PowerLogic DO180
User Manual
BQT7945201-00
06/2024
www.se.com
Legal Information
             The information provided in this document contains general descriptions, technical
             characteristics and/or recommendations related to products/solutions.
             This document is not intended as a substitute for a detailed study or operational and
             site-specific development or schematic plan. It is not to be used for determining
             suitability or reliability of the products/solutions for specific user applications. It is the
             duty of any such user to perform or have any professional expert of its choice
             (integrator, specifier or the like) perform the appropriate and comprehensive risk
             analysis, evaluation and testing of the products/solutions with respect to the relevant
             specific application or use thereof.
             The Schneider Electric brand and any trademarks of Schneider Electric SE and its
             subsidiaries referred to in this document are the property of Schneider Electric SE or
             its subsidiaries. All other brands may be trademarks of their respective owner.
             This document and its content are protected under applicable copyright laws and
             provided for informative use only. No part of this document may be reproduced or
             transmitted in any form or by any means (electronic, mechanical, photocopying,
             recording, or otherwise), for any purpose, without the prior written permission of
             Schneider Electric.
             Schneider Electric does not grant any right or license for commercial use of the
             document or its content, except for a non-exclusive and personal license to consult it
             on an "as is" basis.
             Schneider Electric reserves the right to make changes or updates with respect to or in
             the content of this document or the format thereof, at any time without notice.
             To the extent permitted by applicable law, no responsibility or liability is
             assumed by Schneider Electric and its subsidiaries for any errors or omissions
             in the informational content of this document, as well as any non-intended use
             or misuse of the content thereof.
                                                                                                          PowerLogic DO180
Table of Contents
                Foreword ......................................................................................................5
                     Safety Information ......................................................................................5
                     EU Directives .............................................................................................6
                     Safety Instructions ......................................................................................6
                     About the book ...........................................................................................6
                General Description of DO180 ..................................................................8
                     PowerLogic T500 Platform ..........................................................................8
                     DO180 Module ...........................................................................................9
                     Software Processing................................................................................. 11
                     LED Indicators.......................................................................................... 11
                Physical Mounting and Installation .........................................................14
                     Installation ...............................................................................................14
                         Limits .................................................................................................14
                          Handling Modules ...............................................................................14
                          Module Location within the Chassis or Backplane..................................14
                          Power Supply Requirements................................................................15
                          Configuration Switches........................................................................15
                          Mounting Procedure............................................................................16
                     Wiring Recommendations for PowerLogic T500..........................................17
                     Wiring DO180 ..........................................................................................17
                          Terminal Connection (option C1) ..........................................................18
                          Flat Ribbon Connection (option C2)......................................................21
                Configuration and Maintenance..............................................................24
                     Configuration of the Backplane ..................................................................24
                     DO180 Configuration ................................................................................27
                          Local Acquisition Information ...............................................................28
                          DO180 Signals ...................................................................................28
                          Local Acquisition Coordinates ..............................................................29
                          coreDb Information for a DO180 Module...............................................30
                     Maintenance of Module.............................................................................32
                          webApp..............................................................................................32
                          Using webApp ....................................................................................32
                Appendix ....................................................................................................37
                     Technical Specifications ............................................................................37
                Glossary .....................................................................................................41
BQT7945201-00                                                                                                                    3
Foreword                                                                                        PowerLogic DO180
Foreword
Safety Information
Important Information
                 Read these instructions carefully, and look at the equipment to become familiar
                 with the device before trying to install, operate, service, or maintain it. The
                 following special messages may appear throughout this documentation or on the
                 equipment to warn of potential hazards or to call attention to information that
                 clarifies or simplifies a procedure.
                           The addition of this symbol to a “Danger” or “Warning” safety label indicates that an
                           electrical hazard exists which will result in personal injury if the instructions are not
                           followed.
                           This is the safety alert symbol. It is used to alert you to potential personal injury
                           hazards. Obey all safety messages that follow this symbol to avoid possible injury or
                           death.
                                                         !   DANGER
                 DANGER indicates a hazardous situation which, if not avoided, will result in death or serious
                 injury.
                                                     !       WARNING
                 WARNING indicates a hazardous situation which, if not avoided, could result in death or
                 serious injury.
                                                      !      CAUTION
                 CAUTION indicates a hazardous situation which, if not avoided, could result in minor or
                 moderate injury.
                                                             NOTICE
                 NOTICE is used to address practices not related to physical injury.
Please Note
                 Electrical equipment should be installed, operated, serviced, and maintained only
                 by qualified personnel. No responsibility is assumed by Schneider Electric for any
                 consequences arising out of the use of this material.
                 A qualified person is one who has skills and knowledge related to the construction
                 and operation of electrical equipment and its installation, and has received safety
                 training to recognize and avoid the hazards involved.
BQT7945201-00                                                                                                          5
PowerLogic DO180                                                                               Foreword
EU Directives
                   This equipment complies with the following Directives of the European Parliament
                   and of the Council:
                    •   EMC Directive 2014/30/EU
                    •   LVD Directive 2014/35/EU
                    •   RoHS Directive 2015/863/EU
Safety Instructions
                                                         DANGER
                    HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
                    •   Electrical equipment must be installed, operated, serviced and maintained
                        only by qualified personnel.
                    •   All safety instructions in the Operation Manual must be read, understood and
                        strictly followed, and the technical characteristics of the device must be
                        checked before installing or working on this equipment.
                    •   Do not work alone.
                    •   Apply appropriate personal protective equipment (PPE) and follow safe
                        electrical work practices. See NFPA 70E, NOM-029-STPS-2011, CSA Z462,
                        NFC 18–510 and UTE C18–510–1.
                    •   Turn off all power supplying this unit before working on or inside the
                        equipment. Consider all sources of power, including the possibility of back
                        feeding.
                    •   Before working on the equipment, check for hazardous voltage between all
                        terminals, including the protective earth ground. Always use a proper rated
                        voltage sensing device to confirm that the power is off.
                    •   Start by connecting the device to the protective earth ground and to the
                        functional ground.
                    •   To open a live current transformer secondary circuit, turn off the primary side
                        of the transformer and short-circuit the transformer secondary circuit.
                    •   Screw tight all terminals, even those not in use.
                    •   Set all devices, doors, and covers before turning on power to this unit.
                    Failure to follow these instructions will result in death or serious injury.
6                                                                                        BQT7945201-00
Foreword                                                                          PowerLogic DO180
Conformity
                 The PowerLogic T500 platform and all its components have been developed in
                 accordance with the requirements for a quality management system, complying
                 with the ISO 9001:2015 standard.
Related Documents
                  Product                                    Title of              Reference
                                                             documentation         number
                  Easergy Builder                            User Manual           SE-S856-MSS
BQT7945201-00                                                                                         7
PowerLogic DO180                                                            General Description of DO180
                   The PowerLogic T500 design has been optimized to meet the most demanding
                   requirements of multiple sectors:
                    •   Cost-efficiency, minimum downtime, and compliance with electrical safety,
                        electromagnetic compatibility and environmental standards.
                    •   Safety and reliability requirements for power, gas, water, residual water
                        supply, etc.
                    •   Centralized monitoring and control of geographically-distributed systems
                        which support hierarchical data acquisition and redundant networks.
                    •   Local monitoring and control with data sharing capabilities of plant-distributed
                        devices.
                    •   Quick troubleshooting by means of programmable automation execution.
                    •   Modular design: all I/O, power supply and communication modules have an
                        identical format.
8                                                                                       BQT7945201-00
General Description of DO180                                                                                                    PowerLogic DO180
XS280
                                                                                                                 Profibus-DP
                                         SCADA Client                                  HU280           HU280
                                                                                                                               I/O Modules
                                                                                        Control Modules                          DI180
                                                                                             IED                                 AI160
                                                                                             IED
                                                                                                                                 AX160
                                                                                             IED
                                        PowerLogic T500
                                   WebApp Tool/ WebUI Tool
                                Monitorization and Diagnostic Tool
DO180 Module
Interfaces & Functions
                               Internally, all modules are electrically connected to the backplane using a 48-pin
                               connector on the rear side. In relation to the field connection (external devices),
                               two connectors are located on the front side.
                               According to the DO180 part number, the following ordering options are available
                               for field connection:
                                •    Option C1: EMS74210: 24 Vdc relays with 3.81 mm terminal blocks.
                                •    Option C2: EMS74220: 24 Vdc relays with flat ribbon.
                               The DO180 module includes the following:
                                •    16 independent free-contact digital outputs (DO) in two independent blocks.
                                     Each DO can be configured as:
                                     ◦     Single: pulsed (fixed time) or preset (latched).
                                     ◦     Double: pulsed or preset.
                                •    All DOs are SPST (Single Pole Single Throw) or NO (Normally open).
                                •    External polarization of DO for each block. DO signals are polarized using
                                     24 Vdc.
                                •    Polarization level is monitored for each block.
                                •    A "Select before operate" command management system is used to control
                                     field operation.
                                •    Autocheck of DOs every time when the polarization is reset.
                                •    Commands are continuously supervised to prevent execution of outputs
                                     when an abnormal functioning mode is detected.
                                •    Address and communication rate in the bus are set using the microswitches
                                     located on the rear side.
                                •    20 LED indicators provide information about the status of the module and
                                     each DO.
                                •    The software in the module can be upgraded remotely, from the CPU.
                                •    Hot-swap functionality.
BQT7945201-00                                                                                                                                 9
PowerLogic DO180                                                                                               General Description of DO180
The following figure shows the functional blocks integrated in the DO180 module:
LEDs
Synchronization
Supervision Mechanism
Insulation Insulation
                    •                               I/O to the bus: Connection to the bus in the backplane to share information
                                                    with the CPU.
                    •                               LEDs: 36 LED indicators are available on the front side of the module which
                                                    provides information about the module and the output signals.
                    •                               Synchronization: The DO180 is synchronized by a message received from
                                                    the CPU that includes information about the time. The module is
                                                    synchronized with the synchronization source accuracy used for the CPU.
                    •                               Controller block: The controller block supports the following functions:
                                                    ◦   Parameter settings and control of the digital output blocks
                                                    ◦   Advanced digital outputs processing
                                                    ◦   Updating the Indications block with the module status information
                                                    ◦   Interface with the Profibus communication bus to connect with the CPU
                    •                               Digital outputs: The DO180 has two terminal connectors labeled as J1 and
                                                    J2 which allow the 16 digital outputs to be connected to the field devices.
                                                    Each block receives eight SPST signals with the following features:
                                                    ◦   Permanent output verification and automatic polarization test
                                                    ◦   Independent outputs
                                                    ◦   External polarization 24 Vdc
                                                    ◦   Maximum current per signal: 2 A, 30 Vdc (Ohmic load)
                                                    ◦   Output type: Form A. Contact rating: 5 A max, 75 W (Resistive load,
                                                        220 V), 20 W (Inductive load, 220 V, R/L: 20 ms).
                                                    ◦   Maximum simultaneous current per block 8 A (max. 4 latched outputs)
                                                    ◦   Galvanic isolation through optocoupler in polarization blocks and between
                                                        outputs and power: 2.2 kVrms
10                                                                                                                         BQT7945201-00
General Description of DO180                                                                       PowerLogic DO180
                               The following figure shows the breaking capacity of the relay depending on the
                               voltage level. This figure shows the information that is only applicable for direct
                               current and resistive load.
Software Processing
                               The DO180 manages standard digital signal controlled by a direct execution
                               command. They can operate as latched signals or pulsing variable pulse time.
                               These signals can be associated to simple or double points in coreDb.
                               The behavior of the system depends on the type of the signal. There are the
                               following types of signal:
                                •   Simple digital output
                                •   Double digital output
LED Indicators
                               The module integrates an auto check of the digital outputs that is performed when
                               powering the module or after a polarization interruption. This verification system
                               monitors polarization voltages, the general status of the module and
                               communication.
                               This information is shown through 20 LED indicators on the front of the module.
BQT7945201-00                                                                                                        11
PowerLogic DO180                                                      General Description of DO180
LED indicators
12                                                                                BQT7945201-00
General Description of DO180                                                                                                 PowerLogic DO180
   /    : On                                                                                           : Off
                                                      /    : Blinking
                         ST2
                                            The module is in communication with the CPU.           –
                          –          –      the configured address is incorrect.
                                            The module is not powered, or incorrect address        Check the power input to the backplane and
                                            is configured.                                         that the module is correctly inserted into the
                                                                                                   backplane connector.
    –                     –          –
                                                                                                   Check that the position of microswitches is
                                                                                                   correct and the address is the same as the
                                                                                                   one was assigned in the Easergy Builder tool.
                                            DIA LED lights briefly during startup. If it remains   Update the software and if the problem
                –         –          –      ON, this means an undesired event is detected          remains, contact the support service.
                                            in the firmware or during the startup process.
                                            The module is not operative (incorrect address         Check the polarization input.
                                            or type) and with missing polarization issue.(*)
                                                                                                   Check that the position of microswitches is
                                                                                                   correct and the address is the same which
                                                                                                   was assigned in the Easergy Builder tool.
                                            The autocheck did not work for DOx.                    Check the connection to the DO.(*)
                –         –
 (*) The verification test is done every time when the polarization is reset. If the problem is solved, the module returns to a normal state.
 While the problem is present, command execution is blocked.
BQT7945201-00                                                                                                                                       13
PowerLogic DO180                                                          Physical Mounting and Installation
Handling Modules
                                                      NOTICE
                    HAZARD OF ELECTROSTATIC DISCHARGE
                    •   Handle the module from the front side, as far as possible from the backplane
                        connectors.
                    •   Do not touch the pins of the module connector.
                    •   Keep the module in its antistatic bag or packaging box, when unused.
                    Failure to follow these instructions can result in equipment damage.
                                                      NOTICE
                    HAZARD OF INCORRECT EQUIPMENT OPERATION
                    •   Do not place the CPU next to PS280 power supply module.
                    •   Modules must be installed in vertical position.
                    Failure to follow these instructions can result in equipment damage.
                   Respect the following requirements to place the modules in the chassis or in the
                   backplane:
                    •   When using the PS280 power supply module, place it in slot 1 (left-hand
                        side). In redundant-power supply configurations, use slots 1 and 2 for both
                        power supply modules.
                        Other modules can be located in any position (slot) within the chassis.
                    •   Group the modules to minimize the adverse effects caused by noise and
                        heat.
                    •   Place modules, and specifically CPU modules, as far as possible from the
                        modules which operate at alternating currents or high currents.
                    •   If the system uses redundant CPUs, place both CPUs modules side by side in
                        the backplane.
14                                                                                         BQT7945201-00
Physical Mounting and Installation                                                                     PowerLogic DO180
Backplane positions
                                                                        NOTICE
                                      HAZARD OF INCORRECT WIRING OR SUPPLIED VOLTAGE
                                      •   Check that the voltage input for the backplane is 5.4 Vdc.
                                      •   Check that there is no reverse polarity.
                                      Failure to follow these instructions can result in equipment damage.
                                     The PS280 module supplies power to the modules connected to the backplane, as
                                     required. When using auxiliary power supplies, you need to scale them depending
                                     on the installed PowerLogic T500 modules.
                                     The consumption of all modules is added plus a safety margin (between 20% and
                                     50% of the full power). The power supply efficiency, typically, 70 - 90%, is also
                                     considered to protect the chassis and power supply from overloading.
                                     The maximum power requirement for each DO180 module is:
                                      •   Main power supply : Basic consumption (as indicated in the technical
                                          specifications table at the end of the manual).
                                      •   Polarization supply: 16 x Maximum consumption per signal. Polarization
                                          voltage and maximum current per signal are indicated in the technical
                                          specifications table at the end of the manual.
                                          NOTE: The data is available in the Technical Specification Table at the end of
                                          this manual, page 37.
Configuration Switches
                                     The module identification and Profibus communication speed can be set using the
                                     microswitches on the module rear panel.
BQT7945201-00                                                                                                          15
PowerLogic DO180                                                         Physical Mounting and Installation
                           4         Profibus address
                           5
                           6
                           8      Reserved
                           9
                          10          Profibus speed
                          11
12 Reserved
                         NOTE: For optimal system performance, set the Profibus rate to 1.5 Mbaud.
                         NOTE: Microswitches 8 and 12 are reserved and must be set to OFF.
Mounting Procedure
                   PowerLogic T500 modules can be installed in a 19-inch chassis (BP270) or a
                   backplane (BP260).
                   The BP260 can detect an incorrect installation of the modules. However, some
                   configurations can work correctly even though the modules are not mounted
                   correctly. This situation creates a mechanical instability and might cause serious
                   problems.
16                                                                                           BQT7945201-00
Physical Mounting and Installation                                                                     PowerLogic DO180
                                                                        NOTICE
                                      HAZARD OF INCORRECT MOUNTING OF MODULES
                                      Ensure that configurations are working correctly and modules are mounted
                                      correctly.
                                      Failure to follow these instructions can result in equipment damage.
                                     The following figure shows two modules inserted on the backplane. One of the
                                     modules is incorrectly inserted but this does not prevent its functioning.
                                     PowerLogic T500 module incorrectly inserted on the left (shown with the red
                                     ellipsis) and module correctly inserted on the right
                                     To mount the module in the chassis or backplane, follow the instructions below:
                                      1. Switch off the power supply.
                                      2. Mount the module at the desired position, and if you are using a backplane,
                                         verify that the rear rails are properly mounted using the pre-drilled holes on
                                         the backplane.
                                      3. Firmly press the module to ensure that the connector fits in to the backplane
                                         connector properly. Check the module is correctly mounted onto the
                                         backplane base.
                                      4. Fix the module using the screw located at the top.
                                      5. Insert the terminal (mounting option C1) or flat ribbon connectors (mounting
                                         option C2).
Wiring DO180
                                     A module can be easily replaced by disconnecting the two field-connectors and
                                     removing the module from its slot.
                                     This section provides information about signals field connection, polarization and
                                     commons.
BQT7945201-00                                                                                                             17
PowerLogic DO180                                                          Physical Mounting and Installation
                   Where:
                    •   DO xx: Digital Output xx
                    •   NC: No connected
                    •   Mi: Command i
                    •   +V1 and +V2: Terminal for polarization positive
                    •   -V1 and -V2: Terminal for polarization negative
                   All digital outputs in this module are SPST or NO contact.
SPST contact
18                                                                                         BQT7945201-00
Physical Mounting and Installation                                                                     PowerLogic DO180
DO 01
DO 01
DO 08
DO 08
+V1
-V1
                                                  -              +
                                                       External
                                                      polarization
                                      •   To make the connection, strip between 8 and 10 cm off the cable end, and
                                          protect it with an insulating material as shown in the following figure:
                                      •   The shield at the end of each individual cable is removed for a distance of 0.5
                                          cm, which is the part of copper to introduce in the terminal.
BQT7945201-00                                                                                                          19
PowerLogic DO180                                                         Physical Mounting and Installation
                   Once the module is installed in the cabinet, to avoid jerking and the cable fall on
                   the terminal, due to their weight, join both cables with a plastic bracket. Then fix
                   them to the cabinet or the chassis.
Polarization
                   The digital outputs need a polarization voltage for operation.
20                                                                                        BQT7945201-00
Physical Mounting and Installation                                                                      PowerLogic DO180
                                     The 16 outputs of the DO180 module are divided into two 8-input polarization
                                     blocks. Each block can be polarized independently but both must have the same
                                     value.
                                     The polarization of V1 and V2 voltages is supplied externally from the module.
                                     Even if two power supplies are available, use only one power supply by bridging
                                     the terminals. The terminal +V1 in connector B1 must be interconnected with the
                                     terminal +V2 in connector B2 and the terminal -V1 in B1 with the terminal -V2 in
                                     B2.
BQT7945201-00                                                                                                            21
PowerLogic DO180                                                                                    Physical Mounting and Installation
                                                 TB_DO16
                                                                     DO01
                                                   1
                                                                      DO08
                                                  16
                                                                      +Vx
                                           VP+                        +Vx
                                                                       -Vx
                                                 VP-                   -Vx
                        +                    -
                             External                                      Wiring to field
                            Polarization
                                                                           Internal wiring
Specification Description
Dimensions 65 x 45 x 194 mm
22                                                                                                                   BQT7945201-00
Physical Mounting and Installation                                                                     PowerLogic DO180
Specification Description
Electrical Diagram
                                     TB_DO16/N - TO180/P0 – Electrical diagram – Phöenix Contact
BQT7945201-00                                                                                                                 23
PowerLogic DO180                                                         Configuration and Maintenance
                   Click   next to the graphic of the backplane to add, remove or change the IO
                   modules included on the default configuration.
24                                                                                    BQT7945201-00
Configuration and Maintenance                                                                  PowerLogic DO180
Configuring backplane
                                 1. Using this window, add or remove a module in the backplane. Use      to add
                                    new modules and       to remove a module.
                                 2. Change the address for each module displayed under its image using       .
                                    The address for each module must be the same that is indicated with its rear
                                    switches.
Change address
BQT7945201-00                                                                                                  25
PowerLogic DO180                                                           Configuration and Maintenance
3. Use to configure the time parameters of the polling and digital filtering.
Profibus configuration
                   4. To create a new configuration, use       or select RTU in the tree and right-
                      click.
New configuration
                      If Create defined RTU acquisition points field is checked, all points of the
                      local acquisition of the acquisition blocks included in the default configuration
                      associated with the RTU are included in coreDb.
                      For example, if an HU280 is mounted in a backplane with an acquisition
                      module and Create defined RTU acquisition points is checked, the
                      following points are generated:
                       •    Corresponding inputs, if available, in the Analog or Status table
                       •    Corresponding outputs, if available, in the Commands table
                       •    Supervision point for each block
                      At the end of the operation, the new configuration appears in the RTU tree.
                      Double-click it, so that the Easergy Builder tool goes into configuration mode.
                      Within the configuration, double-click on the laq icon to change the address of
                      the modules.
26                                                                                       BQT7945201-00
Configuration and Maintenance                                                                    PowerLogic DO180
DO180 Configuration
                                The local acquisition device for PowerLogic T500 is named as laq and it is created
                                by default for each PowerLogic T500 configuration.
                                The first step to configure the acquisition is to ensure that the configured
                                backplane in the graphical interface is according to the system. Each module must
                                be addressed according the position of its microswitches. Refer Configuration
                                Switches, page 15.
                                The laq device supports communication between inputs and the outputs managed
                                by the acquisition blocks and coreDb points. To configure the acquisition settings,
                                include all IO modules in the backplane.
                                   NOTE: The graphical interface does not show if the modules are mounted in
                                   one or multiple backplanes. Communication and power supplies modules are
                                   not included in the graphical schematic.
BQT7945201-00                                                                                                   27
PowerLogic DO180                                                                  Configuration and Maintenance
coreDb
                                                DO180
                                                Module
Address: 1
                                                                          Field
                           Digital Output            Name     Coordinate
                                   D1            DO_SIM_1       2001050000
                                   D2            DO_SIM_2       2001050001
                   In the example above, all signals are simple. If a signal is configured as double or
                   counter, its default name must be different.
DO180 Signals
                   The following figure shows the configuration panel when the backplane is
                   composed of a CPU HU280 and one DO180 module with address 6:
Output signals
Select the module on the screen. All digital outputs are displayed.
28                                                                                             BQT7945201-00
Configuration and Maintenance                                                                          PowerLogic DO180
                                The first field of each row specifies the description of the signal (DO_SIM_1 .. DO_
                                SIM_8). In coreDb, each signal is identified using its coordinate.
                                For each signal, the following parameters can be changed:
                                 •   Type of signal: there are two types of signals:
                                     ◦   Simple digital output (DO_SIM)
                                     ◦   Double digital output (DO_DOB)
                                 •   Latch: the possible values are Y or N.
                                     ◦   Y indicates that the signal is latched, that is, the associated command is
                                         permanent over time.
                                     ◦   N indicates that the signal is temporary, that is, the command is retained
                                         for the time indicated in ExeTim field.
                                 •   ExeTim: only available for signals that are not latched. Command timeout
                                     (ms). After this time, the command is deactivated.
                                If any signal is set to a double digital signal, the next signal available is disabled
                                because a double signal takes two signals. The following figure shows the signal
                                DO_DOB_2 configured as double:
                                Click Next button to display all the digital outputs of the module, that is, from 9 to
                                16.
BQT7945201-00                                                                                                         29
PowerLogic DO180                                                            Configuration and Maintenance
                   The following figure shows digital outputs of the DO180 module in the command
                   table:
                   The coordinate is a unique identifier of a signal within a device. For digital outputs,
                   the coordinate is indicated as destination, with the following syntax:
                   2 BBB CC DDDD
                    •   2: digit that specifies coordinate for all PowerLogic T500 local acquisition
                        signals. It is always 2.
                    •   BBB: three digits to indicate the point address according to the
                        communication protocol. In the case of Profibus-DP, the address ranges from
                        000 to 125.
                    •   CC: type of signal:
                        ◦   00: diagnostic signals of the acquisition modules
                        ◦   05: simple digital output (1 bit)
                        ◦   15: double digital output (2 bits)
                    •   DDDD: incremented number of the signal within each type. It does not match
                        the physical position. The first signal of a type is 0000, the second is 0001
                        and so on.
                   For example, if a coreDb point has associated the signal 2003050002 as
                   destination, then it means that this point of coreDb executes a single command
                   (05) on signal (0002) of the module with address 003, according to Profibus-DP
                   (2) protocol.
30                                                                                        BQT7945201-00
Configuration and Maintenance                                                                     PowerLogic DO180
                                 •   The following diagnostic points are created in the status table for each D00x
                                     module:
                                     ◦   D00x_STS_COMM: associated coordinate 200x000000 (as source). The
                                         value indicates with status of the module. Value 1 means that the CPU
                                         cannot communicate with the D00x module.
                                     ◦   D00x_STS_DIAG: associated coordinate 200x000001 (as source). The
                                         value indicates the diagnostics for the module. Value 1 means that the
                                         module indicates a problem (diagnostic). Usually this status corresponds
                                         to a missing polarization.
                                     ◦   D001_STS_FAILBUS1: associated coordinate 200x000003 (as source).
                                         The value indicates if a communication interruption in bus 1 has been
                                         detected. Value 1 indicates a communication interruption in Profibus 1.
                                     ◦   D001_STS_FAILBUS2: associated coordinate 200x000004 (as source).
                                         The value indicates if a communication interruption in bus 2 has been
                                         detected. Value 1 indicates a communication interruption in Profibus 2.
                                To include a point manually, create a new point, select laq as Source Device,
                                click the right-button on the Source Coordinates field and select Launch Point
                                wizard:
                                Select the module in which you need to create these points and then select the
                                point to be created from the Point needed area.
                                     NOTE: The points that are not created are shown in the Point needed list.
                                You can include these points directly in coreDb.
                                For example, if a coreDb point has assigned the signal 2003000000 as source,
                                the value of this point indicates the communication status of the module 003
                                (address).
                                The value of the signal 2007000004 changes to 1 when the communication with
                                the module 007 is lost.
                                For additional information regarding coreDb and operation with signals, refer to
                                the Easergy Builder user manual.
BQT7945201-00                                                                                                      31
PowerLogic DO180                                                         Configuration and Maintenance
Maintenance of Module
webApp
                   The webApp is a set of remote user interfaces for consulting, monitoring and
                   maintenance tasks. Once the username and password have been entered, you
                   can access the main window and, depending on the webtool, several sections are
                   available.
                   webApp is used with the HU280 module.
                        NOTE: webApp has been designed to work only with the cyber security brick.
                        This functionality is not available in systems that do not include the cyber
                        security brick and does not work in systems without the external web server
                        either. The pages are loaded dynamically according to the users roles.
                   When you use webApp, the following message appears before the tool is
                   accessed:
Disclaimer information
Using webApp
                   PowerLogic T500 webApp has an access control that gives access only to
                   authorized users. To get to the window access, enter https://< CPU IP
                   address> in the navigation address bar, where <CPU IP address> must be
                   changed for the correct IP address.
Access screen
                   Enter the Username and Password to access the webApp main window.
                   The webApp main window screen has five tabs:
                    •   Home
                    •   Monitoring & Control
                    •   Diagnostic
32                                                                                    BQT7945201-00
Configuration and Maintenance                                                                      PowerLogic DO180
                                 •   Maintenance
                                 •   Settings
Home Tab
                                Home tab
                                 •   Image associated with the RTU. Click      on the graphic zone to include a
                                     location map corresponding to the GPS coordinates.
                                 •   Notes. This zone allows you to include notes that are shown to other users.
BQT7945201-00                                                                                                      33
PowerLogic DO180                                                           Configuration and Maintenance
                   The Monitoring & control > Data window allows you to monitor the information of
                   each coreDb table:
                    •   Status page: for viewing the status of the digital data.
                    •   Command page: for sending the change of state commands based on the
                        digital data.
                    •   Analog page: for viewing measurement values.
                    •   Setpoint page: for forcing parameter values.
Command information
34                                                                                      BQT7945201-00
Configuration and Maintenance                                                                               PowerLogic DO180
Edit value
                                If you set the value to 1, press OK button, a command is sent to the field, latched
                                or pulsed depending on the configuration of the local acquisition signal.
                                For each signal, the quality information is shown in the table through icons in the
                                Quality column. In coreDb, this information is stored in hexadecimal format.
                                The quality information associated with a signal could include one or more of the
                                following messages:
                                 0x00000000                         OK
                                 0x00000001                         There has been an overflow.
                                 0x00000002                         There has been a carry on a counter or a roll-over.
                                 0x00000040                         The point has not yet been written into the database (No
                                                                    refresh).
0x00000100 The value of the item has exceeded Highest Limit Alarm.
0x00000200 The value of the item has exceeded High Limit Alarm.
BQT7945201-00                                                                                                              35
PowerLogic DO180                                                              Configuration and Maintenance
0x00000400 The point value of the Low Limit Alarm has decreased.
                    0x00000000                               OK
                    0x00010000                               There was an overflow.
                    0x00020000                               There was a carry on a counter or a roll-over.
                      NOTE: If more than one event is detected for a signal, the hexadecimal value
                      monitored for quality bits results from the sum of all. For example:
                      0x00000001 indicates that an overflow occurred and 0x00000002 indicates
                      that there was a carry on a counter or a roll-over. The value 0x00000003 is
                      monitored.
36                                                                                           BQT7945201-00
Appendix                                                                              PowerLogic DO180
Appendix
Technical Specifications
Hardware
                Specifications                           Description
Number of outputs 16
                Imax
                                                         C1 Option: 2 A per output 30 Vdc (Resistive
                                                           load)
                                                         C2 Option: 0.5 A per output 30 Vdc (Resistive
                                                           load)
                Transient voltage protection (outputs)   Peak pulse power dissipation 600 W on 10/1000
                                                         µs waveform. Bidirectional
Weight 740 g
Software
                Specifications                           Description
Single / Double
BQT7945201-00                                                                                            37
PowerLogic DO180                                                                                                                 Appendix
Standard Compliance
 Directive / Test                                  Identification                          Details
 European and British Directives
CISPR 32:2015+A1:2019
                                                   EN 55022:2011
 Continuous conducted emission on power            EN 55032:2015 / AC:2016-07              0.15 MHz to 30 MHz
 leads
                                                   CISPR 16-2-1:2014 / AMD1:2017
                                                   CISPR 32:2015+A1:2019
 EMC - Immunity tests
 Radiated RF Electromagnetic field immunity        EN 61000-4-3:2006 / A1:2008 / A2:2010   80 – 6000 MHz, AM 1 kHz Prof: 80%, 10 V/
 test                                                                                      m
Electrical fast transient / burst immunity test IEC 61000-4-4:2012 ±4 kV, 5 kHz
Power frequency magnetic field immunity test IEC 61000-4-8:2010 50 Hz, 100, 30, 3 A/m continuous
 Electrostatic discharge immunity test             IEC 61000-4-2:2009                      ±4 kV, ±6 kV (direct and indirect contact
                                                                                           discharge)
38                                                                                                                     BQT7945201-00
Appendix                                                                                                      PowerLogic DO180
Applies to PS280
100, 300 V 1 s
 Gradual shut-down / start-up (dc power          60255-26:2013 (Clause 7.2.13)      Shut-down ramp, 60 s
 supply)
                                                                                    Power-off, 5 min
Start-up ramp, 60 s
Electrical Safety
Pollution degree 2
 Environmental tests
 Cold test                                       IEC 60068-2-1:2007                 Test Ad (-40 ºC / 16 h)
Test Ab (-40 ºC / 72 h)
Test Bb (+80 ºC / 72 h)
 Damp heat, cyclic test                          IEC 60068-2-30:2005                +25 ºC / +55 ºC, 93 % RH / 96 % RH, 6
                                                                                    cycles (24 h)
Damp heat steady state test IEC 60068-2-78:2001 Test Cab 93% / +40 °C / 10 days
                                                 IEC 60255-21-3:1988
 Drop test                                       IEC 60068-2-31 :2008               1 m (with packaging)
ISO 4180:2019
Ordering Options
                                      Two options are available for field connection:
                                        •   Option C1: EMS74210: 24 Vdc relays with 3.81 mm terminal blocks.
                                        •   Option C2: EMS74220: 24 Vdc relays with flat ribbon.
BQT7945201-00                                                                                                                      39
                                                                                   PowerLogic DO180
Glossary
                A
                A: ampere. Base unit of electric current in the International System of Units.
                B
                BP260: PowerLogic T500 backplane.
                C
                CPU: Central Processing Unit.
                D
                DC: direct current.
                E
                EMC: Electro Magnetic Compatibility.
                G
                g: gram.
                H
                HU280: PowerLogic T500 CPU module.
BQT7945201-00                                                                                    41
PowerLogic DO180
                   I
                   I/O: Input/Output.
                   K
                   kB: kilobyte.
kHz: kilohertz.
                   L
                   LAN: Local Area Network.
                   M
                   mA: milliampere.
MB: megabyte.
MHz: megahertz.
m: meter.
mm: millimeter.
ms: millisecond.
                   N
                   N/A: not applicable.
                   P
                   PC: Personal Computer.
PWR: power.
                   R
                   RAM: Random Access Memory.
Rx: reception.
42                                                            BQT7945201-00
                                                                                PowerLogic DO180
                S
                SCADA: Supervisory Control And Data Acquisition.
s: second.
                T
                TCP or TCP/IP: Transmission Control Protocol/Internet Protocol. Set of protocols
                 used to transfer data on the Internet.
Tx: transmission.
                V
                VAC: Voltage of Alternate Current.
                W
                W: watts.
                X
                XS280: PowerLogic T500 serial communication module.