UNLCDHS Prog EN
UNLCDHS Prog EN
                                   v3, issue 1
                       © C P Electronics 2016
PROGRAMMING OVERVIEW
     This guide is for programming Version 3 detectors or later. If you are not sure what version of detector you
     have please contact CP Electronics Technical Support.
The functionality of programmable devices is controlled by a number of parameters which can be configured and
changed by the following devices:
All parameters can be programmed using the UNLCDHS handset and are listed in this document; only some can
be programmed using the UHS5 handset.
2. Select the product family from the main PRODUCT FAMILY menu and press .
3. Either select the specific product or Generic Product and press . Generic Product lists all the
   parameters used within the family, but some might not be available or applicable for all products.
7. Point the handset directly at the device and press to send the currently selected parameter, or press and
Each device is fitted with an LED that flashes when it successfully receives a valid command - it won't flash if the
parameter doesn't apply to the device or the value is out of range. The device then waits 5 seconds before
processing the command (enabling more efficient use of macros), and then flashes again to indicate completion. If
you switch the device off during this 5 second period, any pending command will be lost.
                                                             ▪2▪
KEYPAD OPERATION
Button               Short press                      Long press
+ SHIFT
                                                     ▪3▪
Button             Short press                       Long press
+ SHIFT
  2       Numbers 2 to 9, or cycles         -                               -
  ABC
          through the list of
  ...     corresponding letters (e.g. 2 =
          ABC).
  9
 WXYZ
                                                    ▪4▪
PARAMETERS
Basic lux switching settings
1. Ambient light level 2. Occupancy 3. Lux On Time 4. Lux Off Time 5. Lux Off Level 6. Lux On Level
                                                         ▪5▪
Detector Params
Parameter             Default   Range/           Description
                                Option
Detection Mode        Pres      Pres             Select Pres to turn lights on when movement is detected and
                                (Presence) /     off when movement ceases. Select Abs to turn lights off when
                                Abs (Absence)    movement ceases, but the lights must be manually turned on
                                                 by a switch or handset first.
Timeout 20 0 - 99 minutes How long the lights stay on for after movement has stopped.
Abs Recovery (secs)   10        0 - 99 seconds   Sets a period for a detector in Absence mode to operate in
                                                 Presence mode after lights are turned off. This enables a
                                                 person to use movement to retrigger lights which have
                                                 switched off while they are still in the room. If Abs Recovery
                                                 (secs) is set to a non-zero value you should also set Inhibit
                                                 (secs) to 1 to detect any occupancy immediately.
Sensitivity On        9         1-9              Sensitivity level for detecting further movement when the
                                                 lights are already on. 1 = minimum, 9 = maximum (least
                                                 movement required to trigger the lights).
Sensitivity Off       9         1-9              Sensitivity level for detecting any movement when the lights
                                                 are off. 1 = minimum, 9 = maximum (least movement required
                                                 to trigger the lights)..
                                                   ▪6▪
Parameter          Default   Range/           Description
                             Option
Manual Timeout     10        0 - 99 minutes   How long the lights stay off after they have been turned off
                                              using a switch or handset before returning to the automatic
                                              Timeout operation.
                                              Example 1:
                                                 When the user leaves the room they switch the light off.
                                                 The lights stay off for 3 minutes even someone walks
                                                 back into the room. The sensor will revert to automatic
                                                 after 3 minutes, and then walking back in the room will
                                                 turn the lights on - the lights will then stay on until no
                                                 movement has been detected for 15 minutes.
                                              Example 2:
                                                 The user turns the lights off but stays in the room (for
                                                 example to give a presentation). Every time a movement
                                                 is detected, the 3 minute timeout period is retriggered, but
                                                 if no movement is detected for this period operation
                                                 reverts to automatic. This means the lights may turn on
                                                 inadvertently during the presentation if the occupants are
                                                 still for 3 minutes, so you should adjust the manual
                                                 timeout carefully.
Walk Test LED      Off       On / Off         When set to On a red LED on the sensor flashes when
                                              movement is detected. Use this feature to check for adequate
                                              sensitivity levels.
Relay State when   Off       On / Off         If Disable Detect is set Yes, setting Relay State when Det
Det Disabled                                  Disabled to On keeps the channel 1 relay output closed.
                                              Setting it to Off keeps the relay open.
Power Up State     Yes       Yes/No           Select No for a 30 second delay after initial power up before
                                              the detector starts detecting and changing outputs.
Inhibit (secs)     4         1 - 99 seconds   The time to wait after the detector turns lights off before it can
                                              retrigger them. If using the device in Absence mode, set this
                                              time to 0.
                                                 ▪7▪
Lux Control
Parameter           Default   Range/           Description
                              Option
Light Level (MI)    999       1 - 998 (999 =   Sets a target light level to be maintained by the lighting
                              maintained       system.
                              illuminance
                              off)
Lux Learn Level     0         0 - 999          Use with the Readback function to get the lux level the unit is
                                               currently reading. Press Send to update the Light Level (MI)
                                               parameter with this value.
Auto Brightness %   20        0 - 100 (0 =     Value used to set Lux On Level and Lux Off Level
                              disabled)        automatically.
Lux On Level        999       0 - 999          Sets a minimum ambient light level below which lights are
                                               turned on by movement.
                                               The Lux Off Level value must always be greater than the Lux
                                               On Level value.
Lux Off Level       999       0 - 999          Sets a maximum ambient light level above which lights
                                               cannot be turned on by movement.
                                               The Lux Off Level value must always be greater than the Lux
                                               On Level value.
Lux On Time         0         0 - 99 minutes   When the ambient light falls below Lux On Level, the time to
                                               wait before switching on the lights. If at any time during the
                                               timed delay the lux change reverses then the process is
                                               cancelled.
Lux Off Time        0         0 - 99 minutes   When the ambient light rises above Lux Off Level, the time to
                                               wait before switching off the lights. If at any time during the
                                               timed delay the lux change reverses then the process is
                                               cancelled.
Lux Switch NZOL     No        Yes /No          Enables and disables luminaire switching when Off Value is
                                               set to a non-zero value.
                                                  ▪8▪
Output Ch. 1
Parameter             Default   Range/           Description
                                Option
Detection Mode        Pres      Pres             Select Pres to turn lights on when movement is detected and
                                (Presence) /     off when movement ceases. Select Abs to turn lights off when
                                Abs (Absence)    movement ceases, but the lights must be manually turned on
                                                 by a switch or handset first.
Timeout               20        0 - 99 minutes   How long the lights stay on for after movement has stopped.
                                                 (channel 1)
Abs Recovery (secs)   10        0 - 99 seconds   Sets a period for a detector in Absence mode to operate in
                                                 Presence mode after lights are turned off. This enables a
                                                 person to use movement to retrigger lights which have
                                                 switched off while they are still in the room. If Abs Recovery
                                                 (secs) is set to a non-zero value you should also set Inhibit
                                                 (secs) to 1 to detect any occupancy immediately.
Relay Status          Off       On/ Off          Use with the Readback function to see whether the detector
                                                 switch relay is currently in an On or Off state.
 Lux On Level         999       0 - 999          Sets a minimum ambient light level below which lights are
                                                 turned on by movement.
                                                 The Lux Off Level value must always be greater than the Lux
                                                 On Level value.
Lux Off Level         999       0 - 999          Sets a maximum ambient light level above which lights
                                                 cannot be turned on by movement.
                                                 The Lux Off Level value must always be greater than the Lux
                                                 On Level value.
Lux On Time           0         0 - 99 minutes   When the ambient light falls below Lux On Level, the time to
                                                 wait before switching on the lights. If at any time during the
                                                 timed delay the lux change reverses then the process is
                                                 cancelled.
Lux Off Time          0         0 - 99 minutes   When the ambient light rises above Lux Off Level, the time to
                                                 wait before switching off the lights. If at any time during the
                                                 timed delay the lux change reverses then the process is
                                                 cancelled.
                                                    ▪9▪
Parameter          Default   Range/   Description
                             Option
Verify Mode
                                       ▪ 10 ▪
Output Ch. 2
Parameter             Default   Range/ Option    Description
Detection Mode        Pres      Pres             Select Pres to turn lights on when movement is detected
                                (Presence) /     and off when movement ceases. Select Abs to turn lights
                                Abs (Absence)    off when movement ceases, but the lights must be
                                                 manually turned on by a switch or handset first.
Timeout               20 mins   0 – 99 minutes   How long the lights stay on for after movement has
                                                 stopped.(channel 2)
Abs Recovery (secs)   10        0 - 99 seconds   Sets a period for a detector in Absence mode to operate in
                                                 Presence mode after lights are turned off. This enables a
                                                 person to use movement to retrigger lights which have
                                                 switched off while they are still in the room. If Abs Recovery
                                                 (secs) is set to a non-zero value you should also set Inhibit
                                                 (secs) to 1 to detect any occupancy immediately.
Lux On Level          999       0 - 999          Sets a minimum ambient light level below which lights are
                                                 turned on by movement.
                                                 The Lux Off Level value must always be greater than the
                                                 Lux On Level value.
Lux Off Level         999       0 - 999          Sets a maximum ambient light level above which lights
                                                 cannot be turned on by movement.
                                                 The Lux Off Level value must always be greater than the
                                                 Lux On Level value.
Lux On Time           0         0 - 99 minutes   When the ambient light falls below Lux On Level, the time
                                                 to wait before switching on the lights. If at any time during
                                                 the timed delay the lux change reverses then the process
                                                 is cancelled.
Lux Off Time          0         0 - 99 minutes   When the ambient light rises above Lux Off Level, the time
                                                 to wait before switching off the lights. If at any time during
                                                 the timed delay the lux change reverses then the process
                                                 is cancelled.
On Scene              1         1-7              Default scene to switch to after the detector times out and
                                                 then powers up.
                                                 ▪ 11 ▪
Parameter          Default      Range/ Option    Description
Gradual Fade On    0            0 – 99 minutes   When fading up, how long to take to reach the required
Time                                             luminaire brightness.
Fade Off Level     0            0 – 99           Sets a minimal light level to dim down to when no
                                                 movement is detected.
Gradual Fade Off   0            0 – 99 minutes   When fading down, how long to take to reach the required
Time                                             luminaire dimness.
Stepped Fade Off   0            0 – 99 minutes   How long to keep lighting at Fade Off Level before
Time                                             dimming to Off Value.
Dim Output         0            0 - 255          Use with the Readback function to see the dimming output
                                                 level currently being sent to luminaires.
Off Value          0            0 - 99           Dimmed output level when lights manually switched off or
                                                 after detector times out.
                                                 ▪ 12 ▪
Parameter          Default   Range/ Option    Description
Burn-in Hours      0         1 - 999 hours    Determines how long the output will be at 100% so that
                             (0 = disabled)   new lamps burn-in. The burn-in time is not affected by
                                              power supply interruptions.
Speed (On)         40        0 - 99           Determines the dimming response speed during the set up
                                              time. Measured in 0.1 sec intervals.
Speed (Setup)      5         0 - 99           Determines how long the dimming response set-up period
                                              lasts on power-up or on setting change. This enables the
                                              desired lux level to be achieved rapidly when the lights
                                              come on, or during setup.
Set Seconds        120       1 - 999          Sets the dimming response speed after the setup time has
                             seconds          finished.
Verify Mode
                                              ▪ 13 ▪
Config
Parameter      Default           Range/ Option      Description
Channel Mode   Switch and dim    Switch only        Submenu to configure dimming controls.
               together
                                 Switch and dim     Switch only
                                 together
                                                       Choose this option if the dimming channel is
                                 Switch and dim        not required (for example with single
                                 separate              channel devices).
                                          ▪ 14 ▪
Parameter        Default            Range/ Option       Description
Lux Cal Value    0                  0 - 999             Enter the current reading of a lux meter to
                                                        calibrate the photocell in the detector.
Lux Cal Factor   0                  0 - 999             Reads back the effective lux value calculated
                                                        from the photocell reading and Lux Cal Value.
                                              ▪ 15 ▪
User
Parameter              Default   Range/    Description
                                 Option
Set Scene Level           0      0 - 255   Changes a particular scene's illumination level. Select the scene
                                           first using Select Scene and then send Set Scene Level.
                                           255 = 100%
                                           191 = 75%
                                           128 = 50%
                                           64 = 25%
                                           26 = 10%
                                           0 = Off
Manual Override On        -         -      Turns lights on and reverts to automatic operation after the
                                           period set by Manual Timeout in the Detector Params menu.
Manual Override Off       -         -      Turns lights off and reverts to automatic operation after the
                                           period set by Manual Timeout in the Detector Params menu.
Manual Override           -         -      Cancels the manual on and off overrides, returning the detector
Cancel                                     to normal operation.
Override Perm On         -         -       Keeps the channel 1 relay closed. Channel 2 continues to send
                                           out dimming signals until a Cancel command has been received
                                           by sensor.
Override Perm Off        -         -       Keeps the channel 1 relay open. No dimming signal is sent by
                                           channel 2 unless Off Value has been set or a Cancel command
                                           is received by sensor.
Override Perm Cancel     -         -       Return to normal operation after one of the Permanent Override
                                           commands has been sent.
                                                ▪ 16 ▪
                                                                                                                                                         CP Electronics
                                                                                                                                                         Brent Crescent
                                                                                                                                                         London NW10 7XR UK
                                                                                                                                                         Tel: +44 (0)333 900 0671
                                                                                                                                                         Fax: +44 (0)333 900 0674
Due to our policy of continual product improvement, CP Electronics reserves the right to alter the specification of this product without prior notice.   http://www.cpelectronics.co.uk/
Ref WD841 issue 1                                                                                                                                        enquiry@cpelectronics.co.uk