Meti-2500 Series: User'S Manual
Meti-2500 Series: User'S Manual
User’s Manual
www.Elec-Engg.com
                              1
                    [Caution]
                        Ensure to read this manual before installing METi-2500.
                       Make sure that the current input terminal, the secondary of the
                       CT, is not opened when the current is provided to the primary
                       of the CT.
                                                    2
                    Quick Start
connection. The rated current and the phase voltage can be connected up to 5A
and 300V (line voltage display: 600V), respectively. Refer to Chapter 2 or Chapter
                                                        Upper                            Lower
                                                        RS-485                           RS-485
                           N        C       B       A
                                                                      485 485
                                                K                      +   -
                                                                C11
                                                L           C12                              V1
                                        K
                                                            C21                              V2
                                        L                   C22                              V3
                                K
                                                            C31                              VN
                                L                               C32
                                                                          L+   N-   FG
                                                                       AC88~264V
                                                                       DC100-220V
                                                                      3
                    2 Basic method of setting
                       a)     Simultaneously press the Down (∨) and Enter (ENT) keys for three seconds
b) A sign CONN will appear on the first line of Segment, allowing the setting of
c) Press the Enter (ENT) key to change the concerned setup menu.
d) The setup menu on the first line of the Segment will flicker.
                       e) Change the setting value using the UP(∧) or Down (∨) key.
www.Elec-Engg.com
g) Press the UP(∧) or Down (∨) key to move to the next setup menu.
h) Press the ESC key to exit the setup mode and move to the indication mode.
                                               Segment
                              Setting menu                    Setting range       Setting Step      Remark
                                                display
                                                           1:3P4W,2:3P4WD*,
                               Connection
                                                'Conn'      3:3P3W,4:3P3WD,            1
                                  mode
                                                            5:1P3W, 6:1P2W
                                                                                                     Only
                            Primary Voltage      'Pt1'        0*/110 ~ 99990        10/100
                                                                                                 Connection 1,3
                               Secondary
                                                 'Pt2'          110 ~ 300*            10
                                 Voltage
                                CT Ratio          'Ct'        1 ~ 9999(10*)          1/10
                            Communication                                                           Applied
                                                 'Addr'           1*~ 255              1
                                Address                                                          communication
                                                                   4
                                                       Table of Contents
                    1. Overview ……………………………………………………………….. 6
                      a. Features …………………………………………………………………. 6
                      b. Product types…………………………………………………………….. 7
                      c.   Ratings……………………………………………………………………. 9
                      d. Conditions for environmental tests..................................................... 9
                      e. Case Standard……………………………………………………………. 10
                      f.   Instrument Weight............................................................................... 10
www.Elec-Engg.com
                      g. Cleaning.............................................................................................. 10
                    2. Method of Installation and Connection……………………………….. 11
                      a. Installation…………………………………………………………………. 11
                      b. Electric connection……………………………………………………….. 12
                    3. Menu …………………………………………………………………….. 21
                      a. The Configurations of the Front Panel…………………………………. 21
                      b. The Method of Setting ……………………………………………………22
                      c.   Measuring Indication ……………………………………………………..25
                      d. The Methods of Resets of Energy, Peak Power……………………….41
                      e. The time setting mode(only E-version)………………………………….42
                    4. Order Information ……………………………………………………….45
                                                                        5
                    Product Information
                    1 Overview
                     METi-2500 series are high precision, multi-functional digital panel meters, applied
                     with a DIN and ANSI standard.    They are designed to replace various analog
                     meters such as V, A, kW, kWh, power-factors and frequency meters and can be
                     remote controlled using diverse communication methods
                      a) Features
                         ① Supports various communications protocols
                            Designed for a user to construct a power management system with ease,
                            by employing the standard protocols that are widely used in power system
www.Elec-Engg.com
                                                            6
                    b) Product types
                      ① Basic type
                            Model name: METi-2500S
                            Meters a total of fourteen units including voltage, current, electric power,
                          electric energy, frequency and power-factor
                      ② Communication type(Option)
                            Model name: METi-2500CM,CD,CL
                            Provides the same functions as those of METi-2500S and additionally
                          isolated RS485
                      ③ Energy type(Option)
www.Elec-Engg.com
                                                         7
                    Table 1] Product specifications by function
                                            Model
                                                       Accuracy         METi96S-560x   METi96E-560x
                           Function
E Frequency 0.5%
                       G      Monthly accumulated
                                                         0.5%
                                       energy
Harmonic (THD) H
C RS 485 MODBUS CM
O DNP 3.0 CD
M LonWorks CL
                                                                    8
                    c) Ratings
                      ① Frequency: 50/60Hz
                      ② Current Inputs:
                             Inputs : I1,I2,I3
                             CT 5A or 1A (optional)
                             Measurement category Ⅲ
                             Overload : 100Arms for 1second
                             Dielectric Withstand : 3000Vrms, for 1minute
                             Starting Current : 0.005A RMS
                             Burden : 0.05VA(typical) @ 5A
www.Elec-Engg.com
                      ③ Voltage Inputs:
                             Inputs : V1,V2,V3,Vref
                             50 to 300VLN(86.6-600LL) VAC RMS (three phase)
                             Measurement category Ⅲ
                             Overload : 1000VAC RMS continuous
                             Dielectric Withstand: >3250VAC RMS, 60Hz for 1minute
                             Impedance: 2Mohm / phase
                      ④ Power Supply:
                             Rated Inputs : AC: 85 ~ 265VAC, 50~60Hz
                                                 DC:100~300VDC
                             Dielectric Withstand: 2000VAC RMS, 60Hz for 1minutes
                             Burden : 30VA typical
                      ⑤ Operating temperature : -20 to +70℃
                      ⑥ Storage temperature : -25 to +80℃
                      ⑦ Humidity: 5 to 95 % (status of no dewing)
                      ⑧ Pollution degree 2
                    d) Conditions for environmental tests
                      ① Insulation resistance: 2M between the charger and the ground
                      ② AC voltage tests : AC 2000V/ 10mA/ for 1 min. period
                      ③ Fast transients
                             Standard: IEC1000-4-4
                             Power supply terminal common mode: 2kV
                             Current/voltage input: 2kV
                      ④ Temperature cycle test
                             Temperature: -20 to +60 ℃
                             Repetition of two cycles
                                                          9
                    e) Case Standard
                         ① METi-2500
                               Applied with the DIN 96 standard and ANSI 4”
                               90 x 90 x 65 (HxWxD) mm
                    f)   Instrument Weight : 0.5kG
                    g) Cleaning
                         If the meter is dirtied by stain, a user has to clean using a dry towel or a piece
                         of cloth.
www.Elec-Engg.com
                                                            10
                    2 Method of Installation and Connection
                      a) Installation
                         ① As shown on figure 1, insert METi-2500 into a through hole cut out.
                         ② Insert each screw in the holes at the rear side of mounting panel.
                         ③ Fix up screws in the insert holes of METi-2500
                         ④ Tighten the screws by using a screw driver
www.Elec-Engg.com
91mm
65mm
                                                                                   92mm
                                            88mm
                                              100mm                                              92mm
                           88mm
4-Ø5.5D
                                                          11
                         b) Electric connection
                             ① Terminal configurations
                                 The terminal of METi-2500 is configured as follows:.
                                                        Communication
                                                        Terminal:RS485
www.Elec-Engg.com
                    Current input
                                                                                                Voltage input terminal:
                    terminal :
                                                                                                  110 to 300V : direct connection
                      CT rated current : 5A
                                                                                                  over the 300V : PT
                                           Power supply
                                                                              Earth terminal:
                                           terminal :
                                                                              Safety purpose
                                           85~260V Input
                                                                         12
                         ! Caution
                         Ensure that the earth terminal is connected. Otherwise
                         some accident or operational error may occur.
Power Supply
L+ N-
METi-x
                                                     13
                          [Note]
                          If the voltage is supplied without phase, the status display
                          window of METi-2500 will display a sign, ‘E 1,’ when the
                          power is applied.
                          [Note]
                            • The set value should be assigned as a ratio of the
                           primary to the secondary current. If the primary current
                           is 50A and the secondary is 5A CT, the set value will be 10.
                           • If the connections of current input are switched, the
                           status display window of METi-2500 will display a sign,
                           ‘E 1,’ when the power is applied.
                                                      14
                                           METi-x                                         METi-x
                                            485(1)                                        485(1)
                                             + -                                           + -
                                                              MAX 32EA
                    Master                                                                         Terminal
                                                              Max Length: 1.2km
                                                                                                   resister:120Ω
www.Elec-Engg.com
                         A                                    K      L
                         B                                               K        L
                         C                                                            K          L
                         N
METi-x
                                                         15
                        Three-phase and four-wire direct connection
                        Connect the voltage and current input circuits to the lines of the three-
                        phase and four-wire type and to a phase voltage of below 300V, without
                        using PT. The connection mode setting should be No. 2 (CONN: 2).
                    A                                K        L
                    B                                             K      L
                    C                                                        K       L
www.Elec-Engg.com
METi-x
                                                    16
                      The three-phase and three-wire PT connection
                         Connect the voltage and current circuits to the lines of the three-phase
                         and three-wire type in an open delta method, using PT.    The
                         connection mode setting should be No. 3 (CONN: 3).
                     A                                  K      L
                     B
                     C                                                       K        L
www.Elec-Engg.com
METi-x
                                                   17
                        The three-phase and three-wire direct connection
                       Connect the voltage and current circuits to the lines of the three-phase
                       and three-wire type.   The connection mode setting should be No. 4
                       (CONN: 4).
                       A                                 K     L
                       B                                           K       L
                       C                                                       K      L
www.Elec-Engg.com
METi-x
                    [Note]
                    In the three-phase and three-wire PT connection, the B phase voltage
                    and current are assumed to be under a balanced load condition and
                    therefore, the values are metered from the voltage and current of the A
                    and C phases. Hence, if the B phase voltage and current is not under a
                    balanced condition, the unit cannot satisfy its precision standard.
                                                    18
                        The single-phase and three-wire direct connection
                       Connect the voltage and current to the lines of the single-phase and
                       three-wire type and to a phase voltage of below 300V.   The connection
                       mode setting should be No. 5 (CONN: 5).
                       A                                K      L
                       B                                           K      L
                       N
www.Elec-Engg.com
METi-x
                                                   19
                        The single-phase and two- wire direct connection
                        Connect the voltage and current to the lines of the single-phase and
                        two-wire type and to a phase voltage of 300V.   The connection mode
                        setting should be No. 6 (CONN: 6).
A K L
                    N
www.Elec-Engg.com
METi-x
Figure 10) The drawing of the single-phase and two-wire direct connection.
                                                   20
                      3 Menu
                         a) The Configurations of the Front Panel
                            The Figure 11 represents the configurations of the front panel of METi-X.        The
                            front panel is composed of 7-Segments, with four units per each of three lines,
                            which indicate measuring values, an LED that indicates the measuring unit,
                            and a x1000 LED that lights up when a measuring value exceeds the indication
                            range.    In addition, it includes the load factor indicator that displays the use
                            ratio of the load and four operational keys as follows:
                                     Up: To raise a setting value or move to the previous measuring value
                                     Down: To lower a setup value or move to the next measuring value
www.Elec-Engg.com
                                       NEOPIS
                                     METi-2500
                                                                                          V1/V1
                                                                                          A1
                                             100
                                             90                                           kVA
                                             80                                           Peak       LEDs for
                                             70
                                             60                                  x1000
                                             50
                                                                                                     indicating
                                             40
                                                                                          V2/V2
                                                                                          A2         metering
                                       LOAD(%)                                            kVAR       units
                       Load factor                                                        PF
                         indicator                                               x1000
                                                                                          V3/V3
                                                                                          A3
                                         VTHD                                             kW
                    Only Using           ITHD                                             Hz
                                         DMD                                     x1000
                    H-Version
                                         MAX
                                         MON                                                       x1000
                                                   ESC                                             LED
                                                                                      ENT
                    Only Using
                    E-Version
                                                          ESC         UP         DOWN          ENTER
                                                          Key         Key          Key         Key
                                                                 21
                    b) The Method of Setting
                      ① To enter the setting mode
                          Press the Down (V) and Enter (ENT) keys simultaneously for three
                          seconds, referring to figure 12.    Then, as is shown in figure 13, the first
                          item of the setting menu, the setting of the connection mode will appear.
                                NEOPIS
                              METi-2500
                                                                                     V1/V1
                                                                                     A1
                                      100
                                      90                                             kVA
www.Elec-Engg.com
                                      80                                             Peak
                                      70
                                      60                                    x1000
                                      50
                                      40
                                                                                     V2/V2
                                                                                     A2
                                LOAD(%)                                              kVAR
                                                                                     PF
                                                                            x1000
                                  VTHD                                               V3/V3
                                  ITHD                                               A3
                                  DMD                                                kW
                                  MAX                                                Hz
                                  MON                                      x1000
ESC ENT
Seg1 Line
                                                                                The setting is
                               Seg2 Line                                        3P4W      direct
                                                                                connection
Seg3 Line
                                                         22
                    ② To scroll and select a setting menu
                       Use the Up and Down keys to scroll and select a setting menu.       Press
                       the Down key to move down through the setting menu in the order as is
                       shown in figure 14.   Press the Up key to move to the previous menu.
                       Press the Enter key to select a menu.      When a menu is selected, the
                       setting menu on the first line of the Segment flickers.
                      Down+Enter
                                                                                   Enter
                                                    Connection : Conn
www.Elec-Engg.com
Down Up
Primary PT : Pt1
Secondary PT : Pt2
CT ratio : Ct
                                                                                   Enter
                                                    Display Volt: U_dP
Down Up
                                                       23
                       ③ To change and save a setting value
                            Press the Up or down keys to increase or decrease a setting value while
                            the setting item on the first line of the Segment flickers.         Then, press the
                            Enter key to save the changed value, which will stop the flickering of the
                            setting menu. The below table represents the range of the setting values
                            of each menu and corresponding Segment displays.              In order to make it
                            easy to set the first phase voltage and CT ratio, which have wide ranges
                            of setting values, follow these instructions: Press the Up or Down key for
                            three seconds and then, the long key to increase or decrease the value to
                            ten times higher that of the basic setting value.
www.Elec-Engg.com
                    Table 2) The range of the setting value by each menu and the displays of the
                    segments (*: an initial setting value)
                                    Segment                                             Setting
                    Setting menu                            Setting range                              Remark
                                     display                                              Step
                       Primary
                                      'Pt1'                 0*/110 ~ 99990               10/100     Only Conn :1,3
                       Voltage
                      Secondary
                                      'Pt2'                   110 ~ 300*                   10
                       Voltage
                    Communication                                                                      Applied
                                     'Addr'                    1*~ 255                     1
                       Address                                                                      communication
                      Automatic
                                      'rEF'                    0 ~ 10*                     1            [sec]
                        scroll
                                                              24
                      ④ To exit the setup mode
                          Press the ESC key to exit the setting mode and go back to the measuring
                          display mode
                    c) Measuring Indication
                        When provided with the power, the unit will initially display the voltage
                        measuring indication screen.    In order to move to other measuring
                        indication screens, use the Automatic scroll (between 1 and 10 sec./ 0 none
                        scrolling) or Up and Down keys.       To activate the Automatic scroll, do not
                        press any key and wait for two minutes and thirty seconds.       Then, the
                        screen will be automatically switched to the next metering indication menu
www.Elec-Engg.com
                                                         25
                     Table 3) the range and precision of measuring items
                     Measure Items                     Range of measuring                 Precision (%)
Power-factor -1 ~ 1 0.5%
energy
factor
energy
                                                        26
                    ② The voltage indication mode
                       Enables the instant indication of values of the three-phase voltage as is
                       shown in figure 15. In this case, a corresponding voltage unit indication
                       LED lights up.       When a voltage value exceeds 9,999V, the x1000LED
                       lights up, indicating a change of digits.   If a voltage is set as a three-
                       phase/ four-wire for type and L-L for indication, the screen will display the
                       value of the line voltage.
                               NEOPIS
                             METi-2500
www.Elec-Engg.com
                                                                                 V1/V1
                                                                                 A1
                                      100
                                      90                                         kVA
                                      80                                         Peak
                                      70
                                      60                                 x1000
                                      50
                                      40
                                                                                 V2/V2
                                                                                 A2
                                LOAD(%)                                          kVAR
                                                                                 PF
                                                                        x1000
                                 VTHD                                            V3/V3
                                 ITHD                                            A3
                                 DMD                                             kW
                                 MAX                                             Hz
                                 MON                                    x1000
ESC ENT
                                                      27
                    ③ The current indication mode
                       Enables the instant indication of the three-phase current as is shown in
                       figure 16.   In this case, a corresponding current unit indication LED lights
                       up.    When a current value exceeds 9,999A, the x1000LED lights up,
                       indicating that the digits has been changed to the unit of Kilo..
                                  NEOPIS
                               METi-2500
                                                                                   V1/V1
                                                                                   A1
                                       100
www.Elec-Engg.com
                                       90                                          kVA
                                       80                                          Peak
                                       70
                                       60                                 x1000
                                       50
                                       40
                                                                                   V2/V2
                                                                                   A2
                                  LOAD(%)                                          kVAR
                                                                                   PF
                                                                          x1000
                                    VTHD                                           V3/V3
                                    ITHD                                           A3
                                    DMD                                            kW
                                    MAX                                            Hz
                                    MON                                   x1000
ESC ENT
                                                      28
                    ④ The electric power indication mode
                       Enables the instant to indicate the values of phase total apparent power,
                       active and reactive power as is shown in figure 17.         In this case, a
                       corresponding current unit indication LED lights up.       When a value of
                       electric power exceeds 9,999kVA, 9,999kVAR or 9,999kW, the x1000LED
                       lights up, indicating that the digits has been changed to a unit of Mega
                                 NEOPIS
                               METi-2500
www.Elec-Engg.com
                                                                                   V1/V1
                                      100                                          A1
                                      90                                           kVA
                                      80                                           Peak
                                      70
                                      60                                  x1000
                                      50
                                      40                                           V2/V2
                                                                                   A2
                                LOAD(%)
                                                                                   kVAR
                                                                                   PF
                                                                          x1000
                                    VTHD                                           V3/V3
                                    ITHD                                           A3
                                    DMD                                            kW
                                    MAX                                            Hz
                                     MON                                 x1000
ESC ENT
                                                     29
                    ⑤ The peak power, power-factor and frequency indication mode
                       Enables the instant indication of the values of peak electric power, power-
                       factor and frequency as is shown in figure 18.    As for the peak electric
                       power, the highest value of momentary power, after the reset is executed.
                       When a value of peak power exceeds 9,999kW, the x1000LED lights up,
                       indicating that the digits has been changed to a unit of Mega.         The
                       power-factor is the represented as a value between –1 and +1, among
                       which conductive power-factor has a negative value and inductive power-
                       factor, a positive value. Frequency is represented as a value between 45
                       and 65Hz.
www.Elec-Engg.com
                             NEOPIS
                           METi-2500
                                                                              V1/V1
                                   100                                        A1
                                   90                                         kVA
                                   80
                                   70
                                                                              Peak
                                   60                                 x1000
                                   50
                                   40                                         V2/V2
                                                                              A2
                             LOAD(%)
                                                                              kVAR
                                                                              PF
                                                                     x1000
                               VTHD                                           V3/V3
                               ITHD                                           A3
                               DMD                                            kW
                               MAX                                            Hz
                               MON                                   x1000
ESC ENT
Figure 18) The peak power, power-factor and frequency indication mode
                                                    30
                    ⑥ The active energy indication mode
                       Indicates the values of active energy in eight digits as is shown in
                       figure 19.   Since electric energy is a cumulative value, this unit is
                       employed with a value indicating system in eight digits to enhance
                       precision. Hence, it is enabled to indicate a value of up to 9,999,999kWh
                       and goes back to 0 to cumulate from there if a value exceeds its maximum
                       indicative value.   In figure 19, the electric energy can be read as 152,
                       379kWh, which is being displayed even when the power is disconnected
                       by applying a non-volatile EEPROM.
www.Elec-Engg.com
                              NEOPIS
                            METi-2500
                                                                                  V1/V1
                                                                                  A1
                                     100
                        Indicate energy
                                     90                                           kVA
                                     80                                           Peak
                                     70
                                     60                                 x1000
                                     50
                                     40
                                                                                  V2/V2
                        UpperLOAD
                             4digits                                              A2
                             LOAD(%)                                              kVAR
                                                                                  PF
                                                                        x1000
                                VTHD
                        Lower 4digits                                             V3/V3
                                ITHD                                              A3
                                DMD                                               kW
                                MAX                                               Hz
                                MON                                     x1000
ESC ENT
                                                      31
                    ⑦ The reactive energy indication mode
                       Indicates the values of reactive energy in eight digits as is shown in
                       figure 20.   Since an energy is a cumulative value, this unit is employed
                       with a value indicating system in eight digits to enhance precision.
                       Hence, it is enable to indicate a value of up to 99,999,999kWh and goes
                       back to 0 to cumulate from there if a value exceeds this maximum
                       indicative value.   In figure 20, the electric energy can be read as 52,
                       117kVARh, which is being displayed even when the power is disconnected
                       by applying a non-volatile EEPROM.
www.Elec-Engg.com
                              NEOPIS
                            METi-2500
                                                                                 V1/V1
                                                                                 A1
                                     100
                        Indicate energy
                                     90                                          kVA
                                     80                                          Peak
                                     70
                                     60                                 x1000
                                     50
                                     40
                                                                                 V2/V2
                        UpperLOAD
                             4digits                                             A2
                             LOAD(%)                                             kVAR
                                                                                 PF
                                                                       x1000
                                VTHD
                        Lower 4digits                                            V3/V3
                                ITHD                                             A3
                                DMD                                              kW
                                MAX                                              Hz
                                MON                                    x1000
ESC ENT
                                                      32
                    ⑧ The demand current and power indication mode(only E-version)
                      The METi E-version indicates the values of demand current and power in
                      eight digits as is shown in figure 21.
                     The demand current is a three phase average current supplied during the
                     demand time(15minute).
                     When a value of demand current exceeds 9,999A, the x1000LED lights up,
                     indicating that the digits has been changed to a unit of kA.
                     The demand power is a three phase average power supplied during the
                     emand time(15minute).
                     When a value of demand power exceeds 9,999kW, the x1000LED lights up,
www.Elec-Engg.com
                              NEOPIS
                            METi-2500
                                                                                V1/V1
                                                                                A1
                                    100
                                    90                                          kVA
                                    80                                          Peak
                                    70
                                    60                                 x1000
                                    50
                                    40
                                                                                V2/V2
                                                                                A2
                              LOAD(%)                                           kVAR
                                                                                PF
                                                                       x1000
                                VTHD                                            V3/V3
                                ITHD                                            A3
                                DMD                                             kW
                                MAX                                             Hz
                                MON                                   x1000
ESC ENT
                                                       33
                    ⑨ The max demand current and power indication mode(only E-version)
                      The METi E-version indicates the values of max demand current and power
                     in eight digits as is shown in figure 22.
                     A max demand current is a max value among the demand currents, is
                     occurred during a month.
                     When a value of max demand current exceeds 9,999A, the x1000LED lights
                     up, indicating that the digits has been changed to a unit of kA.
                     A max demand power is a max value among the demand powers, is
                     occurred during a month.
                     When a value of max demand power exceeds 9,999kW, the x1000LED
www.Elec-Engg.com
                     lights up, indicating that the digits has been changed to a unit of Mega.
                     To indicate the max demand mode, the DMD led and MAX led light up.
                              NEOPIS
                            METi-2500
                                                                                V1/V1
                                                                                A1
                                    100
                                    90                                          kVA
                                    80                                          Peak
                                    70
                                    60                                 x1000
                                    50
                                    40
                                                                                V2/V2
                                                                                A2
                              LOAD(%)                                           kVAR
                                                                                PF
                                                                       x1000
                                VTHD                                            V3/V3
                                ITHD                                            A3
                                DMD                                             kW
                                MAX                                             Hz
                                MON                                    x1000
ESC ENT
Figure 22) The max demand current and power indication mode
                                                       34
                    ⑩ The monthly max demand and power factor indication mode
                       (only E-version)
                     The METi E-version indicates the values of monthly max demand and power
                     factor in eight digits as is shown in figure 22.
                     A monthly max demand is a max value, is occurred at the last month.
                     When a value of monthly max demand exceeds 9,999kW, the x1000LED
                     lights up, indicating that the digits has been changed to a unit of Mega.
                     A monthly power factor is the average power factor occurred at the last
                     month.
                     The display range for power factor is from zero to one.
www.Elec-Engg.com
                     To indicate the monthly max demand mode, the DMD led lights up and the
                     ‘Mon’ characters is displayed at the first segments
                                                                  Month indication
                                                                  (Mon)
                              NEOPIS
                            METi-2500
                                                                                     V1/V1
                                                                                     A1
                                     100
                                     90                                              kVA
                                     80                                              Peak
                                     70
                                     60                                   x1000
                                     50
                                     40
                                                                                     V2/V2
                                                                                     A2
                              LOAD(%)                                                kVAR
                                                                                     PF
                                                                          x1000
                                VTHD                                                 V3/V3
                                ITHD                                                 A3
                                DMD                                                  kW
                                MAX                                                  Hz
                                MON                                       x1000
ESC ENT
Figure 23) The monthly max demand and power factor indication mode
                                                       35
                    ⑪ The monthly active energy mode (only E-version)
                     The METi E-version indicates the values of monthly active energy
                     accumulated in eight digits as is shown in figure 22.
                     A monthly active energy is accumulated energy data, is occurred at the last
                     month.
                     Since electric energy is a cumulative value, this unit is employed with a
                     value indicating system in eight digits to enhance precision.   Hence, it is
                     enabled to indicate a value of up to 9,999,999kWh and goes back to 0 to
                     cumulate from there if a value exceeds its maximum indicative value.
                     In figure 24, the electric energy can be read as 152, 379kWh, which is being
www.Elec-Engg.com
                              NEOPIS
                           METi-2500
                                                                                V1/V1
                              Energy                                            A1
                                     100
                                      90                                        kVA
                              Indication
                                     80                                         Peak
                                     70
                                     60                                x1000
                                     50
                                     40
                                                                                V2/V2
                        UpperLOAD
                             4digit                                             A2
                             LOAD(%)                                            kVAR
                                                                                PF
                                                                       x1000
                                VTHD
                        Lower 4digit                                            V3/V3
                                ITHD                                            A3
                                DMD                                             kW
                                MAX                                             Hz
                                MON                                    x1000
ESC ENT
                                                      36
                    ⑫ The reverse power indication mode(only E-version)
                     The METi E-version indicates the values of reverse power in four digits as is
                     shown in figure 25.
                     The reverse power is occurred power when the current direction is reverse.
                     When a value of reverse power exceeds 9,999kW, the x1000LED lights up,
                     indicating that the digits has been changed to a unit of Mega.
                     To indicate the reverse power mode, the ‘rE -’ characters is displayed at the
                     first segments
                               NEOPIS                     (Reverse - )
                             METi-2500
                                                                                     V1/V1
                                                                                     A1
                                      100
                                      90                                             kVA
                                      80                                             Peak
                                      70
                                      60                                  x1000
                                      50
                                      40
                                                                                     V2/V2
                                                                                     A2
                                LOAD(%)                                              kVAR
                                                                                     PF
                                                                          x1000
                                  VTHD                                               V3/V3
                                  ITHD                                               A3
                                  DMD                                                kW
                                  MAX                                                Hz
                                  MON                                    x1000
ESC ENT
                                                     37
                    ⑬ The reverse active energy indication mode(only E-version)
                     The METi E-version indicates the values of reverse active energy
                     accumulated in eight digits as is shown in figure 26.
                     A reverse active energy is accumulated an active energy, is occurred at the
                     reverse current.
                     Since a reverse active energy is a cumulative value, this unit is employed
                     with a value indicating system in eight digits to enhance precision.   Hence,
                     it is enabled to indicate a value of up to 9,999,999kWh and goes back to 0 to
                     cumulate from there if a value exceeds its maximum indicative value.
                     In figure 26, the reverse active energy can be read as 52,379kWh, which is
www.Elec-Engg.com
                              NEOPIS
                           METi-2500
                                                                                V1/V1
                      Reverse Energy                                            A1
                                    100
                                    90                                          kVA
                      Indication    80                                          Peak
                                    70
                                    60                                 x1000
                                    50
                                    40
                                                                                V2/V2
                      Upper 4LOAD
                             digit                                              A2
                             LOAD(%)                                            kVAR
                                                                                PF
                                                                       x1000
                                VTHD
                      Lower 4 digit                                             V3/V3
                                ITHD                                            A3
                                DMD                                             kW
                                MAX                                             Hz
                                MON                                    x1000
ESC ENT
                                                      38
                    ⑭ The load factor indication
                       Indicates a ratio of currently applied electric current based on the rated
                       current.   A value is indicated by a total of seven LEDs, of which three are
                       in green, two in yellow and two in red, representing light, medium and
                       overload, respectively.
                                                        39
                    Table 5) The items for diagnosis
                               Items for diagnosis              Indicative values
                            Electric connection error                       1
                                Watch dog reset                             2
                                   Memory fail                              4
                                 EEPROFM fail                               8
                                 Setup value fail                       16
                                 Abnormal reset                         32
                                  Metering fail                         64
www.Elec-Engg.com
                            NEOPIS
                          METi-2500
                                                                                V1/V1
                                                                                A1
                                  100
                                  90                                            kVA
                                  80                                            Peak
                                  70
                                  60                                x1000
                                  50
                                  40
                                                                                V2/V2
                                                                                A2
                            LOAD(%)                                             kVAR
                                                                                PF
                                                                    x1000
                              VTHD                                              V3/V3
                              ITHD                                              A3
                              DMD                                               kW
                              MAX                                               Hz
                              MON                                   x1000
ESC ENT
                                                     40
                    d) The Methods of Resets of Energy, Peak Power
                       The methods of resets of some data including effective/unavailable energy,
                       peak power and diagnosis information that are saved in the EEPROM are as
                       follows:
                      ① Go to the desired measuring indicative window by using the UP and Down
                        keys.
                      ② Press the ESC and ENTER keys simultaneously for three seconds,
                        referring to figure 22.   As for the diagnosis information, if an error prolongs,
                        it cannot be reset.
                      ③ In the E-version, the backup data is reset as same method with upper.
www.Elec-Engg.com
                                     NEOPIS
                                   METi-2500
                                                                                         V1/V1
                                                                                         A1
                                           100
                                           90                                            kVA
                                           80                                            Peak
                                           70
                                           60                                   x1000
                                           50
                                           40
                                                                                         V2/V2
                                                                                         A2
                                     LOAD(%)                                             kVAR
                                                                                         PF
                                                                                x1000
                                       VTHD                                              V3/V3
                                       ITHD                                              A3
                                       DMD                                               kW
                                       MAX                                               Hz
                                       MON                                     x1000
ESC ENT
                      Figure 22) The screen for reset of energy, peak power and diagnosis
                                  information
                                                           41
                    e) The time setting mode(only E-version)
                      ① Entering time setting mode
                        Press the ESC and Down keys simultaneously for three seconds, referring
                        to figure 29.   Then, as is shown in figure 30, the first item of the time setting
                        menu, the setting of the year will appear and the dot of year will be blinking.
                                 NEOPIS
                              METi-2500
                                                                                     V1/V1
www.Elec-Engg.com
                                                                                     A1
                                        100
                                        90                                           kVA
                                        80                                           Peak
                                        70
                                        60                                  x1000
                                        50
                                        40
                                                                                     V2/V2
                                                                                     A2
                                 LOAD(%)                                             kVAR
                                                                                     PF
                                                                            x1000
                                   VTHD                                              V3/V3
                                   ITHD                                              A3
                                   DMD                                               kW
                                   MAX                                               Hz
                                   MON                                      x1000
ESC ENT
                                                          42
                    ② Change time setting
                     To change time setting, use the Up and Down keys and select a setting
                     menu.
                     Press Ent key and the dot and time item will be blinking
                     Press the Up or down keys to increase or decrease a time setting value
                     while the time setting item on the line of the Segment flickers.
                     Press enter key to save the changed value, which will stop the flickering of
                     the setting menu.
                     Press the ESC key to exit the setting mode and go back to the measuring
                     display mode
www.Elec-Engg.com
ESC ENT
                                                      43
                      NEOPIS
                    METi-2500
                                                                      V1/V1
                       Hour100                                        A1
                           90                                         kVA
                           80                                         Peak
                           70
                           60                                 x1000
                           50
                           40
                                                                      V2/V2
                       Minute                                         A2
                      LOAD(%)                                         kVAR
                                                                      PF
www.Elec-Engg.com
                                                              x1000
                        VTHD                                          V3/V3
                       Sec
                        ITHD                                          A3
                        DMD                                           kW
                        MAX                                           Hz
                        MON                                   x1000
ESC ENT
                                            44
                    4 Order Information
                                          METi
                       TYPE1
                         2500 : Large Size Meter
                       TYPE2
                         S: Standard Version
                         E:Energy Version
www.Elec-Engg.com
                       Input Current
                         5: 5A/ 1: 1A
                       Frequency
                         60:60Hz/ 50:50Hz
                       COMM
                         NC: None
                         CM: MODBUS
                         CD: DNP3.0
                         CL: LonWorks
HARMONIC
                                                      45
                                      NEOPIS Co,. Ltd
www.Elec-Engg.com
                    E-Mail
                         neopisweb@neopis.com
                    Headquarter
                         623, U-Chun Factopia Bd, 196 Anyang-7dong,
                         Manan-gu, Anyang City, Kyonggi-do, Korea
                         430-017
                         Tel : +82-31-467-2700
                         FAx: +82-31-467-2711
                                        Printed in Korea
                                  Revision Date : Nov 25, 2004
                                                 46
     www.Elec-Engg.com
47