SM Ser
SM Ser
M58100000y / SM_SER
User Manual
This manual provides information for the assembly, wiring, configuration and
maintenance of the SM_SER module.
SE-M581-USR
www.schneider-electric.com
13/12/2019                                                                                        User Manual – SM_SER
Change Control
             Rev         Date                                          Description
General Information
             The Saitel platform and all its components have been developed in accordance to the requirements
             for a quality management system, complying with the ISO 9001:2015 Norm.
Reference Documents
             User Manual                                     Document Code
Software Versions
             The information in this manual is valid for the software versions listed below. This information is
             also valid for later versions, although some parameters may change slightly:
                                                       Pag 2
User Manual – SM_SER                                                                                                  13/12/2019
Content
                                                          Pag 3
13/12/2019                       User Manual – SM_SER
                    Pag 4
User Manual – SM_SER                                                                                                         13/12/2019
Content
                                                              Pag 5
13/12/2019                                                                                     User Manual – SM_SER
1.1 Introduction
                                                          DANGER
               DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
               injury.
                                                           WARNING
               WARNING indicates a hazardous situation which, if not avoided, could result in death or
               serious injury.
                                                              NOTICE
               NOTICE is used to address practices not related to physical injury. The safety alert symbol shall
               not be used with this signal word.
To Keep in Mind
             Electrical equipment should be installed, operated, serviced, and maintained only by qualified
             personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
             the use of this material.
             A qualified person is who fulfill with requirements in paragraph 1.2
1.1.2        Presentation
             This manual provides information for a safe handling, commissioning and testing. This Safety
             chapter also includes descriptions of the labels on the equipment.
             Documentation for equipment ordered from Schneider Electric is dispatched separately from
             manufactured goods and may not be received at the same time. Therefore, this guide is provided
             to ensure that printed information which may be present on the equipment is fully understood by
             the recipient.
                                                      Pag 6
User Manual – SM_SER                                                                                     13/12/2019
             The technical data in this safety guide is typical only, see the technical data section of the user
             manual for specific details of a particular equipment.
                           Before carrying out any work on the equipment the user should be familiar with the
                           contents of this Safety chapter and the ratings on the equipment’s rating label.
                           THE SAFETY SECTION MUST BE READ BEFORE STARTING ANY WORK ON
                           THE EQUIPMENT.
             The information in this section is intended to get that the equipment is properly installed and
             handled in order to maintain it in safety conditions. It is assumed that everyone who will be
             associated with the equipment will be familiar with the contents of that safety section.
             When electrical equipment is in operation, dangerous voltages will be present in certain parts of the
             equipment. Failure to observe warning notices, an incorrect use, or improper use may endanger
             personnel and equipment and also cause personal injury or physical damage.
                                                           WARNING
                 Before working with the terminal of connection, the device must be turned off and disconnected
                 of the feeding.
             Proper and safe operation of the equipment depends on appropriate shipping and handling, proper
             storage, installation and commissioning, and on careful operation, maintenance and servicing. For
             this reason, only qualified operator may work on or operate the equipment.
             Qualified operator are individuals who:
• Have read and understood the information on the device and its user manual.
             •     Are familiar with the installation, commissioning, and operation of the equipment and of the
                   system to which it is being connected.
             •     Are able to safely perform switching operations in accordance with accepted safety
                   engineering practices and are authorized to energize and de-energize equipment and to
                   isolate, ground, and label it.
             •     Are trained in the care and use of safety apparatus in accordance with safety engineering
                   practices.
             Before the equipment is installed or commissioned, the user must understand the following
             symbols, which may be used on the equipment or referred to in the user documentation.
                                                       Pag 7
13/12/2019                                                                                     User Manual – SM_SER
Table 1 – Symbols
             There are several acquisition blocks in Saitel DP that use dangerous tensions (> 50 V). The user is
             responsible to check that the characteristics of each device are adapted and convenient for his
             installation. The user should read the instructions of installation before proceeding to the use or
             maintenance of the devices.
             Not following these instructions can be dangerous for the people and the devices.
                                                           DANGER
              Devices that handle dangerous tensions are marked with a sticker on the front label (size: 12,5
              mm). This label must be visible all the time while the module is installed on the backplane.
                                                     Pag 8
User Manual – SM_SER                                                                                         13/12/2019
             •     SM_DO16R and SM_DO32T: These modules do not handle high voltages, they will not be
                   marked at the factory. These modules must be marked to inform about the risk when some
                   equipment that manage voltage higher than 50 V are connected to digital outputs.
             It is recommended to install the RTU inside a cabinet with a key. This cabinet only should be
             opened by a qualified person.
                                                                   WARNING
                 If this type of cabinet isn't available, a barrier must be installed in order to avoid an accidental
                 contact with these dangerous elements. This barrier only should can be removed using a
                 special tool.
                 If the barrier has to be removed in order to access to equipment, personnel responsible for the
                 task must be sure that the barrier is installed again when the task is finished.
                 While the RTU is accessible for a user, all people must follow all instructions to prevent
                 electrical risk or discharges.
                 Not following these instructions can give like result that the device do not work properly
                 or even can damage to the people or devices.
                            An electrical risk symbol with enough size must be included on the cabinet’s door or
                            on the barrier.
                                                                NOTICE
                 Terminals will not be accessible to the user directly once it has made the installation of the
                 device. The cabinet will have to remain closed with key or the screen of installed protection.
             The cabinet or installation must have a general switch placed just in the cable entry of the
             installation (see paragraph 1.7.1 )
             For the cleaning of the device it is only necessary using a dry cloth by the surface when it detects
             excessive presence of dust or any element deposited on the surface.
                                                                   WARNING
                 Don’t use liquid products of cleanliness due to the presence of active parts.
             Because of the variety of uses of the product, the managers of the application and use of this
             device of control will have to take the measures to ensure the fulfillment of all the requests of
                                                        Pag 9
13/12/2019                                                                                   User Manual – SM_SER
             security and provision of each application. The requests do reference to the applicable laws,
             regulations, codes and standard.
1.5 Earthing
WARNING
                 Before energizer the device, it has to be placed to earth properly such as it indicates in sections
                 1.5.1 and 1.5.2 .
                 When installing the device, ground is the first thing that should be connected and the last one
                 that should be disconnected.
             •     Improve the behavior in Electromagnetic Compatibility (EMC) and derive perturbations to earth
                   (functional Earth).
                                                                 WARNING
                 All devices with high voltage must be disconnected before dismount a module.
             In the cabinet where the module is mounted, a dedicated connection with green/yellow wire should
             be used to have electric continuity to the installation protective earth. Use a wire with adequate
             section according to IEC 61010.
             Figure 2 – Yellow and Green cable for earthing.
             The design and installation of the cabinet is responsible for compliance with all the existing
             international and national electrical codes concerning protective grounding of any device.
WARNING
                                                      Pag 10
User Manual – SM_SER                                                                                      13/12/2019
                                                                WARNING
               Never connect modules on the backplanes if the power supply hasn’t been disconnected of all
               circuits with high voltages.
             The only modules with a ground connection are the power supplies (SM_PS and SM_PS40). Both
             must be connected to the ground of the cabinet.
             Saitel is susceptible to receive electrostatic discharges during the handling. It is necessary to take
             the usual measures to minimize this risk, since serious damage to the equipment can be caused,
             which may not be detected immediately but which may affect the reliability of the product.
                                                           WARNING
               The enclosure ONLY should be removed when is strictly necessary, because this action has a
               risk for the equipment:
• Before removing the enclosure, the operator must be equipotential with the equipment.
• Avoid touching the electronic. The board must be always manipulated for the edges.
• If the equipment has to be passed between two persons, both must be equipotential.
• Put the module always on an antistatic surface or on a surface equipotential with you.
                   •   During the storage and transport, the module will remain in the packaging.
               Not following these instructions can give like result that the device do not work properly
               or even can damage to the people or equipment.
WARNING
                                                     Pag 11
13/12/2019                                                                                    User Manual – SM_SER
                 The connection / disconnection switch must be installed in a fixed element (for example the wall
                 of the cabinet) and it mustn’t break any earthing wire.
                                                                 WARNING
                 This equipment has been designed ONLY for indoor use.
             If necessary, for use in an outdoor environment, it must be mounted in a specific cabinet providing
             an IP54 degree of protection (typical and minimum for ATEX conditions), that is, protected against
             dust and water splashes.
             The electronic cards of the modules will be able to be tropicalized or no according to the option of
             setting chosen. The tropicalized used is the AVR80, of the company ABchimie. It can consult all the
             technical information of this type of finishing in http://www.abchimie.com/.
             Other data to take into account about the environmental are:
• Operation temperature range: Between -40 ºC and 70 ºC. (IEC 60068-2-1 and IEC 60068-2-2).
             Each Saitel product includes a technical label with the following information:
             Figure 3 – Technical label.
                                                      Pag 12
User Manual – SM_SER                                                                                     13/12/2019
                                                              NOTICE
               On the “Technical data” zone, you can see relevant information about the input and output
               voltage in the module. Any voltage greater than 50 V must be consider as a high voltage.
             All Saitel modules are packaged separately in their own carton box and shipped inside outer
             packaging. Use special care when unpacking the device. Don’t use force.
             The design revision and manufacturing options can be determined using the P/N included in the
             packaging label on packaging.
             After unpacking the device, inspect it visually to be sure it is in proper mechanical condition.
             If the product needs to be shipped, the original packaging must be used, including foams and the
             carton box. If the original packaging is no longer available, make sure that the packaging used is
             according to ISO 2248 specifications for a drop height 1 m.
                          SM_SER is marked with this symbol, it means that, at the end of its life cycle, you
                          mustn't dispose the product together with habitual residues. To avoid possible
                          damage to the environment or to the human health that represents the uncontrolled
                          elimination of residues, please follow the instructions in EOLI document for SM_SER.
                                                     Pag 13
13/12/2019                                User Manual – SM_SER
                           Pag 14
User Manual – SM_SER                                                                                                       13/12/2019
Content
             2       GENERAL DESCRIPTION OF SM_SER ...............................................................14
                                                             Pag 15
13/12/2019                                                                                 User Manual – SM_SER
             The Saitel DP platform is a complete set of devices provided by Schneider Electric for real-time
             control applications and power line automation. It is a high-technology platform which gives a
             solution to the business areas of Schneider Electric.
             The following figures show a Saitel DP in chassis (left) and in backplane (right).
             Figure 4 – Saitel DP in Chassis and Backplane
             Saitel DP’s design has been optimized to meet the most demanding requirements of multiple
             sectors:
• Safety and reliability requirements for power, gas, water, residual water supply, etc.
• Local monitoring and control with data sharing capabilities of plant-distributed devices.
             •   One of the most remarkable features of Saitel DP is its modular design. All I/O, CPU, power
                 supply and communication modules have an identical format, sharing the same enclosure.
             Figure 5 – Saitel DP architecture example
                                                    Pag 16
 User Manual – SM_SER                                                                                    13/12/2019
                   The SM_SER is the serial communication module available in Saitel DP. It expands the control
                   module communication capability. This module is linked with the CPU module (SM_CPU866e)
                   through a bidirectional high-speed channel.
                   The SM_SER module communicates with the CPU module through the internal bus, at a
                   transmission rate of up to 1.5 Mbps. The multiplexing operation allows transfers the message
                   streams bidirectional from input channels and its signals.
                   The communication protocol between the SM_SER module and CPU module follows a master-
                   slave (poll-response) structure, in which the master is the CPU module and the slave are the
                   different SM_SER modules which are installed.
                   Figure 6 – Saitel DP architecture example
• A controller block
                   •   An indication block
Controller Block
                   The controller block supports the following functions:
                   •   Parameterization and control of the communication blocks.:
                           o   Asynchronous communication.
                           o   Configurable transmission/reception.
                           o   Configurable transmission rate up to 38,400 bps.
                           o   Configurable stream (number of bits, start, stop and parity bit).
                           o   RTS/CTS flow control.
                           o   Transmission/reception of complete streams.
                                                          Pag 17
 13/12/2019                                                                                  User Manual – SM_SER
• 6 signals for each channel: TX, RX, RTS, CTS, DTR and DSR.
               •   RS-232 / RS-485 / RS-422 signal levels. All channels are configurable as RS-232, RS-485 or
                   RS-422.
2.3 Interfaces
                                                     Pag 18
User Manual – SM_SER                                  13/12/2019
                                 Pag 19
13/12/2019                                                                                                  User Manual – SM_SER
Content
             3       PHYSICAL MOUNTING & INSTALLING ...............................................................19
                                                             Pag 20
User Manual – SM_SER                                                                                     13/12/2019
3.1 Installation
3.1.1        Handing
                                                                   WARNING
                 The electrostatic discharges may damage semi-conducive devices within the module, if the
                 connector pins are in contact with the backplane.
             •     You should handle the module from the front side, as far as possible from the backplane
                   connectors.
• You should keep the module in its antistatic bag or packaging box, when unused.
             All SM_SER modules in the RTU must be installed in the first backplane. Communication data can
             be expanded to others backplanes. Then, the maximum number of SM_SER modules connected to
             a CPU is 8.
             When using a power supply such as the SM_PS or SM_PS40 module, it must be located in the
             position 1 (slot1 left-hand side). In redundant-power supply configurations, there must be two
             reserved positions for the two power supply modules. These positions must be 1 and 2.
Remaining modules can be located in any position (slot) within the chassis.
             Modules must be grouped to minimize the adverse effects caused by noise and heat, therefore,
             modules, and more specifically the CPU modules, must be placed as far as possible from the
             modules which operate at alternating currents or high currents.
             If the system has redundant CPUs, both control modules must be put together in the backplane
                                                      Pag 21
13/12/2019                                                                                 User Manual – SM_SER
             The SM_PS and SM_PS40 modules (power-supplies) are scalable to supply power to the modules
             connected to the backplane, as required. When using auxiliary power supplies, it is necessary to
             scale them depending on the installed Saitel DP modules.
             The consumption of all modules will be added plus a safety margin (between 20% and 50% of the
             full power). The power supply efficiency typically, 70 - 90% shall also be considered, to protect the
             chassis and power supply from overloading.
             The maximum power requirement for each SM_SER module is: 3.9 W.
                     •   Mount the module at the desired position, and if you are using a backplane mounting,
                         verify that the rear rails are properly mounted using the pre-drilled holes on the
                         backplane.
                     •   Firmly press the module to assure the connector fits in the connector properly. Check
                         whether the module is correctly mounted to the backplane base.
                                                    Pag 22
User Manual – SM_SER                                                                               13/12/2019
             The Profibus communication speed must be the same for all Saitel DP modules, which is
             determined by the speed of the master, configured by software, in the control module. The speed is
             set using microswitches 9, 10 and 11 as shown in the following table:
             Table 3 – Configuration switches
                                                      NOTICE
              For optimal system performance is recommended to set the Profibus rate to 1.5
              Mbaud. Microswitches 8 and 12 are reserved and must be set to OFF.
                                                      Pag 23
13/12/2019                                                                                  User Manual – SM_SER
                                                                 WARNING
                 Particular care must be taken when connecting the shielding to make sure it is effective.
The shield connection depends on the equipotentiality between the connected devices:
             •       Guaranteed equipotentiality: Both devices are connected to a ground system, so that the
                     same potential level is guaranteed. The shield must be connected at both ends.
             •       Limited equipotentiality: Both devices are connected to ground but not to the same ground
                     system. To limit the difference of potential that can be produced among them a cable with the
                     appropriate cross-section will be installed between the grounding of both. The shield must be
                     connected at one end.
                                                                  DANGER
                 Connecting NOT equipotential devices could be hazardous for persons and equipment.
                 1        Rx (-)          B          I/O
                 3        Tx (+)          Y          I/O
                 4, 5     GND
                 6        Rx (+)          A          I/O
                 8        Tx (-)          Z          I/O
                                                        Pag 24
User Manual – SM_SER                                                                               13/12/2019
                 1        Rx (-)                       I
                 3        Tx (+)                       O
                 4, 5     GND
                 6        Rx (+)                       I
                 8        Tx (-)                       O
                 1        /CTS                         I
                 2        /DTR                         O
                 3        Data transmission            O
                 4
                          GND
                 5
                 6        Data reception               I
                 7        /DCD                         I
                 8        /RTS                         O
                                                           Pag 25
13/12/2019                                                                                User Manual – SM_SER
             For each communications port that works as end of the bus, a terminal with termination resistors
             (120 to 150 Ω) for both reception and transmission channels must be installed.
                                                     NOTICE
              It is important to note that for each bus, two and only two devices must function as
              termination of the bus.
             There are two recommended models for these auxiliary terminal (both by Phoenix Contact):
             Figure 9 – FL-PP-RJ45-SC and VIP-3/PT/RJ45
             For example, the following figure shows how you can use a 5-pin terminal for RS-422 and for RS-
             485 in full-duplex communications:
             Figure 10 – Termination resistor in full-duplex communications
                                                     NOTICE
              These figures should be understood as an example. You can use some other
              mechanism that provides you with the same functionality.
             To connect the SM_SER port with the auxiliary terminal, if the bus is RS-422 or full-duplex RS-485,
             the cable to be used is shown in the following figure:
             Figure 12 – Cable for connection SM_SER-Auxiliary terminal in full-duplex communications
                                                    Pag 26
User Manual – SM_SER                                                                                   13/12/2019
             •   Thirty-two indications for the channel signals. Four indications for each channel to display the
                 “Transmission” status (TX1-TX8), “Reception” (RX1-RX8), “Request to Send “(RTS1-RTS8)
                 and “Clear to Send” (CTS1-CTS8).
                                                    Pag 27
13/12/2019                                                                                  User Manual – SM_SER
Receiving data.
Transmitting data.
                                                       Pag 28
User Manual – SM_SER                                   13/12/2019
                                    Pag 29
13/12/2019                                                                                              User Manual – SM_SER
Content
             4      MAINTENANCE & CONFIGURATION ...................................................................29
                                                           Pag 30
User Manual – SM_SER                                                                                    13/12/2019
NOTICE
              To perform the operations described in this chapter, the user must be familiar with the
              configuration tool. Otherwise, please consult the user manual of Easergy Builder.
             In the Workspace of Easergy Builder, create a new RTU using        button or pressing right button
             of the mouse in an empty area of the RTUs tree:
             Figure 15 – Adding new RTU
             Pressing button next to the picture, you can add, remove or change the I/O modules included on
             the default configuration.
             Figure 16 – Add, remove or change I/O modules
             Each I/O module is allocated to a unique and identifying number in the bus (Profibus address). This
             number is assigned using the switches available in the rear panel of the module.
             The CPU needs to know the address and the types of I/O modules installed in the bus in order to
             initialize and switch to data acquisition mode properly.
             All examples in this chapter are made using an SM_CPU866e CPU but all operation is similar for
             SM_CPU866.
             Figure 17 – Acquisition modules in the default configuration
                                                   Pag 31
13/12/2019                                                                                   User Manual – SM_SER
             •   Add or remove module in the backplane. Use button           to add new modules and       to
                 remove a module.
             Figure 18 – Adding one or several I/O modules.
             •   The address for each module is displayed under its picture and it can be changed using the
                 button    . The address for each module must be the same that is indicated with its rear
                 switches.
             •   Use button      to configure the time parameters of the polling and digital filtering:
             Figure 19 – Configuration parameters.
To create a new configuration, select your RTU in the tree and pulse right button of the mouse or
             If the field "Create acquisition points defined in the RTU" is marked, all points of the local
             acquisition of the acquisition blocks included in the default acquisition configuration associated with
             the RTU will be included in coreDb.
             For example, if a SM_CPU866e has a backplane with a SM_DO16R module, if "Create
             acquisition points defined in the RTU", following points are generated:
                                                     Pag 32
User Manual – SM_SER                                                                                   13/12/2019
             •   System supervision points by default in the Status and Analog table: WARN_PS1, FAIL_RTU,
                 DOING_WELL….
             At the end of the operation, the new configuration will appear in the RTUs tree. Double-click on it
             and the Configuration mode is activated.
             Figure 21 – Configuration mode.
             Double click on the laq Device and the backplane configuration window allows to modify the
             acquisition configuration.
             Selecting the module SM_DO16R, you can configure each field signal
             Figure 22 – Configuration mode.
Other buttons in this window are explained in the user manual of Easergy Builder.
                                                    Pag 33
13/12/2019                                                                                User Manual – SM_SER
              For example, this figure shows an RTU with a 866e and an SM_SER module. The “Channel
              Architecture” zone displays all channels and links (channel associations) which are defined.
                       •   Channel1 and Channel2: COM1 and COM2 (HU_A)
              Where:
              •   Name: Identifying name
• Description: Description
                                                       Pag 34
User Manual – SM_SER                                                                                  13/12/2019
             •   Type: Channel type depending on the implemented communication protocol. There are three
                 types:
                       o   TCP
                       o   UDP
                       o   ASYNC (RS-232, RS-485 or RS-422 serial communication)
             •   Channel: The physical port that will be used for this channel. The list of physical channels
                 available depends on the CPU type:
                       o   SM_CPU866 and SM_CPU866e: COM1, COM2, COM3, COM4 and SM_SERx-
                           COMy. Only ports of the SM_SER configured will be available.
                       o   HU_A and HU_AF: COM1, COM2, RS-485 and AB_SERx-COMy. Only ports of the
                           AB_SER configured will be available.
                       o   HU_B: COM1 and COM2
                       o   HU_BI: COM1/RS-485. Only one of these ports can be used at the same time
                       o   HU 250: RS-485, K7 RS SLOT(1) and K7 RS SLOT(2). K7 RS SLOT 1 and 2 will be
                           available or not depending on the configuration of the slots 1 and 2
             •   Baudrate: To specify the communication speed. The speed ranges between 300 and 256000
                 bps
             •   Protocol: It defines the asynchronous protocol which will be used. The available protocols are
                 RS-232, RS-485 and RS-422. RS-485 allows 2 or 4-wire communications.
             •   RS-485 / RS-422:
                       o   Termination resistor
                       o   Polarization
             •   Modem Control: These parameters allow configuring the signals for modem control in the
                 communication ports. Not all values are available for each CPU
                       o   DTR Control: Flow control
                                    ENABLE: DTR at high logical level (1)
                                    DISABLE: DTR at low logical level (0)
                                    TOGGLE (only available for K7 modem): DTR control depends on the
                                     parameter “DTR - RTS delay”.
                       o   RTS Control: To configure the RTS output
                                    DISABLE. Disables the use of the RTS signal
                                    ENABLE: It enables the RTS signal, and keeps it active.
                                    AUTO: The RTS signal timing will be defined automatically.
                                    TOGGLE: It allows defining timing for RTS signal.
                       o   CD Control:
                                    ENABLE: CD at high logical level (1).
                                    DISABLE: CD at low logical level (0).
                       o   DSR Control:
                                    ENABLE: DSR at high logical level (1).
                                                    Pag 35
13/12/2019                                                                                  User Manual – SM_SER
             For 2-wire RS-485 communications, it is very often necessary to set the RTS control to TOGGLE,
             and define all times to 0 ms. Thus, reception while transmitting is disabled (to avoid echo).
             When use webApp, the following message is shown previously to access the tool:
             Figure 25 – Disclaimer information
                                                    Pag 36
User Manual – SM_SER                                                                                 13/12/2019
             Write the Username and Password in order to access the webApp’s main window:
             This screen contains 5 menus:
• Home
• Diagnostic
• Maintenance
                       •   Settings
Home
             Select Home in the main toolbar and the following information is shown:
             Figure 27 – Home tab
             •   Device Information. It is possible to add the names of the operators who have used or
                 configured the equipment or a specific custom note that can be viewed each time a connection
                 is established to this RTU. This information can be changed using button “Edit”, next to “Device
                 information”.
                                                    Pag 37
 13/12/2019                                                                                   User Manual – SM_SER
               •   Location. The GPS coordinates for the RTU location (place, latitude, longitude, and altitude)
                   should be entered here by the installer. Location is not set automatically. The image must be
                   included manually by clicking button      on the map.
               •   Image associated to the RTU. It could be useful to include a location map corresponding to the
                   GPS coordinates. Use button         on the graphic zone to do it.
               •   Notes. This zone allows the user to include notes that are shown to other users. Use button
                             too add new notes.
               •   Factory information: This zone shows the manufacturer, model and the version of the
                   software loaded on the HU module. Using button        next to the text “Factory Information”, it is
                   also possible to include an image of the particular RTU or CPU for identification purposes.
Monitoring and Control
               This menu is used to monitor and control the information regarding to system status and coreDb
               points.
               Select “Monitoring & control  System information” and the following information the system is
               displayed or not depending on whether the corresponding monitoring point was included or not in
               coreDb. In the following image, for each data, the supervision point that must be included in coreDb
               is indicated in a blue square.
               Figure 28 – Monitoring and control view - System information
               On the other hand, the “Monitoring and control  Data” allows to monitor the information of each
               coreDb table:
• Command page: For sending change of state commands based on the digital data.
                                                      Pag 38
 User Manual – SM_SER                                                                                 13/12/2019
Diagnostic
              •   In the menu Diagnostic you can find a Trace tab. The channels configured with Easergy
                  Builder can be monitored in Trace tab. The user can choose the channel to monitoring and it
                  click in the field “Show selected traces”.
              Figure 29 – Diagnostic View
              Once the username and the password are introduced in the login window, the main workspace is
              displayed:
              Figure 31 – Initial screen of Saitel webTool
                                                     Pag 39
13/12/2019                                                                                  User Manual – SM_SER
• User who is logged in the session (user target in the previous picture).
• Active language for the session. Use the pull-down field “Language” to change it.
             •   The main menu is located on the left side of the window. It allows you to access all information
                 of the RTU:
• Monitoring: Gives access to the coreDb tables and the values for each register and field.
• Bins: Gives access to the devices that have been configured in the RTU.
• Network configuration: Gives information about the physical devices and rooters.
             Once the backplane is configured, the CPU module (866 or 866e) already knows the type of
             acquisition blocks that are been installed and their corresponding addresses.
             To update the software of the SM_SER module, you need:
             •   SM_SER module must be correctly addressed and working fine in the backplane (LED Run
                 must be blinking).
             •   SM_SER.bin file with the new version. This file must be available in the flash folder of the CPU.
                 If not, you can contact Schneider Electric in order to ask for it. Use an SFTP client and transfer
                 this binary file into the CPU flash folder.
             The console tool can be executed using any commercial tool for serial or SSH connection. In this
             manual, PuTTy software is used.
             Open a serial connection as follow:
             Figure 32 – PuTTY configuration
             SSH connection via Ethernet can be used too. More information about the console use in the CPU
             user manual. In the following picture, CPU866e is used:
                                                    Pag 40
User Manual – SM_SER                                                                                   13/12/2019
                                                             NOTICE
               If the baseline includes the cybersecurity brick, you need to login in the console with Installer.
               No other user has permissions to execute this operation. Please, consult the CPU user manual
               for more information.
             If the file SM_SER.bin is available in the flash folder, use one of the following commands to
             upgrade the software of SM_SER modules:
             Table 8 – Upgrading SM_SER software.
                                                             NOTICE
               Console commands are case-sensitive, and quotation marks must be included.
             After running the command, the console will show some messages indicating the process status.
             Finally, if no problem is found, we will have updated the firmware of the modules.
                                                    Pag 41
13/12/2019                                                                              User Manual – SM_SER
             •   SMx: Change the monitor channel to channel x. This operation must be confirmed before
                 channel x is the new channel monitoring.
• RB: Reboot
                                                    Pag 42
User Manual – SM_SER                                     13/12/2019
                                    Pag 43
13/12/2019                                                                                                   User Manual – SM_SER
       Hardware Specifications
       Number of channels.                     8
       Isolation between channels              2 kVRMS
       Signal level                            RS-232 / RS-485 / RS-422
       Signals                                 Rx - Tx - RTS - CTS - DTR - DSR
       Consumption                             3.4 W (Using 8 channels)
       Interfaces
       Field connection                        8 ports
                                               RJ-45 connector
       RS-485 connection                       Resistance < 100 Ω/km
                                               Wire: 0.22 mm2 (24 AWG)
                                               Impedance: 120 Ω
                                               Max wiring length: 1200 m
                                               Half duplex / Full duplex
       RS-422 connection                       Resistance < 100 Ω/km
                                               Wire: 0.22 mm2 (24 AWG)
                                               Impedance: 100 Ω
                                               Max wiring length: 1200 m
       Software
       Transmission features                   Configurable per channel
       CE Mark
       Standards, Directives and    LVD – Low Voltage Directive                     Directive 2006/95/CE
       harmonized norms.                                                            Directive 2004/108/CE
                                    EMC – Electromagnetic Compatibility
                                    RoHS 2 – Restriction of Hazardous               Directive 2011/65/EU, according to royal legislative
                                    Substances                                      decree (RD) 219/2013
                                                           Pag 44
User Manual – SM_SER                                                                                    13/12/2019
       CE Mark
       Emission EMC tests   Radiated emissions                From 30 MHz to 1000 MHz (Class A).
                                                              From 150 kHz to 30 MHz (Class A).
                            EN 55011
                            Radiated emission
                                                              At 1 m from 10 kHz to 1000 MHz
                            ANSI C37.1)
                            Conducted emissions
                                                              Compliant with voltage fluctuations and flicker
                            EN 61000-3-3
                            Conducted emission                <1.5% Vpp voltage supply
                                                              from 1 kHz to 10 kHz.
                            ANSI C37.1
                            Harmonics limits
                                                              Class A
                            EN 61000-3-2, IEC 61000-4-7
       Immunity EMC tests   Radiated, radio-frequency
                                                              1 V/m/MHz from 10 kHz to 25 MHz (AM)
                            ANSI C37.1
                            Radiated, radio-frequency
                                                              35 V/m/MHz from 25 MHz to 1000 MHz (FM)
                            ANSI C37.90.2
                            EFT burst                         ±4 kV/5 kHz
                                                              AC or DC power and I/O lines (Level 4).
                            EN 61000-4-4
                                                              ±2 kV in
                            Surge
                                                              AC or DC power and ±1 kV in I/O lines
                            EN 61000-4-5                      (Level 3).
                            Common mode RF
                                                              10 VRMS from 150 kHz to 80 MHz (Level 3).
                            EN 61000-4-6
                            Magnetic field
                                                              30 A/m at 50 Hz (Level 4)
                            EN 61000-4-8
                            Pulse magnetic field
                                                              10 A/m at 50 Hz (Level 3)
                            EN 61000-4-9
                                                              0% voltage supply, 20 ms (Level 0):
                            Voltage drops and power faults    Special level:
                            EN 61000-4-11                          Voltage falls of 30% during 10 ms
                                                                   Voltage falls of 60% during 100 ms
                                                                   Voltage falls of >95% during 5000 ms
                            Oscillatory wave
                                                              Class III, ±2.5 kV/5 kHz (Level 3).
                            IEC 60255-22-1 (EN 61000-4-12).
                            Oscillatory wave
                                                              1 MHz at ±2.5kV
                            ANSI C37.90.1
       Electrical Safety    General requirements
                                                              Compliant with all the standard's requirements
                            EN 61010-1 and IEC 60255-1
                            Dielectric rigidity
                                                              Isolation >100 MΩ, 2 kVRMS
                            IEC 60255-5
                            Impulse voltage                   ±5 kV in AC or DC power
                                                              ±4 kV in I/O lines
                            IEC 60255-5
       Envirnmental tests   Cold
                                                              -40ºC during 16h (Cold start)
                            EN 60068-2-1:2007
                            Dry heat
                                                              +55 ºC during 16h
                            EN 60068-2-2:2007
                            Cyclic humid heat                 From 25 ºC to 55 ºC
                                                              with 95% RH, 2 cycles of 24 h.
                            IEC 60068-2-30
                                                   Pag 45
13/12/2019                         User Manual – SM_SER
Ordering Options
                          Pag 46
User Manual – SM_SER                                                 13/12/2019
Glossary
             A
             A: Ampere.
             AC: Alternate Current.
             AWG: American Wire Gauge.
             C
             ºC: Celsius degree.
             COM: Communication port.
             CPU: Central Processing Unit.
             D
             DC: Direct Current.
             DI: Digital Input.
             DO: Digital Output.
             E
             EMC: ElectroMagnetic Compatibility.
             G
             g: Gram.
             GPS: Global Positioning System.
             H
             Hz: Hertz.
             I
             IED: Intelligent Electronic Device.
             I/O: Input / Output.
             ISO 9001: International standard for Quality Systems.
             K
             kHz: Kilohertz.
             L
             LED: Light Emitting Diode.
                                                   Pag 47
13/12/2019                                                   User Manual – SM_SER
             M
             mA: Milliampere.
             MHz: Megahertz.
             m: Meter.
             mm: Millimeter.
             ms: Millisecond.
             N
             N/A: Non-Application.
             P
             PC: Personal Computer.
             PS: Power Supply.
             R
             RTU: Remote Terminal Unit.
             S
             s: Second.
             SFTP: Secure File Transfer Protocol.
             SM_DO16R: Digital Outputs to Relay module.
             SM_PS: Power supply module.
             SM_PS40: Power supply module.
             SM_SER: Communication module for expansion.
             V
             VAC: Volt of Alternate Current.
             VDC: Volt of Direct Current.
             W
             W: Watt.
                                                    Pag 48
 User Manual – SM_SER                                                                                                                                  13/12/2019
Index of Figures
Figure 1 – Barrier of protection for elements with dangerous voltages. ....................................................................... 9
Figure 2 – Yellow and Green cable for earthing. ........................................................................................................10
Figure 3 – Technical label. ..........................................................................................................................................12
Figure 4 – Saitel DP in Chassis and Backplane .........................................................................................................16
Figure 5 – Saitel DP architecture example .................................................................................................................16
Figure 6 – Saitel DP architecture example .................................................................................................................17
Figure 7 – Backplane positions...................................................................................................................................21
Figure 8 – Saitel DP module inserted incorrectly .......................................................................................................22
Figure 9 – FL-PP-RJ45-SC and VIP-3/PT/RJ45 ........................................................................................................26
Figure 10 – Termination resistor in full-duplex communications ................................................................................26
Figure 11 – Termination resistor in half-duplex communications ...............................................................................26
Figure 12 – Cable for connection SM_SER-Auxiliary terminal in full-duplex communications ..................................26
Figure 13 – Cable for connection SM_SER-Auxiliary terminal in half-duplex communications .................................27
Figure 14 – LED indicators .........................................................................................................................................27
Figure 15 – Adding new RTU .....................................................................................................................................31
Figure 16 – Add, remove or change I/O modules .......................................................................................................31
Figure 17 – Acquisition modules in the default configuration .....................................................................................31
Figure 18 – Adding one or several I/O modules. ........................................................................................................32
Figure 19 – Configuration parameters. .......................................................................................................................32
Figure 20 – Add configuration.....................................................................................................................................32
Figure 21 – Configuration mode. ................................................................................................................................33
Figure 22 – Configuration mode. ................................................................................................................................33
Figure 23 – SM_SER Channel Architecture ...............................................................................................................34
Figure 24 – Channel Setup .........................................................................................................................................34
Figure 25 – Disclaimer information .............................................................................................................................36
Figure 26 – Access screen. ........................................................................................................................................37
Figure 27 – Home tab .................................................................................................................................................37
Figure 28 – Monitoring and control view - System information ..................................................................................38
Figure 29 – Diagnostic View .......................................................................................................................................39
Figure 30 – Saitel webTool login window. ..................................................................................................................39
Figure 31 – Initial screen of Saitel webTool ................................................................................................................39
Figure 32 – PuTTY configuration ................................................................................................................................40
Figure 33 – SSH connection .......................................................................................................................................41
Figure 34 – SM_SER Main Menu ...............................................................................................................................42
Figure 35 – Channel Configuration .............................................................................................................................42
                                                                               Pag 49
 13/12/2019                                                                                                                              User Manual – SM_SER
Index of Tables
Table 1 – Symbols ........................................................................................................................................................ 8
Table 2 – Addressing the SM_SER module ...............................................................................................................23
Table 3 – Configuration switches................................................................................................................................23
Table 4 – RS-485 port pinout......................................................................................................................................24
Table 5 – RS-422 port pinout......................................................................................................................................25
Table 6 – RS-232 port pinout......................................................................................................................................25
Table 7 – Led indicators meaning..............................................................................................................................28
Table 8 – Upgrading SM_SER software. ...................................................................................................................41
                                                                                 Pag 50
 User Manual – SM_SER                                                                                                     13/12/2019
                                                                                                                             Printed in:
                                                                                                              Monday, February 17, 2020
Schneider Electric
C/ Charles Darwin s/n
Parque Científico y Tecnológico de la Cartuja
Seville, Spain
SE-M581-USR-02 02/2020
Pag 51