is specific to IEC 60870-5-104 and lives with it. The ASDU package has no dependency on the transport: the field widths that differ between companion standards are a parameter (asdu.Params), so the same codec serves an IEC 60870-5-101 link layer. See ARCHITECTURE.md.

Client quickstart

package main

import (
	"context"
	"fmt"
	"log"
	"time"

	"github.com/otfabric/go-iec104/asdu"
	"github.com/otfabric/go-iec104/client"
)

func main() {
	ctx := context.Background()

	// Dial connects and sends STARTDT. Every ASDU the station sends reaches
	// the handler, in order.
	c, err := client.Dial(ctx, "10.0.0.5:2404",
		client.WithReconnect(client.Reconnect{}),
		client.WithHandler(client.HandlerFunc(func(a *asdu.ASDU) {
			for _, obj := range a.Objects {
				if m, ok := obj.(asdu.MeasuredFloat); ok {
					fmt.Printf("%s ioa=%d value=%g quality=%s\n", a.Cause, m.IOA, m.Value, m.Quality)
				}
			}
		})))
	if err != nil {
		log.Fatal(err)
	}
	defer c.Close()

	// General interrogation of station 1: returns when the station sends
	// the activation termination.
	data, err := c.Interrogate(ctx, 1, asdu.QOIStation)
	if err != nil {
		log.Fatal(err)
	}
	fmt.Printf("interrogation returned %d ASDUs\n", len(data))

	if err := c.ClockSync(ctx, 1, time.Now()); err != nil {
		log.Fatal(err)
	}

	// Select before operate.
	cmd := asdu.SingleCommand{IOA: 6001, Value: true, Select: true}
	if err := c.Command(ctx, 1, cmd); err != nil {
		log.Fatal(err)
	}
	cmd.Select = false
	if err := c.Command(ctx, 1, cmd); err != nil {
		log.Fatal(err)
	}
}

Request methods block until the station answers and return a *iec104.NegativeError when it refuses. A context without a deadline is bounded by WithRequestTimeout (default 10s).

Server quickstart

package main

import (
	"log"

	"github.com/otfabric/go-iec104/asdu"
	"github.com/otfabric/go-iec104/server"
)

func main() {
	mux := server.NewMux()

	mux.HandleFunc(asdu.C_IC_NA_1, func(s *server.Session, req *asdu.ASDU) {
		qoi := req.First().(asdu.Interrogation).Qualifier
		_ = s.Confirm(req)
		_ = s.Send(s.Context(), asdu.New(qoi.Cause(), req.CommonAddr,
			asdu.SinglePoint{IOA: 1001, Value: true},
			asdu.SinglePoint{IOA: 1002, Value: false}))
		_ = s.Terminate(req)
	})

	mux.HandleFunc(asdu.C_SC_NA_1, func(s *server.Session, req *asdu.ASDU) {
		cmd := req.First().(asdu.SingleCommand)
		if cmd.IOA != 6001 {
			_ = s.Reject(req, asdu.CauseUnknownIOA)
			return
		}
		_ = s.Confirm(req)
		// operate the process ...
	})

	srv, err := server.New(mux, server.WithCommonAddrs(1))
	if err != nil {
		log.Fatal(err)
	}
	log.Fatal(srv.ListenAndServe(":2404"))
}

Mux answers a type without a handler with "unknown type identification" and an invalid cause of transmission with "unknown cause of transmission"; WithCommonAddrs answers a foreign station address with "unknown common address".

Events go out with Server.Enqueue: each redundancy group delivers them, in order, to its one started connection, keeps them while no control centre is connected and sends again what was not acknowledged when a connection is lost. Session.Send and Server.Broadcast send immediately and buffer nothing.

srv, err := server.New(mux,
	server.WithRedundancyGroups(
		server.RedundancyGroup{Name: "main", Allow: []string{"10.0.0.0/24"}},
		server.RedundancyGroup{Name: "backup"}), // everyone else
	server.WithEventQueue(10000))

_ = srv.Enqueue(asdu.New(asdu.CauseSpontaneous, 1,
	asdu.SinglePoint{IOA: 1001, Value: true, Time: asdu.Now()}))

Production features

Feature How Notes
Cancellation context.Context on Connect, every request, Send, StartDT/StopDT and on a server's Session.Send A cancelled request releases its slot and leaves the connection up
Automatic reconnect client.WithReconnect Exponential backoff; WithStartHandler runs on every fresh connection, the place for a general interrogation
Automatic retries client.WithRetry Only for requests that read: Interrogate, CounterInterrogate (read), Read, TestCommand. Commands are never repeated
Redundancy client.NewGroup Several connections to one station, exactly one started, automatic failover and manual Switchover
Structured logging iec104.NewSlogLogger, or any iec104.FieldLogger Constant messages with fields (component, remote, state, type, error, …); silent by default
Metrics hooks iec104.Metrics, RequestMetrics, HandlerMetrics Connections, frames, request outcomes with duration and retries, handler duration
c, err := client.Dial(ctx, "10.0.0.5:2404",
	client.WithLogger(iec104.NewSlogLogger(slog.NewJSONHandler(os.Stderr, nil))),
	client.WithMetrics(myMetrics),
	client.WithReconnect(client.Reconnect{}),
	client.WithRetry(client.Retry{Attempts: 3}),
	client.WithStartHandler(func(ctx context.Context, c *client.Client) {
		_, _ = c.Interrogate(ctx, 1, asdu.QOIStation) // refresh after every (re)connect
	}))

Why there is no connection pool. A pool suits request/response protocols whose connections are interchangeable. An IEC 60870-5-104 connection is a session: the station pushes its spontaneous data on the one connection that has data transfer started, and sequence numbers, acknowledgements and command procedures belong to it. More connections add availability, not throughput, and the standard defines exactly that as a redundancy group:

g, err := client.NewGroup([]string{"10.0.0.5:2404", "10.1.0.5:2404"},
	client.WithHandler(h),
	client.WithSwitchHandler(func(active *client.Client) { /* failover happened */ }))
if err := g.Connect(ctx); err != nil { ... }
defer g.Close()

data, err := g.Interrogate(ctx, 1, asdu.QOIStation) // on the active connection

Why commands are not retried. When the confirmation of a command is lost, the command may still have operated the process, and the protocol has no way to ask. Repeating it is a decision for the application, with the process state in hand. See ERRORS.md.

The ASDU model

Information objects are plain structs named for what they mean. The type identification selects the variant on the wire:

Struct Without time tag CP24Time2a CP56Time2a
SinglePoint M_SP_NA_1 M_SP_TA_1 M_SP_TB_1
DoublePoint M_DP_NA_1 M_DP_TA_1 M_DP_TB_1
MeasuredFloat M_ME_NC_1 M_ME_TC_1 M_ME_TF_1
SingleCommand C_SC_NA_1 C_SC_TA_1
…

asdu.New picks the type from the first object: no time tag when its Time is zero, CP56Time2a otherwise. Set ASDU.Type for the other variants and ASDU.Sequence for the compact SQ=1 encoding. The full table is in INTEROPERABILITY.md.

a := asdu.New(asdu.CauseSpontaneous, 1,
	asdu.MeasuredFloat{IOA: 4001, Value: 49.98, Time: asdu.Now()})
wire, err := a.Encode(asdu.IEC104)   // M_ME_TF_1
back, err := asdu.Decode(wire, asdu.IEC104)

Types without an object model (the private range 128..255) are not an error: they travel as ASDU.Raw in both directions.

Protocol parameters

Both sides take apci.Params; the defaults are those of the standard.

Parameter Default Meaning
K 12 Maximum I frames sent and not yet acknowledged; Send blocks beyond it
W 8 Acknowledge at the latest after this many received I frames
T0 30s Connection establishment timeout (client)
T1 15s Timeout for an acknowledgement or U-frame confirmation; closes the connection
T2 10s Longest wait before acknowledging when there is nothing to send (T2 < T1)
T3 20s Idle time before a TESTFR is sent; 0 disables
p := apci.DefaultParams()
p.T3 = 10 * time.Second
c, err := client.Dial(ctx, addr, client.WithParams(p))

Error semantics

Situation How it is reported
Station refuses a request (P/N bit, or cause 44..47) *iec104.NegativeError; Cause() tells why
No answer in time context.DeadlineExceeded, wrapped
Connection could not be established iec104.ErrConnectFailed, wrapping the cause
Not connected / data transfer stopped iec104.ErrNotConnected / iec104.ErrNotStarted
Identical request still pending iec104.ErrBusy
Request method called from a client handler iec104.ErrInHandler
Peer closed or transport failed iec104.ErrConnectionLost
No acknowledgement within T1 iec104.ErrTimeout; connection closed
Peer broke the protocol iec104.ErrProtocol; connection closed
Value cannot be encoded asdu.ErrInvalidValue, asdu.ErrTypeMismatch, …

Full guide: ERRORS.md.

Examples

The examples folder has nine programs to start from. Seven are self-contained (station and controlling station in one process, over TCP on loopback), so they run as they are:

go run ./examples/quickstart      # the smallest station and client
go run ./examples/commands        # select-before-operate, set points, refusals
go run ./examples/files           # download, upload and directory
go run ./examples/events          # event queue, broadcast, end of initialization
go run ./examples/redundancy      # redundancy group, switchover, failover
go run ./examples/tls             # TLS with certificates on both sides
go run ./examples/observability   # logs, states, metrics, retries, reconnect

Two are separate programs, for trying the library against another implementation or a device:

make build
./bin/example-server -addr :2404
./bin/example-client -addr 127.0.0.1:2404 -operate 6001

Both take -debug to log every APDU.

Development

make check      # format, lint, vet, vulnerability scan, tests, coverage
make test       # tests with the race detector
make fuzz       # codec fuzz targets (FUZZTIME=30s each)
make bench      # codec benchmarks

Tests need no hardware and no external process: client and server are tested against each other and against scripted peers over loopback TCP.

The e2e package runs the library against itself, end to end, as part of go test ./...:

  • Station scenarios over TCP, TLS and with k = w = 1, against a station that serves the fixture of the interop suite (the one the reference clients are run against below): interrogation, counter interrogation and read value by value, every command type with and without time tag, select-before-operate, the refusals, file download, STARTDT/STOPDT, the idle test, reconnect, concurrent sessions, the event queue and redundancy on both sides.
  • Wire matrix: every one of the 67 type identifications, in the variants the wire format distinguishes (time tags and their flags, SQ = 0 and SQ = 1, full APDUs, the P/N and test bits, raw private types), sent through both codecs and both protocol machines and compared field by field; again with the IEC 101 field sizes and a time zone other than UTC; and 40,000 frames each way to wrap the 15-bit sequence numbers.
  • Everything around a connection: state callbacks, logs and metrics of both sides against each other; retries; session limit, accept filter and redundancy groups by address; event queue overflow; broadcast; requests that time out, are cancelled, collide or are pending when the station shuts down; a handler that panics; mutual TLS; unsolicited data amid requests; STOPDT in the middle of an event stream; a link that goes silent without closing, so that both sides find out by their timers.

Together they execute about 85% of the library's statements. The rest is what two correct peers never do to each other (malformed frames, sequence errors, protocol violations) and is covered by the scripted-peer tests of internal/link and the codec tests.

Interop tests

The interop package tests go-iec104 against three independent implementations, MZ Automation lib60870-C, OpenMUC j60870 and wendy512/iec104 on its engine go-iecp5, packaged as container images by otfabric/iec104-interop.

make interop    # needs Docker; about four minutes
Direction What is checked
go-iec104 client → reference servers File download with the content the fixture defines. Interrogation, counter interrogation and read return the fixture value by value; every command type with and without time tag, select-before-operate and deactivation; refusals (unknown type, cause, common address, object); STARTDT/STOPDT cycles; k = w = 1; the idle test in both directions; reconnect after a station restart; concurrent sessions; a redundancy group across two stacks with failover and switchover
reference clients → go-iec104 server 34 scenarios per client, file download among them. Each must have the outcome the standard prescribes, and the client's complete result (every ASDU, in order, field by field) must equal what it gets from the reference server of its own stack; an event queue delivered and acknowledged

The images are the only thing shared with iec104-interop; nothing of it is cloned or built here. Scenarios, expected values and assertions live in this repository.

This version is qualified against iec104-interop v0.2.0 (lib60870-C v2.4.1, j60870 1.7.2, wendy512/iec104 v1.0.4 on go-iecp5 v1.2.6). The three images are pinned by digest in interop/harness.go, the Makefile and the Interop workflow, which runs on every push and pull request. To test against another build, set IEC104_INTEROP_LIB60870_IMAGE, IEC104_INTEROP_OPENMUC_IMAGE or IEC104_INTEROP_WENDY512_IMAGE; to run one stack only, IEC104_INTEROP_ADAPTERS=lib60870.

The references do not all support the same. The suite asks each image what it declares (print-capabilities) and skips, rather than fails, what an image lacks:

lib60870-C j60870 wendy512/iec104
Everything in the table above except the rows below ✅ ✅ ✅
Commands with time tag ✅ ✅ — the stack drops them
File download, reference as server (GetFile) ✅ — no file server —
File download, reference as client (FileServer) ✅ ✅ —

Limitations

  • No IEC 62351-5 application-layer security. Its type identifications are named and carried as raw payload, the procedures are not implemented; see SECURITY.md. Use TLS with client certificates.
  • File transfer covers download, upload and the directory. Upload and the directory are verified by this repository's own tests only: no reference stack offers them through the interop images yet. File deletion and the query log have their types in the codec but no procedure.
  • The event queue is in memory. It survives a control centre that is away, not a restart of the station.
  • Verified against three third-party stacks, lib60870-C, j60870 and wendy512/iec104 (see Interop tests); not against certified test equipment or field devices.

Details in INTEROPERABILITY.md.