PERKINS 150 kVA

This document provides specifications for a 150 kVA standby and 135 kVA prime power generator set including its size, weight, fuel tank capacity, noise level, and engine details. Key specifications of the alternator are also listed. The document defines the differences between continuous, standby, and prime power ratings.

Uploaded by

Андрей
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
95 views2 pages

PERKINS 150 kVA

This document provides specifications for a 150 kVA standby and 135 kVA prime power generator set including its size, weight, fuel tank capacity, noise level, and engine details. Key specifications of the alternator are also listed. The document defines the differences between continuous, standby, and prime power ratings.

Uploaded by

Андрей
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Output Power

Standby Power (ESP) kVA 150


kW 120
Prime Power (PRP) kVA 135
kW 108

Size Wx L x H Weight Fuel Tank Noise dB(A)


(mm) (kg) (lt) @ 7m
Canopied 1100x3320x1600 1875 260 71
Open Skid 1100x2350x1350 1454 260 N/A

Continuous Power Standby Power Prime Power


The maximum power which a generating The max power available during a The maximum power which a generating
set is capable of delivering continuously variable electrical power sequence, set is capable of delivering continuously
whilst supplying a constant electrical load. under the stated operating conditions, for whilst supplying a variable electrical load.
Average load can be 100%. The which a generating set is capable of Average load should be 70%. The
generator must not be overloaded. delivering in the event of a utility power generator can be overloaded 10% for 1
outage or under test conditions for up to hour per 12 hrs.
200 hrs of operation per year under
average of 70% load. Overloading isn’t
permissible.
Engine
Manufacturer PERKINS
Model 1106A-70TG1
Cylinder Configuration INLINE
No of Cylinders 6
Displacement lt 7,01
Stroke mm 135
Bore mm 105
Compression Ratio 18,2:1
Aspiration TURBOCHARGE-INTERCOOLER
Governor Type MECHANIC
Cooling System WATER
Coolant Capacity lt 21
Lubrication Oil Capacity lt 16,5
Electrical System VDC 12
Speed / Frequency 50 Hz rpm 1500 rpm / 50 Hz
Engine Gross Power (Standby 50 Hz) kW 137
Fuel Consumption %110 ESP 50 Hz lt/h 33,8
Fuel Consumption %100 PRP 50 Hz lt/h 30,28
Fuel Consumption %75 PRP 50 Hz lt/h 22,7
Fuel Consumption %50 PRP 50 Hz lt/h 15,9
Exhaust Outlet Temperature 50 Hz °C 576
Exhaust Gas Flow 50 Hz m3/min 22,66
Combustion Air Flow 50 Hz m3/min 8,09
Cooling Air Flow 50 Hz m3/min 182

Alternator
Manufacturer LEROY-SOMER
Model TAL044H
No of Phases 3
Power Factor 0,8
No of Bearings SINGLE
No of Poles 4
No of Leads 6
Voltage Regulation (Steady State) ± %1
Insulation Class H
Degree of Protection IP 23
Excitation System AVR (Automatic Voltage Regulator),
Brushless
Connection Type STAR
Total Harmonic Content (No Load) < %2
Frequency Hz 50
Voltage Output 50 Hz VAC 230 / 400
Rated Power (Standby) 400_50 Hz kVA 150
Efficiency (4/4_400 V_50 Hz) % 92,8