Features: 83 Series - Modular Timers 12 - 16 A
Features: 83 Series - Modular Timers 12 - 16 A
SERIES
                                    Contact specification
                                    Contact configuration                                          1 CO (SPDT)                       1 CO (SPDT)                       1 CO (SPDT)
                                    Rated current/Maximum peak current             A                   16/30                              16/30                           16/30
                                    Rated voltage/Maximum switching voltage V AC                     250/400                             250/400                         250/400
                                    Rated load AC1                                VA                   4,000                               4,000                           4,000
                                    Rated load AC15 (230 V AC)                    VA                    750                                 750                             750
                                    Single phase motor rating (230 V AC)         kW                     0.5                                 0.5                              0.5
                                    Breaking capacity DC1: 30/110/220 V            A              16/0.3/0.12                        16/0.3/0.12                      16/0.3/0.12
                                    Minimum switching load                 mW (V/mA)                300 (5/5)                            300 (5/5)                      300 (5/5)
                                    Standard contact material                                          AgNi                                AgNi                            AgNi
                                    Supply specification
                                    Nominal voltage (UN)          V AC (50/60 Hz)                    24...240                            24...240                        24...240
                                                                                V DC                 24...240                            24...240                        24...240
                                    Rated power AC/DC                VA (50 Hz)/W                  < 1.5 / < 2                        < 1.5 / < 2                      < 1.5 / < 2
                                    Operating range                             V AC                16.8...265                           16.8...265                     16.8...265
                                                                                V DC                16.8...265                           16.8...265                     16.8...265
                                    Technical data
                                    Specified time range                                (0.05…1)s, (0.5…10)s, (0.05…1)min, (0.5...10)min, (0.05...1)h, (0.5...10)h, (0.05...1)d, (0.5...10)d
                                    Repeatability                                  %                    ±1                                  ±1                              ±1
                                    Recovery time                                 ms                    200                                 200                             200
                                    Minimum control impulse                       ms                     —                                  —                                50
                                                                                                                                                                                                X-2013, www.findernet.com
                                                                                                                                                                           Wiring diagram
                                                                                                                                                                        (without control signal)
                                                                8 3 . 0                1 . 0 . 2 4 0 . 0                              0        0       0
                                    Series                                                                            Versions
                                    Type                                                                              0000 = Standard
                                    0 = Multi-function (AI, DI, GI, SW, BE, CE, DE, WD)                               Supply voltage
                                    1 = On-delay (AI)                                                                 240 = (24 ... 240)V AC/DC
                                    2 = Interval (DI)                                                                 Supply version
                                    4 = Off-delay with control signal (BE)                                            0 = AC (50/60 Hz)/DC
                                    6 = Power off-delay (True off-delay) (BI)
                                    8 = Star-delta (SD)                                                               No. of poles
                                    9 = Asymmetrical flasher (LI, LE, PI, PE)                                         1 = 1 CO (SPDT)
                                                                                                                      2 = 2 CO (DPDT) for 83.02 and 83.62
                                                                                                                      2 = 2 NO (DPST-NO) for 83.82
                                Technical data
                                Insulation
                                Dielectric strength                 between input and output circuit          V AC 4,000
                                                                    between open contacts                     V AC 1,000
                                Insulation (1.2/50 μs) between input and output                                    kV 6
                                EMC specifications
                                Type of test                                                                           Reference standard 83.01/02/11/21/41/82/91 83.62
                                Electrostatic discharge                             contact discharge                  EN 61000-4-2           4 kV                            4 kV
                                                                                    air discharge                      EN 61000-4-2           8 kV                            8 kV
                                Radio-frequency electromagnetic field               (80 ÷ 1,000 MHz)                   EN 61000-4-3         10 V/m                          10 V/m
                                                                                    (1,000 ÷ 2,700 MHz)                EN 61000-4-3           3 V/m                           3 V/m
                                Fast transients (burst) (5-50 ns, 5 and 100 kHz) on Supply terminals                   EN 61000-4-4           7 kV                            6 kV
                                                                                    on control signal terminal (B1)    EN 61000-4-4           7 kV                            6 kV
                                Surges (1.2/50 μs) on Supply terminals              common mode                        EN 61000-4-5           6 kV                            6 kV
 Timers and Monitoring relays
                                4
                                                                                             83
                                                                                             SERIES
                            83.11              83.21
                            Screw terminal     Screw terminal
                            83.82              83.91
                            Screw terminal     Screw terminal
X-2013, www.findernet.com
                                                                                         5
83
SERIES
                                Accessories
                                                      Sheet of marker tags, for types 83.01/11/21/41/62/82, plastic, 72 tags, 6x12 mm 060.72
060.72
087.02.2
Z1 Z2
                                                                                                                                    15 - 18                     15 - 16
                                                                                          OFF               Open                    25 - 28                     25 - 26
                                                                                                                                    15 - 18                     15 - 16
                                                                                          ON                Open                    25 - 28                     25 - 26
                                                                                                            Open                    15 - 18                     15 - 16
                                                                                          ON         (Timing in Progress)           25 - 28                     25 - 26
                                                                                                                                    15 - 16                     15 - 18
                                                                                          ON                Closed                  25 - 26                     25 - 28
* The LED on type 83.62 is illuminated when supply voltage is supplied to timer.
• Possible to control an external load, such as another relay coil or timer, connected to the control signal terminal B1.
                                      **             ** A voltage other than the supply voltage can be applied to the control signal (B1), example:
                                                        A1 - A2 = 230 V AC
                                                        B1 - A2 = 12 V DC
                                6
                                                                                                                                                                                                           83
                                                                                                                                                                                                           SERIES
                            Functions
                            Wiring diagram                               U = Supply voltage                             S = Signal switch                            = Output contact
                            Multi-function                  Type                                                               (AI) On-delay.
                            without control signal         83.01                                                               Apply power to timer. Output contacts transfer after preset
                                                           83.02                                                               time has elapsed. Reset occurs when power is removed.
                                                                                                                               (DI) Interval.
                                                                                                                               Apply power to timer. Output contacts transfer immediately.
                                                                                                                               After the preset time has elapsed, contacts reset.
                                                  83.01
                                                                                                                               (GI) Pulse delayed.
                                                                                                                               Apply power to timer. Output contacts transfer after preset
                                                                                                                               time has elapsed. Reset occurs after a fixed time of 0.5s.
                            83.02 type
                                  Contact mode selector                   Functions without control signal (example: AI)                      Functions with control signal (example: BE)
2 timed contacts
                                                                             Both output contacts (15-18 and 25-28)                             Both output contacts (15-18 and 25-28)
                                                                                    follow the timing function                                         follow the timing function
                                                                        Both output contacts [15-18 and 25(21)-28(24)]                     Both output contacts [15-18 and 25(21)-28(24)]
                                                                                     stay permanently open                                              stay permanently open
                                        1 timed +
                                 1 instantaneous contact
X-2013, www.findernet.com
                                                                     The output contact 15-18 follows the timing function               The output contact 15-18 follows the timing function
                                                                    The output contact 21-24 follows the power supply (U)              The output contact 21-24 follows the control signal (S)
                                                                                                                                                                                                       7
83
SERIES
                                with control signal (S)           83.41                              (BE) Off-delay with control signal.
                                                                                                     Power is permenently applied to the timer.
                                                                                                     The output contacts transfer immediately on closure of the
                                                                                                     control signal (S). Opening the control signal initiates the
                                                                                                     preset delay, after which time the output contacts reset.
83.41
                                Asymmetrical recycler             83.91                              (LI) Asymmetrical flasher (starting pulse on)- (Z1-Z2 open).
                                without control signal                                               Apply power to timer. Output contacts transfer immediately
                                                                                                     and cycle between ON and OFF for as long as power is
                                                                                                     applied. The ON and OFF times are independently
 Timers and Monitoring relays
adjustable.