DG 05 002 e 08 14 Modbus 6878
DG 05 002 e 08 14 Modbus 6878
KG
                                                                        Engine & Turbine Management
                                                                        Am Haselbach 1
                                                                        D-79677 Schönau/Germany
                                   HEINZMANN®
                                   Engine & Turbine Controls
MODBUS
Operating Instructions
                     Copyright 2014 by Heinzmann GmbH & Co. KG. All rights reserved.
       This publication may not be reproduced by any means whatsoever or passed on to any third parties.
HEINZMANN shall not be held liable for any indirect and direct
damage nor for any incidental and consequential damage that results
from application of any of the examples, data or miscellaneous
information as given in this manual.
HEINZMANN shall not provide any guarantee for the design and
planning of the overall technical system. This is a matter of the operator
its planners and its specialist engineers. They are also responsible for
checking whether the performances of our devices match the intended
purpose. The operator is also responsible for a correct initial start-up of
the overall system.
                                                                                    Version Information
Version Information
                                                     Table of Contents
                                                                                                                                      Page
2 Introduction ......................................................................................................................... 11
   2.1 Message format of data transmission ............................................................................ 11
   2.2 Example of a data transmission ..................................................................................... 12
3 Installation ........................................................................................................................... 14
   3.1 Bus topology .................................................................................................................. 14
   3.2 Bus configuration .......................................................................................................... 15
   3.3 RS485-two-wire-system ................................................................................................ 16
      3.3.1 Bus cable in RS485-two-wire-systems .................................................................. 18
      3.3.2 Derivation cable in RS485-two-wire-systems ....................................................... 18
   3.4 RS485-Four-wire-system .............................................................................................. 19
      3.4.1 Bus cable in RS485-four-wire-systems ................................................................. 20
      3.4.2 Derivation cable in RS485-four-wire-system ........................................................ 21
   3.5 RS232 Operation ........................................................................................................... 21
   3.6 Slave participant ............................................................................................................ 22
   3.7 Master participant .......................................................................................................... 22
   3.8 Reference potential ........................................................................................................ 22
   3.9 Shield ............................................................................................................................. 23
   3.10 Line termination .......................................................................................................... 25
   3.11 Line polarization .......................................................................................................... 26
   3.12 Bus accessories ............................................................................................................ 27
   3.13 Device side connection module ................................................................................... 27
   3.14 Connector plug and socket .......................................................................................... 27
7 Parameter description......................................................................................................... 43
   7.1 List 1: Parameters .......................................................................................................... 43
   7.2 List 2: Measurements .................................................................................................... 43
   7.3 List 3: Functions ............................................................................................................ 45
   7.4 List 4: Curves and maps ................................................................................................ 45
10 Index ................................................................................................................................... 48
- The environment
The signal words used in this publication are specifically designed to direct your attention to
possible damage extent!
                  Safety instructions are not only denoted by a signal word but also by hazard
                  warning triangles. Hazard warning triangles can contain different symbols
                  to illustrate the danger. However, the symbol used is no substitute for the
                  actual text of the safety instructions. The text must therefore always be read
                  in full!
                  This symbol does not refer to any safety instructions but offers important
                  notes for better understanding the functions that are being discussed. They
                  should by all means be observed and practiced.
2 Introduction
Modbus is a serial Master-Slave-protocol. This protocol is open and therefore freely
accessible for any user. It provides two transmission modes RTU and ASCII and can be used
on RS232 and RS485 or RS422.
For application of the Modbus protocol, the HEINZMANN control units of the THESEUS
and HELENOS series must be equipped with an add-on pc board. The HEINZMANN
Connection Module uses exclusively RTU mode. Throughout this document, it will therefore
be only this mode that is made reference to. As a connection an RS485 or RS422 interface is
provided. Hence an additional level converter will be required for connection to an RS232
interface.
Any details concerning the design and operation of the interface relate to the below
specifications which can be downloaded from www.modbus.org.
    Hardware reference: Modbus over Serial Line Specification and Implementation Guide
    V1.02 – Dec 20, 2006
    Protocol reference: Modbus Application Protocol Specification V1.1b3 – April 26, 2012
The following sections give a general overview of the functionality, concept and structure of
the Modbus protocol. Experienced Modbus users may skip them and continue with chapter
  3 Installation.
                                Request
                                master
                                                          Reply
                                                          slave
Figure 1: Request-reply-cycle
   The Modbus protocol defines a simple Protocol Data Unit (PDU) independent of the type
   of network used and includes a function code indicating by which of the diverse actions the
   data is to be processed.
Operating Instructions Modbus                                                                11
2 Introduction
     As additional information, the Application Data Unit (ADU) includes the participant
     address (ID) allowing Master and Multi-Slave operation, and a so-called Error Check
     defined as the check-sum over the characters to be transmitted. The address and the error
     check are added before and behind the character string as shown in Figure 2 and are
     transmitted together with it.
3 Installation
The installation of a Modbus data bus system requires particular care, especially with regard
to electromagnetic compatibility as well as to the data transmission rate to be obtained in
dependence on type and length of the conductor. In order to avoid errors in the pre-
commissioning phase, the most important points concerning the installation will be discussed
in advance. More details will be dealt with in later chapters or are to be found in the Modbus
Specification, see section 2 Introduction.
     A remote data cable (trunk) is running across some longer distance from a Modbus Master
     to one or more Modbus Slaves. Preferably, the individual Slaves are to be connected to the
     trunk directly by a linear structure (from node to node, Daisy-Chain structure) or by a short
     derivation cable.
     The elements of the bus are:
     ITr – Trunk Interface – a bus cable. For different distances, cables with suitable properties
     must be used, such as characteristic impedance, shield and line construction. The cable
     lines form a bus of linear structure which is characterized by having two ends. Maximum
   length is 1,200 m. For more details see the sections 3.3.1 Bus cable in RS485-two-wire-
   systems and 3.4.1 Bus cable in RS485-four-wire-systems.
   IDv – Derivation Interface – a derivation cable. By the derivation cable all bus signals, the
   reference potential and the shield must be conducted from the bus to the participant (Slave
   or Master). A derivation cable may connect several participants, e.g., the devices in a
   switch cabinet. Derivation cables must not be longer than 20 m. If there is a local tap with
   more than one derivation cables connected, the cable length must be limited to 40 m
   divided by the number of derivation cables. For more details see sections
     3.3.2 Derivation cable in RS485-two-wire-systems and           3.4.2 Derivation cable in
   RS485-four-wire-system.
   Passive TAP – a passive tap. The tap connects the bus cable with the derivation cables,
   i.e., the data lines, the line for the reference potential and the shield. Possibilities of
   earthing and termination can be provided within the tap.
   Active Tap – a tap having an integrated bus driver. The rest is very much the same as with
   the passive tap.
   AUI – Attachment Unit Interface – a data cable connecting active taps with the
   participants.
   Slave – a participant serving as a Slave device. The maximum number of participants of
   the bus without repeater is 31. For more details see section 3.6 Slave participant.
   Master - a participant serving as a Master device. Only one Master may be connected to
   the bus. For more details see section 3.7 Master participant.
   LT – Line Terminator – Bus terminator. At either extremity of the bus a line termination
   must be provided. For more details see section 3.10 Line termination.
     Master. This will also require an additional line with the reference potential (Common).
     RS232 operation is provided only for a point-to-point connection.
     As communication equipment the following items will be of importance:
         Slave participant,
         Master participant ,
         Bus cable,
         Derivation cable,
         Reference potential,
         Shield,
         Bus earthing,
         Line termination, and
         Line polarization.
     3.3 RS485-two-wire-system
     In a two-wire-system, bi-directional data are being transmitted, viz. Master-Slave and
     Slave-Master, by a common balanced twisted pair of conductors. There is, in addition, a
     separate conductor (e.g. a twisted pair of conductors) for the reference potential
     (Common). The complete cable must have an external shield.
     The 2-wire-system constitutes the configuration most frequently used in practice. The
     layout of the bus must be about the same as shown in Figure 4. In a daisy-chain structure,
     no derivation cables may be used.
                                                                       Master device
                                                                 +5V
                                                                                           DC       D
                                                                        Pull Down
                                                                                           DC
                                                             Pull Up
                                                                                                R
                                                                                                            PE
D1
                                                                                                                                       150 Ohm
                                                                       D0
                                                                       Common
Shield
PE
     DC             R                   DC       R                                                                DC      R
     DC                  D         PE   DC               D               PE                                       DC               D         PE
                                             Contact                   EIA/TIA-
 Designati                                      at                       485
                        for Device                                                                             Description
    on                                       Participa                 Designati
                                                nt                        on
     D1                       I/O               yes                                 B/B’        Transmitter-receiver-terminal 1 (+),
                                                                                                voltage V1
                                                                                                (V1 > V0 for binary 1 and OFF-state
                                                                                                respectively)
     D0                       I/O               yes                                 A/A’        Transmitter-receiver-terminal 0 (–),
                                                                                                voltage V0
                                                                                                (V0 > V1 for binary 0 and ON-state
                                                                                                respectively)
  Common                       -                yes                                 C/C’        Reference potential
                                                                                                and optionally as supply potential
   Shield                      -                yes                                  -          Cable shield
     The connectors A and A’ pin no. 8 and 9 respectively and B and B’ pin no. 4 and 5
     respectively have to be shorted to use the two-wire-system with the Modbus connection
     module for HEINZMANN devices.
   3.4 RS485-Four-wire-system
   With 4-wire-systems, data transmission in both directions, viz. Master-Slave and Slave-
   Master, is made by two separate balanced twisted pairs of conductors. There is, in addition,
   a separate conductor (e.g., a twisted pair of conductors) for the reference potential
   (Common). The complete cable must have an external shield.
   An example of the bus configuration is shown in Figure 5. In the daisy-chain structure no
   derivation cable may be used.
                                                                                      Master device
                                                             +5V                     +5V
Pull Down
                                                                                            Pull Down
                                                                                                           D            DC
                                                          Pull Up
                                                                                  Pull Up
                                                                                                                 R      DC      PE
                                                                    TXD 1
 150 Ohm                                                            TXD 0                                                                          150 Ohm
                                                                    RXD 1
 150 Ohm                                                            RXD 0                                                                          150 Ohm
                                                                    Common
Shield
PE
     DC       R                      DC      R                                                                                DC       R
     DC               D        PE    DC               D              PE                                                       DC               D     PE
                                             Contact                             EIA/TIA-485
                          for Device
   Desig-                                      at                                Designation
                                                                                                                              Description
   nation                                    Partici-
                   Master           Slave     pant                               Master                  Slave
                                     Contact      EIA/TIA-485
                     for Device
     Desig-                            at         Designation
                                                                              Description
     nation                          Partici-
                   Master    Slave    pant       Master    Slave
                    DC
                         DC
                                                                                                    DC
                                                                                                         DC
                                                               UCM1       UCM
  CEMV                                       Common
                                                                                                                         CEMV ≈ 1uF
          GND1       CISO     COMMON                           UCM2                  COMMON CISO ≈ 50pF        GND2
                                               PE
         PE                                                                                                              PE
UCM1 – Common mode voltage from transmitter with interference induced among the conductors within the bus cable.
UCM2 – Interference induced between Common line and protective earthing conductor.
                     The indicated common mode voltage UCM must not exceed the level of -7/+12 V
                     (specific working range). The reference potential (Common) is to be connected
                     to all participants. Then UCM = UCM1 will hold for interferences.
         Note
    3.9 Shield
    The Modbus standard requires a shielded cable.
    According to this standard, the shield of every cable must be connected at one end to the
    protective earthing conductor (PE). The shield of any cable is to be connected either to the
    shield of the other cable or at one of its extremities to protective earthing. The admissible
    variants are shown in Figure 4, Figure 5, Figure 7 and Figure 8.
    According to our recommendations, the optimum shield configuration will be best as
    follows:
              A common shield for the bus cables. The only earthing point must preferably be
              located on the Master or its tap.
              A separate shield for the derivation cables. The only earthing point must be located in
              the participant's cubicle.
    These rules are observed by the examples in Figure 4, Figure 5 and Figure 8.
                                                                       Cabinet 1
                                                                       Master device
                                                                 +5V
                                                                                    DC            D
                                                                        Pull Down
                                                             Pull Up
                                                                                    DC   R
                                                                                                        PE
      150 Ohm
                                                                                                                                  150 Ohm
                               Common
                               Shield
                          PE                                 PE                                   PE
     DC         R                       DC       R                                                                    R
                                                                                                             DC
     DC               D                 DC               D                                                   DC
                                PE                                            PE                                              D
                                                                                                                                            PE
     Slave device l                     Slave device m                                                       Slave device n
     Cabinet 2                          Cabinet 3                                                            Cabinet 4
                                                                                             Figure 7: Reference potential and shield
                                                                       Cabinet 1
                                                                       Master device
                                                                 +5V
                                                                                    DC            D
                                                                        Pull Down
                                                             Pull Up
                                                                                    DC   R
                                                                                                        PE
      150 Ohm
150 Ohm
Common
Shield
PE
     DC         R                       DC       R                                                                    R
                                                                                                             DC
     DC               D                 DC               D                                                   DC
                                PE                                            PE                                              D
                                                                                                                                            PE
     Slave device l                     Slave device m                                                       Slave device n
     Cabinet 2                          Cabinet 3                                                            Cabinet 4
                                                                                             Figure 8: Reference potential and shield
   The external shield serves as an electrostatic and electromagnetic shield and must not be
   used as a conductor for the reference potential. The shield must not have a second electric
   connection to the earthing bus or to the casing.
                                             TXD
    L                                        1
                                            TXD                                                     L
                                            0RXD
    T                                                                                               T
    L                                       1RXD                                                    L
                                             0
    T                                                                                               T
   In order to obtain optimum transmission quality and/or signal quality, particularly over
   long distances, the data line is to have a termination as a twisted data conductor pair at both
   extremities according to Figure 9. For this, termination load must correspond to the
   characteristic impedance of the data line.
                                                                            Master device
                                                     +5V                   +5V
                                                            Pull Down
                                                                                  Pull Down
                                                                                              D          DC
                     Slave device n
                                                  Pull Up
Pull Up
                                                                                                    R    DC
                        D     R
     If the polarization is implemented in the active/passive tap of the Master device the tap
     must be supplied 5 V DC either from the Master device or from an electrically separated
     source.
                 Line polarization serves to set the OFF-state, where the OFF-state designates
                 the silent state when there is no transmission from any participant. Actually in
       Note      silent state, however, a polarization current between 3.6 and 5.1 mA DC must
                 be flowing. With a DC termination by 150 Ohms, this will in silent state cause
                 a differential signal of 0.27 to 0.38 V DC. The maximum polarization current
                 will increase interference immunity.
4 Module functions
The HEINZMANN control unit is always defined as a Slave and by request from the
connected Master can be made to execute a data transfer as determined by the function code.
In accordance with the function code, the reply following this request may consist of a read-
out of data, an acknowledgement of data received, an exception response or no response.
     The diagnostics function is confined to the sub-function codes that are specified in Table 7;
     any other sub-functions are not supported and are rejected through an exception response.
     The request data field or data word is to be assigned the value 0x0000 except for the sub-
     function code 0x0000 which supports any length and selectable values of the data words.
   This functionality serves for diagnosing the communication result and allows to indivi-
   dually or globally reading out and reset the counter states that are being incremented with
   regard to success, error of communication, etc.
     Table 9 gives an overview of the options for setting the transmission types with regard to
     parity bit and stop bits.
     Example of parameterization:
     Modbus functionality is to be activated with the baud rate set to 9600 Baud and the Slave
     device address to 1. The data transmission type for a character is to be selected as
     including one bit for even parity and one stop bit. It should be noted that after making
     modifications to the settings for the baud rate, the activation of the functionality and the
     transmission type these changes must be saved and the control unit reset.
              Number Parameter                      Value          Unit
                21800      Modb:Baudrate             9.600         kBaud
                21801      Modb:SlaveID                  1
                25800      ModbusOn                      1
                25801      Modb:ParityBitOn              1
                25802      Modb:ParityOddOrEven          0
                25803      Modb:OneOrTwoStopBit          1
              Indication
                23800      Modb:Baudrate             9.600         kBaud
   On request, the shipping state can be modified in dependence of customer wishes and
   project requirements.
                By being invariably set to four the access level for the Modbus allows to
                transmit all measurements and indication values as well as all application
     Note       specific parameters.
     The user is informed about the maximum number of data words that can be read out by the
     measurement
          23810 Modb:NoOfTxParams                   Number of valid parameter numbers in the
                                                    data array.
     Example of parameterization:
     Speed, oil pressure and oil temperature are to be read out via Modbus. A control unit of the
     HELENOS series is being used.
             Number Parameter                         Value      Unit
                29200     Modb:TxParamSet(0)            2000
                29201     Modb:TxParamSet(1)            2905
                29202     Modb:TxParamSet(2)            2909
                29202     Modb:TxParamSet(3)               0
             Indication
                23810     Modb:NoOfTxParams                3
                 2000     Speed                       1500.2     1/min
                 2905     OilPressure                   3.15     bar
                 2909     OilTemp                      -10.2     °C
     The data are transmitted by their external value ranges. As regards the value ranges of the
     different parameters the user should refer to the publications describing the HEINZMANN
     control devices or read them out directly from the control unit using one of the
     HEINZMANN diagnostics tools. To interpret the data words transmitted correctly, account
     must be taken of the number of decimal places and of whether the value range can also be
     negative.
     In the above example, the data word for speed will be transmitted by the value 15002 as
     obtained from 1500.2 10 for one decimal place, that for oil pressure by the value 315 as
     obtained from 3.15 100 for two decimal places, and that for oil temperature by –102 as
     obtained from 10.2 10 for one decimal place.
     Since speed and oil pressure can assume positive values only, it is but the number of digital
     places that must be taken into account as powers of ten. Likewise, if oil temperature is
     interpreted as already signed, it will also be the number of digital places that is to be
     evaluated as power of ten.
     If oil temperature is evaluated as not yet signed the above example will yield a data word
     having the value 65,434. Any values greater than or equal to 32,768 are to be interpreted as
     negative values provided the external value range admits of negative values. The correct
     signed value is obtained as the difference between the data word and 65,536, and as a
34                                                                       Operating Instructions Modbus
                                                                  5 Parameterization and commissioning
   second step it is but the number of digital places that must be taken into account to
   calculate the final value.
                 If in the above example any request should include a start address equal or
                 greater than two or if the quantity of data to be read exceeds two data words,
     Note        an exception response will be transmitted.
                                             Data Field
                         Index                                     Type
                            0      8 Bit (high)   8 Bit (low)      switch
                            1                16 Bit                sensor
                            2                16 Bit                sensor
                            3                16 Bit                sensor
                            4                16 Bit                sensor
      The data received by the control unit can be viewed via these indication values
         23820 Modb:RxBinary                      Binary values 16 bits wide, and
         23821 Modb:RxSensor(0) to
         23824 Modb:RxSensor(3)                   Sensor values.
      Example of parameterization:
      As in the above example, the speed, oil pressure and oil temperature must be read via
      Modbus. It must be possible to specify the PID parameters for the speed governor
      100 Gain, 101 Stability and 102 Derivative using Modbus. A control unit of the
      HELENOS series is being used.
               Number Parameter                  Value         Unit
                 29200      Modb:ParamSet(0)       2000
                 29201      Modb:ParamSet(1)       2905
                 29202      Modb:ParamSet(2)       2909
                 29203      Modb:ParamSet(3)        100
                 29204      Modb:ParamSet(4)        101
                 29205      Modb:ParamSet(5)        102
                 29206      Modb:ParamSet(6)          0
               Activation
                 25804      Modb:ExtendedOn           1
               Indication
                 23810      Modb:NoOfParams            6
                  2000      Speed                 1500.2       1/min
                  2905      OilPressure             3.15       bar
                  2909      OilTemp                -10.2       °C
      For further details concerning the parameterization of sensors and switching function,
      refer to the chapters Sensors and Inputs and Outputs of the respective Basis
      Information. In this brochure, it is only the specific extension of the particular
      functionality required for Modbus that will be dealt with.
               Indication
                  2900      PowerSetpoint             50.0       %
                  3074      ErrModbusComm                0
                 23821      Modb:RxSensor(0)           0.0       %
                 23822      Modb:RxSensor(1)          50.0       %
                 23823      Modb:RxSensor(2)           0.0       %
                 23824      Modb:RxSensor(3)           0.0       %
             Activation
               25804      Modb:ExtendedOn              1
             Indication
                2900      PowerSetpoint             50.0       %
                3074      ErrModbusComm                0
               23821      Modb:RxSensor(0)           0.0       %
               23822      Modb:RxSensor(1)          50.0       %
               23823      Modb:RxSensor(2)           0.0       %
               23824      Modb:RxSensor(3)           0.0       %
             Indication
                2815      SwitchSpeedFix1            1
                3074      ErrModbusComm              0
               23820      Modb:RxBinary             04        Hex
             Activation
               25804      Modb:ExtendedOn            1
             Indication
                2815      SwitchSpeedFix1            1
                3074      ErrModbusComm              0
               23820      Modb:RxBinary             04        Hex
             Activation
               25804      Modb:ExtendedOn            1
             Indication
                3851      LastIdentifier            94
               23816      Modb:SaveParameter         1
6 Technical data
Interface:                     EIA/TIA-485/422 standard
                               4-wire interface
Insulation:                    electrically separated
Insulation voltage:            1000 Volts(RMS), 1 min
Signal voltages against
reference potential (Common): –7 V to +12 V D.C.
Interference immunity (ESD): to EN 61000-4-2 (intended)
Connector:                     D-Sub 9 (male)
Signal assignment:             according to Modbus Specification 4-wire interface
7 Parameter description
21800    Modb:Baudrate
         Level:                        4   Modbus
         Range:        9.6..19.2 kBaud     Parameter baud rate, modification only effective after
         Page(s):                    32    reset
21801    Modb:SlaveID
         Level:                        4   Modbus
         Range:                  1..247    Unique device address as Slave
         Page(s):                    32
21820    Modb:RxTimeOut
         Level:                        4   Modbus
         Range:                  0..60 s   Reception time limit for requests for writing binary
         Page(s):                    38    values or sensor values
3074     ErrModbusComm
         Level:                     1      Modbus
         Range:                  0..1      Error indication Modbus communication
         Page(s):                 38
3174     SErrModbusComm
         Level:                     1      Modbus
         Range:        0..255 or 0..1      Error Counter or sentinel for the occurrence of
                                           3074 ErrModbusComm
23800    Modb:Baudrate
         Level:                      4     Modbus
         Range:        9.6..19.2 kBaud     Indication value for the pre-set baud rate
         Page(s):                   32
23801    Modb:BusMessageCnt
         Level:                      4     Modbus
         Range:               0..65535     Quantity of valid received messages
         Page(s):                   42
23802    Modb:CommErrorCnt
         Level:                      4     Modbus
         Range:               0..65535     Quantity of faulty received messages
         Page(s):                   42
23803    Modb:ExceptErrCnt
         Level:                       4   Modbus
         Range:              0..65535     Quantity of exception messages transmitted
         Page(s):                   42
23804    Modb:SlaveMessageCnt
         Level:                       4   Modbus
         Range:              0..65535     Quantity of messages transmitted
         Page(s):                   42
23805    Modb:SlaveNoRespCnt
         Level:                       4   Modbus
         Range:              0..65535     Quantity of messages received requiring no response
         Page(s):                   42    (here: only transmission message from Master)
23806    Modb:BusCharOvrCnt
         Level:                       4   Modbus
         Range:              0..65535     Quantity of messages not correctly received due to
         Page(s):                   42    character overrun
23810    Modb:NoOfTxParams
         Level:                       4   Modbus Basic Version
         Range:                 0..100    Number of valid parameter numbers entered in the data
         Page(s):                   35    field for read access
23810    Modb:NoOfParams
         Level:                       4   Modbus Extended Version
         Range:                 0..100    Number of valid parameter numbers entered in the data
         Page(s):                   35    field for read access and write access
23815    Modb:ResetDevice
         Level:                       4   Modbus Extended Version
         Range:                    0..1   Modbus function: Force reset of the control unit
         Page(s):               36, 41
23816    Modb:SaveParameter
         Level:                       4   Modbus Extended Version
         Range:                    0..1   Modbus function: Save parameter values in the control
         Page(s):               36, 41    unit
23820    Modb:RxBinary
         Level:                       4   Modbus
         Range:       0000..FFFF Hex      Binary values for write access
         Page(s):                   36
23821    Modb:RxSensor(x)
to       Level:                       4   Modbus
23824    Range:              0..65535     Sensor values for write access
         Page(s):                   36
25800    ModbusOn
         Level:                        4   Modbus
         Range:                     0..1   On/Off switch Modbus functionality. Modification will
         Page(s):                    32    be effective after reset only
25801    Modb:ParityBitOn
         Level:                        4   Modbus
         Range:                     0..1   Selection transmission mode with or without parity bit.
         Page(s):                    32    Modification will be effective after reset only
                                           0 = no parity bit
                                           1 = with parity bit
25802    Modb:ParityOddOrEven
         Level:                        4   Modbus
         Range:                     0..1   Selection odd or even parity with parity bit set.
         Page(s):                    32    Modification will be effective after reset only
                                           0 = even parity
                                           1 = odd parity
25803    Modb:OneOrTwoStopBit
         Level:                        4   Modbus
         Range:                     0..1   Selection one or two stop bits. Modification will be
         Page(s):                    32    effective after reset only
                                           0 = two stop bits
                                           1 = one stop bit
25804    Modb:ExtendedOn
         Level:                        4   Modbus Extended Version
         Range:                     0..1   Activation of Modbus Extended Version
         Page(s):                    32
29200    Modb:TxParamSet(x)
to       Level:                    4       Modbus Basic Version
29299    Range:             0..29999       Data field for read access
         Page(s):                 34       Any parameters or measurement numbers must be
                                           entered whose values will be transmitted on request
29200    Modb:ParamSet (x)
to       Level:                        4   Modbus Extended Version
29299    Range:                 0..29999   Data field for read access and write access
         Page(s):                     34   Any parameters or measurement numbers must be
                                           entered whose values will be transmitted on request or
                                           should be received
8 Index of Figures
Figure 1: Request-reply-cycle .................................................................................................. 11
Figure 2: Protocol frame .......................................................................................................... 12
Figure 3: Bus topology ............................................................................................................. 14
Figure 4: RS485 – two-wire-system......................................................................................... 17
Figure 5: Signal definition – four-wire-system ........................................................................ 19
Figure 6: Reference potential ................................................................................................... 23
Figure 7: Reference potential and shield .................................................................................. 24
Figure 8: Reference potential and shield .................................................................................. 24
Figure 9: Line termination in four-wire-system ....................................................................... 25
Figure 10: Line polarization in a four-wire-system ................................................................. 26
9 Index of Tables
Table 1: Master request ............................................................................................................ 13
Table 2: Slave reply.................................................................................................................. 13
Table 3: Slave exception reply ................................................................................................. 13
Table 4 Signal definition – two-wire-system ........................................................................... 17
Table 5: Signal definition – four-wire-system ......................................................................... 20
Table 6: Function codes ........................................................................................................... 28
Table 7: Sub-functions of the diagnostic function ................................................................... 29
Table 8: Exception codes ......................................................................................................... 30
Table 9: Setting for transmission type...................................................................................... 32
Table 10: Write access rights ................................................................................................... 35
Table 11: Write data ................................................................................................................. 36
Table 12: Signal assignment .................................................................................................... 42
10 Index
Access level ......................................................... 33       Interference Immunity .......................................... 42
Baud Rate ..................................................31, 42, 43          Line Termination.................................................. 16
Binary Value .......................................35, 37, 39, 44              Master ..................................... 15, 22, 23, 28, 30, 38
Broadcast.............................................................. 28      Master Participant ...........................................16, 22
Bus Cable ............................................ 14, 15, 16, 23           Parameterization .................................................. 31
Bus Topology ....................................................... 14         Parity ...............................................................12, 42
Channel Type ..................................................38, 39           Parity Bit ...................................................31, 32, 45
Connection Module ...................................11, 14, 27                 Participant Address .............................................. 12
Connector ........................................................27, 42        Polarization ...............................................16, 22, 26
Data Transmission...........................................11, 42              Protocol Reference ............................................... 11
DcDesk 2000 ........................................................ 31         Read Access ........................................ 28, 33, 44, 45
Derivation Cable ............... 15, 16, 18, 19, 21, 23, 25                     Reception Time Limit .....................................37, 43
Device Address .........................................28, 31, 43              Reference Potential15, 16, 18, 19, 21, 22, 26, 27, 42
Diagnostic Function ............................................. 28            Reset Control Unit ....................................35, 40, 44
Diagnostics Tool .......................................12, 31, 34              RTU Mode ................................................11, 12, 42
EIA/TIA-485/422 Standard.......................14, 27, 42                       Save Parameter Values..............................35, 40, 44
Error Check .......................................................... 12       Sensor Value ....................................... 35, 37, 38, 44
Exception Code .........................................12, 30, 42              Shield .................................................. 14, 15, 23, 25
Four-Wire-System .....................................15, 19, 22                Signal Assignment ............................................... 42
Function Code ...........................................11, 28, 42             Signal Voltages .................................................... 42
    0x03 ............................................................12, 33     Slave................................................................15, 28
    0x06 ................................................................. 35   Slave Participant .............................................16, 22
    0x08 ................................................................. 41   Socket................................................................... 27
    0x10 ................................................................. 35   Stop Bits .............................................. 31, 32, 42, 45
Handprogrammer HP-03-03................................. 31                     Sub-Function Code .............................................. 28
Hardware Reference ............................................. 11             Switching Functions ............................................. 39
Insulation.............................................................. 42     Tap .............................. 15, 18, 21, 22, 23, 25, 26, 27
Insulation Voltage ................................................ 42          Termination .......................................................... 25
Interface ..........................................................31, 42      Two-Wire-System .....................................15, 16, 22
    RS232 ...................................................11, 15, 22         Visual Error Indication......................................... 42
    RS422 .........................................................11, 15       Write Access ................................. 28, 35, 37, 44, 45
    RS485 ...................................................11, 15, 22